Abstract— Demands of renewable energy are increasing due to its effectiveness and sustainability.
However, this energy source depends much on the weather and is unstable. Therefore, it needs to be
connected to the power network via grid-connected inverters using power electronics devices. The power
quality of inverter outputs depends much on the control strategy and modulation. The conventional control
methods such as the proportional-integral (PI) and proportional resonance (PR) use the control loops and
depend on the controller coefficients. The hysteresis current control method offers the best dynamic
response. However, its switching frequency is very difficult to control. This paper presents a method basing
on the model predictive control. In the proposed method, the inverter switching states are optimally chosen
to minimize the cost function. This helps inverters reduce the switching counts while ensuring the low
output harmonics. Thus, this can help inverters decrease the switching loss. The simulation results on
Matlab/Simulink have validated the effectiveness of the proposed control method compared with that of the
hysteresis current one.
Keywords— Grid-connected inverters, current harmonics, PR control, hysteresis control, model
predictive control.
www.ijaems.com Page | 26
Quang-Tho Tran et al. International Journal of Advanced Engineering, Management and Science, 7(3)-2021
cause overcurrent for IGBTs due to the high overshoot. Grid Anti-
Va Vb vc Cf Ia Ib Ic
islanding
Moreover, the digital control platforms basing on control PLL
DSPs become very popular due to the semiconductor
technology development and suitable for the discrete Vmax
Ia
Ia-ref - HC
control. This helps the digital control methods increase Vmax Q Iq_ref =0 + controller
profile dq Ib
advantages. In which, a method basing on the model
Ib-ref - HC
prediction will promote these benefits. The method of + controller
Ic-ref - HC
control loops. However, the MPC in [13] has not been + controller
www.ijaems.com Page | 27
Quang-Tho Tran et al. International Journal of Advanced Engineering, Management and Science, 7(3)-2021
g = f ( x ( k ) , u ( k ) ,..., u ( k + N ) )
(2)
N = x =2 =8 y 3
(3)
Then, the cost function of the current control using the
MPC will be defined as follows.
g = ia* ( k + 1) − iap ( k + 1) + ib* ( k + 1) − ibp ( k + 1)
(4)
Where ia ( k + 1) and ib ( k + 1) are the real and image of
* *
www.ijaems.com Page | 28
Quang-Tho Tran et al. International Journal of Advanced Engineering, Management and Science, 7(3)-2021
V=
3 dt
+
3
( ia + pib + p 2ic ) Begin
i=
2
3
( ia + pib + p 2ic )
ê(k)=V_old-(L/Ts)*i(k)-(R-L/Ts)*i_old
(10)
e=
2
3
(Vga + pVgb + p 2Vgc )
(11) N=0
And assume that
(V nN + pVnN + p 2VnN ) = VnN (1 + p + p 2 ) = 0
(12) N=N+1
Then, the inverter output voltage will be as follows.
di
V = Ri + L +e Ip(k+1)=(1-RTs/L)*i(k)+(Ts/L)*(V(k)-ê(k))
dt (13) Calculate S
The derivative of the current in the discrete domain with
the sampling cycle Ts according to the forward Euler
method will be as follows.
g=|i*a-ipa|+|i*b-ipb|+Lamda*S
di i ( k + 1) − i ( k )
dt Ts (14) No
The predictive current at the time k+1 will be as. g<g_opt?
RT T
Yes
i p ( k + 1) = 1 − s i ( k ) + s V ( k ) − e ( k )
L L (15) g_opt=g
Yes
Apply
optimal v(k)
www.ijaems.com Page | 29
Quang-Tho Tran et al. International Journal of Advanced Engineering, Management and Science, 7(3)-2021
www.ijaems.com Page | 30
Quang-Tho Tran et al. International Journal of Advanced Engineering, Management and Science, 7(3)-2021
V. CONCLUSION
This paper has presented a method using the model
predictive control for three-phase grid-connected inverters.
An algorithm for reducing the number of switching
commutations is also proposed by including the weight
Fig. 15: Switching counts of the HC and MPC with =0
factor in the cost function of the MPC. The simulation
models of the MPC and HC methods built on
Matlab/Simulink are used for verifying the proposed
The current total harmonic distortions of the HC control
algorithm.
are 2.42 % and 4.79 %. These values are higher than those
The performance of the proposed MPC method has also
of the MPC one, 2.26 % and 4.55 % respectively.
been validated when comparing the simulation results of
Moreover, the fundamental current magnitude of the MPC,
the MPC with those of the HC one. The current harmonics,
as 39.96 A and 20 A, are higher than those of the HC one,
the number of switching commutations, overshoot, and
as 39.72 A and 19.76 A respectively. This helps increase
settling time are also considered quantitively.
the generation efficiency of the inverters.
In addition, the number of switching commutations in each
ACKNOWLEDGEMENTS
fundamental period in Fig. 15, with =0, has showed that
This work belongs to the project grant No: T2020-21TĐ
the switching counts of the MPC in the black are lower
funded by Ho Chi Minh City University of Technology
than 80. While those of the HC method in the red are
and Education, Vietnam.
always higher than 80.
REFERENCES
[1] R. Teodorescu, M. Liserre, and P. Rodriguez, Grid
Converters for Photovoltaic and Wind Power Systems.
2011.
[2] S. Lakhimsetty, V. S. P. Satelli, R. S. Rathore, and V. T.
Somasekhar, “Multilevel Torque Hysteresis-Band based
Direct-Torque Control Strategy for a Three- Level Open-
End Winding Induction Motor Drive for Electric Vehicle
Applications,” IEEE J. Emerg. Sel. Top. Power Electron.,
vol. 7, no. 3, pp. 1969–1981, 2019.
Fig. 16: Switching counts of the HC and MPC with =0.01 [3] S. Madanzadeh, A. Abedini, A. Radan, and J.-S. Ro,
“Application ofquadratic linearization state feedback
control with hysteresis reference reformer to improve the
When considering the reduction of switching count with dynamic response of interior permanent magnet
synchronous motors,” ISA Trans. J., vol. 99, pp. 167–190,
the weight factor =0.01, the number of switching
2020.
commutations of the MPC, in the blue in Fig. 16, is always
[4] Y. Xue et al., “Vector-Based Model Predictive Hysteresis
lower than 65. Although the number of switching Current Control for Asynchronous Motor,” IEEE Trans.
commutations of the MPC is lower than those of the HC, Ind. Electron., vol. 66, no. 11, pp. 8703–8712, 2019, doi:
the current THD of the MPC is still lower than that of the 10.1109/TIE.2018.2886754.
HC in Fig. 17. [5] S. J, A. S, and R. Ramchand, “Current Error Space Vector
Based Hysteresis Controller for VSI Fed PMSM Drive,”
IEEE Trans. Power Electron., vol. 35, no. 10, pp. 10690–
www.ijaems.com Page | 31
Quang-Tho Tran et al. International Journal of Advanced Engineering, Management and Science, 7(3)-2021
10699, 2020.
[6] A. Narendran and R. Sureshkumar, “Hysteresis-controlled -
landsman converter based multilevel inverter fed induction-
motor system using PIC,” Microprocess. Microsyst., vol.
76, 2020.
[7] R. Viswadev, A. M, V. V. Ramana, B. Venkatesaperumal,
and S. Mishra, “A Novel AC Current Sensorless Hysteresis
Control for Grid-tie Inverters,” IEEE Trans. Circuits Syst.
II Express Briefs, vol. 67, no. 11, pp. 2577–2581, 2020.
[8] M. Kale, E. Ozdemir, and Electrical, “An adaptive
hysteresis band current controller for shunt active power
filte,” Electr. Power Syst. Res., vol. 73, pp. 113–119, 2005.
[9] J. C. Das, “Power system harmonics,” in Power System
Harmonics and Passive Filter Designs, New Jersey: John
Wiley & Sons, 2015, pp. 11–16.
[10] IEEE, “IEEE Recommended Practice for Utility Interface
of Photovoltaic (PV) Systems,” IEEE Std 929-2000. 2000,
doi: 10.1109/IEEESTD.2000.91304.
[11] IEEE Standard, “IEEE Application Guide for IEEE Std
1547(TM), IEEE Standard for Interconnecting Distributed
Resources with Electric Power Systems,” IEEE Std 1547.2-
2008, no. April, pp. 1–217, 2009, doi:
10.1109/IEEESTD.2008.4816078.
[12] J. Cheng, CEng, CEM, CEA, and CMVP, “IEEE Standard
519-2014,” Schneider Electric. p. 50, 2014.
[13] M. B. Shadmand, R. S. Balog, and H. Abu-Rub, “Model
predictive control of PV sources in a smart DC distribution
system: Maximum power point tracking and droop
control,” IEEE Trans. Energy Convers., vol. 29, no. 4, pp.
913–921, 2014, doi: 10.1109/TEC.2014.2362934.
[14] J. Yuan, Y. Yang, P. Liu, and F. Blaabjerg, “Model
Predictive Control of An Embedded Enhanced-Boost Z-
Source Inverter,” 2018 IEEE 19th Work. Control Model.
Power Electron. COMPEL 2018, vol. 2, no. 3, pp. 1–6,
2018, doi: 10.1109/COMPEL.2018.8459954.
[15] J. M. C. Geldenhuys, H. Du Toit Mouton, A. Rix, and T.
Geyer, “Model predictive current control of a grid
connected converter with LCL-filter,” 2016 IEEE 17th
Work. Control Model. Power Electron. COMPEL 2016,
2016, doi: 10.1109/COMPEL.2016.7556734.
[16] D. Sankar and C. A. Babu, “Model predictive control of
five level cascaded H bridge multilevel inverter for
photovoltaic system,” Proc. 2016 Int. Conf. Cogener. Small
Power Plants Dist. Energy, ICUE 2016, no. September, pp.
14–16, 2016, doi: 10.1109/COGEN.2016.7728946.
[17] P. Ghani, A. A. Chiane, and H. M. Kojabadi, “An adaptive
hysteresis band current controller for inverter base DG with
reactive power compensation,” in PEDSTC 2010 - 1st
Power Electronics and Drive Systems and Technologies
Conference, 2010, pp. 429–434, doi:
10.1109/PEDSTC.2010.5471776.
[18] J. Rodriguez and P. Cortes, Predictive control of power
converters and electrical drives. John Wiley & Sons, Ltd.,
Publication, 2012.
www.ijaems.com Page | 32