You are on page 1of 11

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO.

5, SEPTEMBER/OCTOBER 2019 5289

Dual Operation Mode of a Transformerless H-Bridge


Inverter in Low-Voltage Microgrid
Qusay Salem , Libo Liu, and Jian Xie

Abstract—This paper presents the bilateral operation of a as a distributed static series compensator where a new control
transformer-less H-bridge inverter as a power flow controller method is used to minimize the exchange of active power be-
and fault current limiter in low-voltage distribution network. tween the power system and the distributed synchronous series
A novel control strategy has been developed to initiate and ac-
tivate the H-bridge inverter to control the power flow at point compensator (DSSC). In [8], active and reactive power con-
of common coupling (PCC). On the other hand, the H-bridge trol of an H-bridge inverter connected in series to the distribu-
inverter operation like a short-circuit current limiter during grid tion grid has been controlled by a novel control method that
disturbance event and its smooth reinsertion after fault clearance needs no information about the line parameters. Furthermore,
have also been clarified. Besides, an island mode control strategy Saradarzadeh et al. [9] have modeled the H-bridge inverter as
incorporating synchronization controller, and proper coordination
with flip flops have been implemented in order to synchronize the a multilevel cascaded topology where a fixed and variable dc-
microgrid with the main grid before reclosing the circuit breaker. bus control methods are employed to control the power flow
The results confirm: The effectiveness and feasibility of the novel between two feeders. Also, the cascaded H-bridge inverter has
control methodology in activating the real power flow; the inverter been introduced in [10] as a power flow controller by implement-
capability of minimizing the short-circuit current during fault and ing a hierarchical control strategy with multiple control loops.
the successful resynchronization of the microgrid voltage source
inverter (VSI) and the H-bridge inverter to the main grid. However, the usage of the H-bridge inverter as a single phase
transformerless inverter has been introduced only in [11] to con-
Index Terms—Fault current limiter, microgrid, power flow con-
troller, resynchronization, transformer-less H-bridge inverter. trol the bidirectional power flow between the main grid and a
designated microgrid in the low-voltage distribution network.
Two novel control strategies have been used to control the in-
I. INTRODUCTION
verter operation and the dc-link capacitor was supposed to be
OWER flow controllers-based power electronics are form-
P ing the core of most flexible ac transmission systems
(FACTS) devices applications in power systems [1], [2]. These
pre-charged where an external voltage source is used to charge
the dc-link capacitor. However, to reduce the cost and number of
components, the inverter activation in this paper is accomplished
FACTS devices employ voltage source converters (VSCs) to by implementing a novel control strategy which facilitates the
perform the real or reactive power support according to system charging process without the need of supplementary devices.
needs [3]. One of the most common topologies of the VSCs is The benefit of the new control strategy over the existing ones
the H-bridge either if the switches employ insulated-gate bipo- is that no additional equipment is needed to charge the dc-link
lar transistors (IGBTs) or MOSFETs. Moreover, the H-bridge as a voltage of the inverter. Besides, the transient effect of the power
VSC has been extensively utilized in the design of the static syn- and/or current at point of common coupling (PCC) during the in-
chronous series compensator (SSSC) for power flow and voltage verter insertion process is significantly reduced since the inverter
regulation purposes especially in high and medium voltage net- is activated at zero net-power and thus, the inverter components
works [4]–[6]. In distribution networks, the H-bridge inverter has will be protected.
been rarely used to control the power flow transfer between two Furthermore, one of the main crucial problems concerning the
networks. In [7], the authors introduced the H-bridge inverter microgrid development is the increase of the fault current level.
Ensuring the reliability and stability of microgrids operation
when faults occur in the utility grid side is considered as a chal-
Manuscript received December 27, 2018; revised March 8, 2019 and April
14, 2019; accepted May 15, 2019. Date of publication May 19, 2019; date of lenging issue. So that, the strategies that can mitigate the short-
current version August 14, 2019. Paper 2018-IACC-1398.R2, presented at the circuit current and hence, prohibit the isolation of the microgrid
2018 IEEE International Conference on Environment and Electrical Engineer- from the main utility grid are of great significance [12]–[15]. The
ing and 2018 IEEE Industrial and Commercial Power Systems Europe, Palermo,
Italy, Jun. 12–15, and approved for publication in the IEEE TRANSACTIONS ON islanding detection techniques are provided to detect the island
INDUSTRY APPLICATIONS by the Industrial Automation and Control Commit- event and to perform the disconnection process. However, the
tee of the IEEE Industry Applications Society. (Corresponding author: Qusay reconnection is accomplished by implementing different resyn-
Salem.)
The authors are with the Institute of Energy Conversion and Storage, Univer- chronization schemes, in which the difference of the voltage
sitat Ulm, Ulm 89081, Germany (e-mail: qusay.salem@uni-ulm.de; libo.liu@ magnitude, frequency, and phase angle of the main grid and the
uni-ulm.de; Jian.xei@uni-ulm.de). microgrid are reduced as much as possible [16]–[18]. Per-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. forming the disconnection and reconnection with existence
Digital Object Identifier 10.1109/TIA.2019.2917807 of series VSCs between the main grid and the microgrid

0093-9994 © 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
5290 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 5, SEPTEMBER/OCTOBER 2019

is not discussed widely in the literature. In [19] and [20],


short-circuit analysis with series VSC between two networks is
investigated. Both of them considers a series power converter
as short-circuit current limiter in distribution and transmission
networks, respectively. The power converter has considered
IGBTs for the H-bridge switches so that the disconnection and
resynchronization process of the power converter is not a serious
problem since the IGBTs have high current rating capability.
However, the H-bridge inverter in this paper considers MOSFET
devices which have reduced cost, power losses, and switching
frequency. However, it is worth noting that such devices have
limited short-circuit current rating which makes their operation
under short-circuit events more critical. Thus, the disconnection Fig. 1. Circuit topology of the single phase-full bridge inverter.
and reconnection process between the two networks must be TABLE I
properly accomplished. H-BRIDGE INVERTER SWITCHING COMBINATIONS
In this paper, a transformer-less H-bridge inverter-based
power MOSFETs is proposed to be connected between the utility
and the microgrid to control the power flow. The activation pro-
cess of the series transformer-less H-bridge inverter as a power
flow controller into the power network is presented. Further-
more, the H-bridge inverter operation as a fault current limiter
and its reinsertion process are clearly described. Besides, an
and lower MOSFET of each inverter leg is varied to control the
island control method of the microgrid voltage source inverter
switching operation of the circuit. Switching the H-bridge in a
(VSI) and the synchronization controller structure are presented.
proper sequence will create an ac output voltage, and this output
Once the microgrid and the main grid are synchronized and re-
voltage can be either +Vdc , −Vdc , or 0 depending on the control
connected with each other, the H-bridge inverter can be rein-
of the H-bridge MOSFETs. The prospective switching combina-
serted into the network.
tions of the H-bridge are formulated in Table I.
The rest of the paper is organized into four sections. Fol-
The unipolar pulsewidth modulation (PWM) is applied as a
lowing the introduction, the power flow control capability of
modulation method to control the output voltage of the H-bridge
the H-bridge inverter is presented in Section II where the basic
inverter,Vout . The switching commands M1 and M4 will be ON
configuration, system description, control methodology, and the
when the reference signal is larger than the carrier signal while
activation process are investigated. Section III investigates the
M2 and M3 will be ON when the reference signal is smaller
H-bridge inverter operation as a fault current limiter in addition
than the carrier signal [21]. The output voltage of the H-bridge
to the disconnection and reconnection process of the microgrid.
inverter can be changed by varying the reference or control sig-
Finally, the conclusion is presented in Section IV.
nal. So that, two major definitions of the modulation ratios are
developed as follows:
II. POWER FLOW CONTROL CAPABILITY
ma = Vref /Vcarrier (1)
The transformerless H-bridge inverter can behave like a series
power flow controller between two networks in which a specified mf = fcarrier /fref (2)
power flow amount can be controlled between a designated mi-
where ma is the amplitude modulation ratio (modulation index)
crogrid and the main grid in the distribution network. Depending
and mf is the frequency modulation ratio, Vref is the amplitude
on a desired real power flow reference at PCC, a series voltage
of the reference signal, Vcarrier is the amplitude of the carrier
is injected at PCC with respect to the line current. The variation
signal, fcarrier is the switching frequency, and fref is the funda-
of the PCC voltage due to injecting series voltage into the line
mental frequency.
will change the real power of the microgrid distributed genera-
If ma < 1.0, the sinusoidal PWM operates in the linear range
tor (DGs) in accordance to P/V droop characteristics. Thence, a
so that the amplitude of the fundamental frequency component
balance between the total load demand and the real power gener-
varies linearly with ma such that
ation is achieved to satisfy a desired real power reference at PCC.
Vout = ma . Vdc . (3)
A. Basic Configuration of the H-bridge Inverter
Fig. 1 depicts the basic topology of the single phase-full bridge B. System Description
inverter which is often called as an H-bridge inverter, consider- Fig. 2 shows a single line diagram of the studied network
ing the power switches arrangement. The inverter consists of which includes the microgrid, the main grid and the transformer-
two legs, and each leg includes two series connected power less H-bridge inverter. The resistance and inductance of the main
MOSFETs. grid are denoted by RG , LG , respectively. The inductance of the
A MOSFET connected in antiparallel with a diode formu- H-bridge inverter is denoted by Linv . The system parameters
lates each power control device. The turn-ON time of the upper are given in Table II. The considered lines or cables have the

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
SALEM et al.: DUAL OPERATION MODE OF A TRANSFORMERLESS H-BRIDGE INVERTER IN LOW-VOLTAGE MICROGRID 5291

Fig. 3. Relationship of the DG droop characteristic with the line length.


Fig. 2. Single line diagram of the studied network.

TABLE II
SYSTEM PARAMETERS

same impedance value (Rline = 0.8 Ω, Lline = 0.25 mH) and


the same length 100-m long for each and they are mainly resistive
in which R>>X.
Fig. 4. Control methodology of the H-bridge inverter.
Furthermore, the mathematical modeling of the network, the
microgrid modeling and the droop control are extracted from
[11] where 10 DG units are connected in parallel to the PCC the ability of the DG to supply the required load demand will be
through short underground cables. Every DG unit has its own reduced and thus, the real power at PCC cannot be controlled
local load which is also considered to be resistive. The micro- to zero.
grid DG units are supported with P/V droop characteristics to
generate the real power. C. Control Methodology
The main factor which controls the real power exchange at The major task of the transformer-less H-bridge inverter as
PCC to zero is the injected series voltage Vinv generated from a series inverter is to control the line power flow. The direct
the control unit of the H-bridge inverter. Depending on the state control of the line current in terms of power control has been
of power flow, this series voltage will increase or decrease the accomplished, in which the exchanged power is maintained un-
voltage at PCC VPCC and thus, the voltage at each DG node in der an open-loop control defined by a power reference. In order
the microgrid VDGi . Then, every DG droop characteristic will be to activate the series H-bridge inverter at PCC between the mi-
adjusted automatically to match the load demand and to satisfy crogrid and the main utility grid, the real power amount at PCC
the desired real power reference Pref at PCC as given in the should be reduced to zero to avoid any expected transients or
following: malfunctions of the control methodology during the initializa-
P = P0 − kP (u − u0 ) (4) tion process. Another solution for activating the inverter can be
done by using a pre-charged capacitor for the dc-link voltage re-
where P is the DG real power, u0 is the initial root mean square gardless of the real power flow amount at PCC. In this paper, the
(RMS) voltage 230 V, u is the DG measured RMS voltage which insertion process has been done by reducing the real power flow
is between 203 V - 253 V, P0 is the initial DG real power output, amount at PCC to zero which means that the DG units provide
andkP is the slope of the DG droop characteristic which is given only the required real power for the local loads. Fig. 4 depicts
as the control methodology of the H-bridge inverter which consists
kP = (Pmax − Pmin) /(umax − umin ). (5) of three parts.
The first part is responsible of injecting the in-phase part of
Furthermore, it should be noted that the line impedance or the injected voltage (ud,max ) by controlling the dc-link voltage.
length of line is another factor which reflect or contribute on A ramp function is used to charge the dc-link voltage gradually
making the real power at PCC equal zero. The relationship be- to the reference value through a specified slope. The second
tween the line length with the DG droop characteristic is depicted part is responsible only of tracking the line current phase by
in Fig. 3. It is clearly shown that the DG droop characteristic is a phase-locked loop. The third part considers generating the
limited with the line length increase. This means that controlling needed quadrature part of the injected voltage (uq,max ). A band-
the power at PCC to zero depends on the slope flexibility of the pass filter is integrated for damping the real power oscillations.
DG droop characteristic which is responsible of satisfying the However, damping factor determination and filter design are out
load demand. As the line impedance or length is increased, of the scope of this paper.

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
5292 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 5, SEPTEMBER/OCTOBER 2019

The inverter mode of operation is dependent on the real power


flow direction. That means; the H-bridge inverter operates in its
inductive mode if the proportional integral (PI) controller output
is negative, and the injected voltage will have +90◦ phase shift
with respect to the line current. However, the H-bridge inverter
operates in its capacitive mode if the PI controller output is
positive, and the injected voltage will have −90◦ phase shift
with respect to the line current.

D. Insertion and Activation Process


The stability and performance of the control methodology
including the dc-link control loop and the power flow control
loop have been examined by changing the real power reference
during simulating the power network of Fig. 2. The measured
dc-link voltage and the measured real power flow at PCC have
been monitored at every step change of the real power reference.
Fig. 5(a)–(f) depicts the activation process of the H-bridge in-
verter into the power network where an interaction between the
microgrid and the H-bridge inverter is initiated to control the
power flow. At (0 s < t < 0.5 s), the H-bridge inverter is out
of service so that the dc-link voltage is zero and the real power
amount at PCC is also zero. At (0.5 s < t < 1 s), the H-bridge
inverter is activated with keeping the real power flow reference
at zero and a ramp function is utilized to charge the dc-link ca-
pacitor voltage gradually to the reference voltage value (20 V).
Note that how the dc-link voltage charging is smooth and depicts
no high transients.
At (t = 1 s), the real power flow reference is increased to 10
kW and the reference dc-link voltage is activated. Note that how
the power flow controller follows smoothly the reference and
how the dc-link voltage is stabilized at the reference value. At
(t = 2 s) and (t = 3 s), the real power reference is decreased
to 5 kW and 0 kW, respectively. It can also be seen that the con-
trollers track smoothly the reference real power and the dc-link
voltage reference without any high transients. Both of control
loops (power flow control loop and dc-link voltage control loop)
are working properly in tracking their references.
The real power and voltage of the microgrid including DGs
and loads are varied depending on the series injected voltage at
PCC. Thus, a desired real power reference at PCC is achieved
by fulfilling the required balance between the total load demand
and total power generation. It is worth noting that the initial real
power value and the droop characteristic of all DG units are the
same. After (t = 1 s), it is clearly shown that with every step
change in the real power reference, the real power and RMS
voltage of the DGs and the loads are varied to satisfy the power
balance inside the microgrid.

III. FAULT CURRENT LIMITING CAPABILITY


In this section, the microgrid is represented as a DG unit
in which only one VSI is delivering power into the PCC.
Furthermore, the island control method and the synchronization
controller have been implemented in order to synchronize the
microgrid with the main grid before reclosing the circuit breaker Fig. 5. Activation process of the H-bridge inverter at PCC.
and switching to grid-connected mode. The transformer-less

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
SALEM et al.: DUAL OPERATION MODE OF A TRANSFORMERLESS H-BRIDGE INVERTER IN LOW-VOLTAGE MICROGRID 5293

Fig. 7. Single line diagram of a power network under fault event.

grid. The reference voltage and frequency are derived from in-
verse droop characteristics. However, the phase angle generated
from the droop control named as θdroop is determined at the
beginning by the system operator. Once the system operator
activates the synchronization controller, the switch will transfer
Fig. 6. Control structure of the microgrid DG VSI in island mode. to the new phase angle.
After the disconnection and islanding of the microgrid, the
synchronization controller is triggered by the system operator
H-bridge inverter acts as a short-circuit current limiter where no to derive the new phase angle θnew to ensure that the microgrid
power flow control is taking place. The fault current is limited is synchronized with the main grid before circuit breaker reclose
by changing the operation of the H-bridge from an inverter to and switching to the grid connected mode. The synchronization
current-limiting mode. controller is designed by extracting the phase angle difference
between the grid voltage and the PCC or microgrid side voltage.
Then, the sine of this angle difference is generated and passed
A. Microgrid Resynchronization Process through PI controller. The output of the PI controller is compared
Under grid fault conditions, each DG unit in the microgrid with the old measured phase angle, so that the new phase angle
should detect the islanding event and switch its operation to which tracks the grid voltage phase is generated. Finally, the
voltage control mode in order to provide a constant voltage to generated voltage is transformed to dq voltage references to be
the local loads [22], [23]. Therefore, the VSI of the microgrid inserted into the voltage and current control loops [16].
DG will perform as a grid-forming power converter fed by an ex-
ternal dc source. Furthermore, to keep the microgrid frequency B. Transformer-Less H-Bridge Inverter as a Fault Current
and voltage within their nominal limits and in order to main- Limiter
tain the microgrid energy balance, the VSI of the microgrid DG
units will supply and/or store only the needed amount of energy. Fig. 7 presents the single line diagram of a power network,
Power sharing among the microgrid DG units can be accom- where the microgrid and the utility are connected together via
plished by means of power control loops [24] or droop control series voltage source inverter which represents the H-bridge in-
strategies [25]. During the disconnection process of the micro- verter. The impedances of the grid, microgrid, line are denoted
grid, the amplitude and frequency of the reference voltage will by ZG , Zm , and Zline , respectively.
be settled down to their nominal values. However, the phase an- When the fault occurs at point A, then the circuit breaker
gle will be the one detected previously to the separation of the cannot isolate the microgrid and the H-bridge inverter from the
circuit breaker [26]. fault transient which can destroy the inverter power MOSFET
To generate the reference voltage magnitude and frequency devices and the dc-link capacitor.
of the microgrid VSI in its island operation mode, inverse Therefore, the series inverter should inject a voltage near or
droop characteristics which are well explained in [27] are imple- equal to the microgrid peak voltage in order to limit or com-
mented. Furthermore, when the fault is cleared, then switching pletely remove the short circuit current which is calculated as
the microgrid operation from autonomous mode to the grid- iSC = (Vm − Vinv ) / Ztotal . (6)
connected mode can be initiated. However, to avoid the hard
transients in the process of reconnection, the microgrid VSI has It can be noticed from (6) how the short-circuit current
to be synchronized with the main grid before reclosing the circuit limitation is dependent on the voltage difference between the
breaker [28]. The circuit breaker will still have opened and the microgrid voltage and the series inverter voltage. Thus, to inject
microgrid VSI will continue to operate in the island mode until the required voltage automatically, the series inverter operation
the synchronization condition is satisfied. After that, the micro- mode is changed from inverter mode to the current-limiting
grid VSI is again reconnected to the main grid, and the control mode once the protection scheme detects the fault event. By
strategy changed to current control mode instead of voltage con- turning off all the MOSFET devices and turning ON the antipar-
trol mode. Fig. 6 depicts the control structure of the microgrid allel diodes, the series inverter performs in its current-limiting
VSI in the island mode and the synchronization controller which mode and charges the dc-link capacitor to the peak voltage
is incorporated to synchronize the microgrid VSI with the main difference between the microgrid and the faulted node. The

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
5294 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 5, SEPTEMBER/OCTOBER 2019

Fig. 8. H-bridge inverter operation during fault. (a) Forward current direction
through diodes. (b) Reverse current direction through diodes. (c) H-bridge circuit
model during fault. Fig. 9. Relationship between the short-circuit current and dc-link voltage.

short-circuit current passes only through the antiparallel diodes Vmax


VCm = 
which can handle the fault current since the diode surge current (1 − ω 2 /ωn2 )2 + ((2ζω/ωn ))2
is much more than the MOSFET [29].
 
The operation of the H-bridge in the current-limiting mode −1 2ζωωn
ϕ = tan
during the fault is depicted in Fig. 8(a) and (b), where the dc- ωn2 − ω 2
link capacitor is charged regardless of the line current direction. 
Fig. 8(c) represents the H-bridge circuit model during the fault r1,2 = −ζωn ± ζ 2 − 1
where the initial dc-bus voltage and the forward voltage drop VCm (ω cos (ϕ) + r2 sin (ϕ))
of the diodes are neglected. The total inductance and resistance A=
r2 − r1
between the faulted node and the source are denoted by LT and
RT , respectively. The dc-bus capacitance is denoted by Cdc and VCm (ω cos (ϕ) + r1 sin (ϕ))
B= .
VS is the grid voltage which is given by VS = Vmax sin(ωt). r1 − r2
Regarding the circuit model of Fig. 8(c), the capacitor voltage The capacitor voltage and line current are determined for 0 <
time domain differential equation is given by [19] ζ < 1 as indicated in
d2 Vdc dVdc Vdc (t) = e−ζωn t [A cos (ωd t) + B sin (ωd t)]
VS = LT Cdc + RT Cdc + Vdc . (7)
dt2 dt
+ VCm sin (ωt − ϕ) (12)
By rearranging (7) taking into account the damping factor ζ  
and resonant frequency ωn then idc (t) = Cdc e−ζωn t (Bωd − Aζωn ) cos (ωd t)
d2 Vdc dVdc − (Bζωn + Aωd ) sin (ωd t) + VCm ω cos (ωt − ϕ)
ωn2 VS = + 2ζωn + ωn2 Vdc . (8) (13)
dt2 dt
Moreover, the transfer function of the system is indicated as where,

Vdc (s) ωn2 ωd = ω n 1 − ζ 2 , A = VCm sin (ϕ) ,
H (s) = = 2 . (9)
VS (s) s + 2ζωn s + ωn2
B = VCm (ζωn sin (ϕ) − ω cos (ϕ))/ωd .
The capacitor voltage and line current are determined after
solving (7) for ζ ≥ 1 as indicated in Equations (7)–(13) clarify the impact of the capacitor value
on the dc-link voltage and the line current. If the capacitor value
Vdc (t) = Aer1 t + Ber2 t + VCm sin (ωt − ϕ) (10) is decreased, this will reduce the peak short-circuit current, but
the capacitor will charge more quickly which can lead to dc-link
idc (t) = Cdc [Aer1 t + Ber2 t + VCm ω cos (ωt − ϕ)] (11)
voltage overshoot at the fault starting time. Therefore, the dc-link
where capacitor value is selected based on investigating three different
capacitor values as shown in Fig. 9, where the charging time
1
ωn2 = of the dc-link capacitor in correspondence to the short-circuit
LT Cdc current can be noticed. It is clearly shown that lowest capacitance

RT Cdc value (blue-colored) has reduced the peak short-circuit current
ζ= and charges the dc-link voltage more quickly.
2 LT

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
SALEM et al.: DUAL OPERATION MODE OF A TRANSFORMERLESS H-BRIDGE INVERTER IN LOW-VOLTAGE MICROGRID 5295

Fig. 10. H-bridge inverter operation after fault during the delay period.

After fault clearance and once the microgrid are synchronized


with the main grid, the H-bridge inverter should be reinserted
smoothly into the network to avoid the hard transients at the mo-
ment of reconnection which can harm the inverter components.
To do that, the upper or lower two MOSFET devices should be
blocked at the moment of reconnection for some milliseconds so
that the current will not flow through the dc-link capacitor. Dur- Fig. 11. Coordination of the breaker, H-bridge, and control mode during dis-
ing this period, the dc-link voltage can be discharged through connection and reconnection process.
a parallel connected resistor in order to allow the inverter to be
reinserted again into the network. utility grid, the protection scheme output becomes high and sub-
Therefore, the PWM switching commands either M 1 and sequently the flip-flops of the circuit breaker, the H-bridge in-
M 3 or M 2 and M 4 (see Fig. 1) should be blocked (zero sig- verter control unit, and the VSI control mode denoted by FF 1,
nal) to allow the current flow only through the upper or lower FF 2, and FF 3, respectively are adjusted to the set command.
two MOSFET devices and to allow discharging of the dc-link ca- Furthermore, when the fault is cleared, the fault clear signal
pacitor voltage to zero before inserting the inverter again into is set high manually to reset the flip-flops and thus changing the
the network. Once the two networks are reconnected and the VSI control mode, the H-bridge inverter operation, as well as the
dc-link voltage discharges to zero, then the inverter can be rein- circuit breaker state. It is worth noting that the fault clear signal
serted and its switching operation can be enabled. By closing which is controlled manually will not be triggered unless the
a switch which manages parallel connection of a resistor with synchronization criterion is achieved. The trip signal initiates the
the dc-link capacitor, then the dc-link voltage can be discharged circuit breaker tripping and reclosing, the block signal activates
during the delay period. The current flow and the resistor paral- the H-bridge inverter blocking state. Finally, the microgrid VSI
lel connection during this period are described in Fig. 10. This control mode is altered between its grid-connected and island
step can ensure safe and smooth inverter reinsertion after fault operation modes depending on the switch signal state.
clearance and breaker reclose.

D. Test Validation and Verification


C. Coordination With Flip-Flops
The power network presented in Fig. 6 has been implemented
During islanding and resynchronization of the microgrid due and simulated using piecewise linear electrical circuit simula-
to short-circuit events, a proper coordination with flip-flops is tion (PLECS) and SimPowerSystems toolboxes in Simulink to
required for the whole power system components. The circuit investigate the disconnection and reconnection process of the
breaker which isolates the main utility grid from the microgrid system components. The microgrid is represented by a single
should receive a signal from a specified protection scheme once DG unit which feeds a resistive load with 5 kW. The short cir-
it detects a fault event and once the fault is cleared as well. The cuit is started at t = 1 s and cleared at t = 1.5 s.
VSI of every microgrid DG unit should detect any islanding The short-circuit is applied at the nearst location to the H-
event or resynchronization process in order to decide whether bridge as a worst case scenario taking into account two fault
to work in grid-connected mode or island mode. The H-bridge inception angles (FIA) at 0◦ and 90◦ . The threshold for applying
inverter control unit should also be informed about the fault ini- the current-limiting mode is 1.5 times the H-bridge maximum
tiation and clearance in order to plan for the reinsertion process power flow current so as to keep safe operation of the power
into the network. Fig. 11 depicts the appropriate coordination switches. Moreover, the MOSFET is not able to bear high transient
of the circuit breaker, the H-bridge inverter control unit, and the current for a period more than 100 μs. However, the antiparallel
microgrid VSI control mode. diodes are able to withstand higher current density which is
The protection scheme monitors the instantaneous current nominated as surge or transient current. A fast fault detection
value as it is faster to be detected than the RMS value. Once method based on monitoring the instantaneous current passing
the protection scheme discovers that the current exceeds a spec- through the H-bridge inverter is used to detect the fault event in
ified or threshold value due to a short-circuit event in the main a period of time less than 100 μs. Once the fault is detected, the

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
5296 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 5, SEPTEMBER/OCTOBER 2019

Fig. 13. FFT analysis of the PCC voltage during the fault.

The impact of the voltage and/or current distortion in the


proposed methodology is testified by measuring the harmonic
spectrum of the PCC voltage once the fault is initiated as de-
picted in Fig. 13. The total harmonic distortion (THD) limit at
PCC in 400 V low voltage distribution networks should not ex-
ceed 5% as stated in [30]. The THD is measured once the fault
Fig. 12. System behavior during the short-circuit event. is initiated (t = 1 s) for the first three cycles of the PCC voltage.
It can be seen that the THD factor of the PCC voltage is small
and below 5% at the time of fault initiation.
anti-parallel diodes are turned on and the surge current passes The simulation time sequence of the test validation model is
through the diode only for half a sinusoidal cycle 10 ms. As soon as the following.
as the dc-link capacitor starts charging, the short-circuit current 1) At (0.5 s < t <1 s): The microgrid VSI operates in grid-
will be limited. connected mode and the H-bridge inverter control unit is
The short-circuit current capability has been investigated to enabled to inject series voltage into the line.
see the behavior of the H-bridge inverter where the point on wave 2) At t = 1 s: The short-circuit is initiated and the circuit
or the FIA is considered at 0◦ and 90◦ . Fig. 12(a)–(d) depicts the breaker is opened, the proposed flip-flops are set high, the
system behavior considering two different FIAs. microgrid VSI switch its operation to island control mode,
Fig. 12(a) shows the PCC voltage where the FIA is consid- the MOSFET devices are turned OFF and the antiparallel-
ered on near zero crossing 0◦ , and at maximum value of voltage diodes are turned ON, VDC charges to the difference
90◦ . It can be seen that for both cases, the short-circuit current between the peak network voltage and the faulted node
is detected within approximately 100 μs and the dc-link voltage voltage.
starts charging to limit the fault current as shown in Fig. 12(b) 3) At t = 1.2 s: The synchronization controller is triggered
and (c). Note that the short-circuit current is limited for both by the system operator.
cases where the initial surge current passes through the anti- 4) At t = 1.5 s: The short-circuit is cleared and the cir-
parallel diodes for a period much less than 10 ms. The corre- cuit breaker is reclosed, the microgrid VSI get back to
sponding phase angle jump of the PCC voltage for both FIAs is work again in grid-connected mode, the PWM switching
shown in Fig. 12(d). It can be seen that the phase angle jump is commands M1 and M3 are set to zero (delay), VDC
small since the short-circuit is fast detected and limited. discharges to zero during the delay period.

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
SALEM et al.: DUAL OPERATION MODE OF A TRANSFORMERLESS H-BRIDGE INVERTER IN LOW-VOLTAGE MICROGRID 5297

Fig. 14. Voltage magnitude and phase angle of both networks before and after
triggering the synchronization controller in island control mode.

Fig. 16. System performance during the disconnection and reconnection pro-
cess.

Fig. 15. Frequency of both networks during synchronization process.

5) At t = 1.7 s: The H-bridge inverter is reinserted, the switch-


ing commands M1 and M3 are enabled, reconnection pro-
cess of the H-bridge is completed.
The voltage magnitude, phase angle and, frequency of both the
microgrid and main grid in the island control mode before and af-
ter triggering the synchronization controller are demonstrated in
Figs. 14 and 15, respectively. Based on the droop characteristics
applied to the microgrid VSI power control, it can be seen that
both voltage sources have different frequency and phase angle.
Nevertheless, as soon as the system operator activates the syn- Fig. 17. DC-link capacitor voltage and inverter voltage during the disconnec-
tion and reconnection process.
chronization process, then the synchronization controller forces
the microgrid to track the main grid voltage, phase angle and,
frequency.
Fig. 16 presents the microgrid real and reactive power, the The performance of the H-bridge inverter in terms of the dc-
line current and PCC voltage during the disconnection and re- link capacitor voltage and its terminals voltage during the dis-
connection process. At t = 1 s, the inverter MOSFET devices are connection and reconnection process is depicted in Fig. 17.
turned OFF and the antiparallel diodes are turned ON so that the Once the fault is initiated, note that how the dc-link volt-
inverter switches its operation from an inverter mode to a current- age charges to the voltage difference between the peak network
limiting mode. Therefore, the fault current is limited very fast voltage and the faulted node. It is worth noting that between
and no transients appeared at the moment of disconnection. As (1.5 s < t < 1.7 s), the switching commands M1 and M3 are set
the microgrid is synchronized with the main grid before closing to zero (delay) in order to allow the dc-link voltage discharging.
the circuit breaker, it can be noticed that the power values in In order to reinsert the H-bridge inverter smoothly, the dc-link
addition to the line current and PCC voltage have no transients voltage is discharged to zero using a parallel-connected resistor
at the moment of reconnection. during this delay period.

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
5298 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 5, SEPTEMBER/OCTOBER 2019

IV. CONCLUSION [14] R. J. Millar, S. Kazemi, M. Lehtonen, and E. Saarijärvi, “Impact of MV


connected microgrids on MV distribution planning,” IEEE Trans. Smart
In this paper, two different issues have been investigated re- Grid, vol. 3, p. 2100–2108, Dec. 2012.
garding the transformer-less H-bridge inverter feasibility be- [15] D. E. Olivares et al., “Trends in microgrid control,” IEEE Trans. Smart
Grid, vol. 5, no. 4, p. 1905–1919, Jul. 2014.
tween the main grid and microgrid. The first issue was the power [16] I. Balaguer, Q. Lei, S. Yang, U. Supatti, and F. Z. Peng, “Control for grid-
flow control capability in which an advanced control methodol- connected and intentional islanding operations of distributed power gener-
ogy has been used to activate the H-bridge inverter as a power ation,” IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 147–157, Jan. 2011.
[17] L. Tao, C. Schwaegerl, S. Narayanan, and J. H. Zhang, “From laboratory
flow controller. The second issue was the capability of limit- microgrid to real markets—challenges and opportunities,” in Proc. 8th Int.
ing the fault current by changing the operation mode of the Conf. Power Electron., 2011, pp. 264–271.
transformer-less H-bridge from an inverter mode to a current- [18] H. Laaksonen and K. Kauhaniemi, “Stability of microgrid with different
configurations after islanding due to fault in the utility grid,” Int. Rev. Elect.
limiting mode and thus, ensuring stable operation of the micro- Eng., vol. 3, no. 3, pp. 498–512, 2008.
grid. It was observed from the simulation results that the control [19] M. Saradarzadeh, S. Farhangi, J. Schanen, P.-o. Jeannin, and D. Frey,
methodology has tracked the real power reference successfully “Combination of power flow controller and short-circuit limiter in dis-
tribution electrical network using a cascaded H-bridge distribution-static
at every step change. Besides, it is clearly shown that the H- synchronous series compensator,” IET Gener., Transmiss. Distrib., vol. 6,
bridge inverter has limited the short-circuit current by inject- no. 11, pp. 1121–1131, 2012.
ing the required voltage into the line. The successful microgrid [20] S. Bacha, D. Frey, J. L. Schanen, E. Lepelleter, P. O. Jeannin, and R. Caire,
“Short-circuit limitation thanks to a series connected VSC,” in Proc. 23rd
reconnection and the H-bridge inverter reinsertion confirm the Annu. IEEE Appl. Power Electron. Conf. Expo., 2008, pp. 1938–1945.
validity of the proposed approaches. [21] A. Roshan, “A dq rotating frame controller for single phase full-bridge
The future work will focus on the in-depth short-circuit anal- inverters used in small distributed generation systems,” Master thesis, Vir-
ginia Polytechnic Inst. State Univ., Blacksburg, VA, USA, 2006.
ysis considering X/R impact in transient and steady-state behav- [22] M. E. Haque, M. Negnevitsky, and K. M. Muttaqi, “A novel control
ior, directional versus non-directional overcurrent settings, and strategy for a variable-speed wind turbine with a permanent-magnet syn-
short-circuit current capability of the microgrid versus PCC of chronous generator,” IEEE Trans. Ind. Appl., vol. 46, no. 1, pp. 331–339,
Jan./Feb. 2010.
the system. Besides, a test-bed setup will be built in lab level to [23] T. C. Green and M. Prodanović, “Control of inverter-based micro-grids,”
validate the proposed approaches by experimental results. Elect. Power Syst. Res., vol. 77, no. 9, pp. 1204–1213, 2007.
[24] E. Barklund, N. Pogaku, M. Prodanovic, C. Hernandez-Aramburo, and T.
C. Green, “Energy management in autonomous microgrid using stability-
REFERENCES constrained droop control of inverters,” IEEE Trans. Power Electron.,
vol. 23, no. 5, pp. 2346–2352, Sep. 2008.
[1] F. H. Gandoman et al., “Review of FACTS technologies and applications
[25] Y. W. Li and C.-N. Kao, “An accurate power control strategy for power-
for power quality in smart grids with renewable energy systems,” Renew.
electronics-interfaced distributed generation units operating in a low-
Sustain. Energy Rev., vol. 82, pp. 502–514, 2018.
voltage multibus microgrid,” IEEE Trans. Power Electron., vol. 24, no. 12,
[2] D. Soto and T. Green, “A comparison of high-power converter topologies
pp. 2977–2988, Dec. 2009.
for the implementation of FACTS controllers,” IEEE Trans. Ind. Electron.,
[26] J. Rocabert, G. M. S. Azevedo, A. Luna, J. M. Guerrero, J. I. Candela, and
vol. 49, no. 5, pp. 1072–1080, Oct. 2002.
P. Rodríguez, “Intelligent connection agent for three-phase grid-connected
[3] G. Cao, Z. Y. Dong, Y. Wang, and P. Zhang, “VSC based series FACTS
microgrids,” IEEE Trans. Power Electron., vol. 26, no. 10, pp. 2993–3005,
controllers for damping local mode oscillations,” in Proc. IEEE Power
Oct. 2011.
Eng. Soc. Gen. Meeting, 2007, pp. 1–7.
[27] Q. Salem and J. Xie, “Transition from grid-connected to islanded drooped
[4] K. Sen, “SSSC-static synchronous series compensator: Theory, modeling,
microgrid based on islanding detection scheme,” Int. J. Power Energy Syst.,
and application,” IEEE Trans. Power Del., vol. 13, no. 1, pp. 241–246,
vol. 36, no. 3, pp. 112–118, 2016.
Jan. 1998.
[28] G. Iwanski and W. Koczara, “DFIG-based power generation system with
[5] S. Kamel, F. Jurado, and Z. C. b, “Power flow control for transmission net-
UPS function for variable-speed applications,” IEEE Trans. Ind. Electron.,
works with implicit modeling of static synchronous series compensator,”
vol. 55, no. 8, pp. 3047–3054, Aug. 2008.
Int. J. Elect. Power Energy Syst., vol. 64, p. 911–920, 2015.
[29] Q. Salem, L. Liu, and J. Xie, “Islanding and resynchronization process of
[6] M. E. Moursi, A. Sharaf, and K. El-Arroudi, “Optimal control schemes for
a grid-connected microgrid with series transformerless H-bridge inverter
SSSC for dynamic series compensation,” Elect. Power Syst. Res., vol. 78,
installed at PCC,” in Proc. IEEE Int. Conf. Environ. Elect. Eng., IEEE Ind.
p. 646–656, 2008.
Commercial Power Syst. Eur., 2018, pp. 1–6.
[7] A. Pashaei, B. Zahawi, and D. Giaouris, “New control method for distri-
[30] T. Hoevenaars, K. LeDoux, and M. Colosino, “Interpreting IEEE STD 519
bution network distributed static series compensator,” in Proc. 5th IET Int.
and meeting its harmonic limits in VFD applications,” in Proc. IEEE Ind.
Conf. Power Electron., Mach. Drives, 2010, pp. 1–5.
Appl. Soc. 50th Annu. Petroleum Chem. Ind. Conf., 2003, pp. 145–150.
[8] E. L. Pelleter, S. Bacha, R. Caire, and J. Guiraud, “Active and reactive
power flow control based on a D-SSSC for looped and meshed distribution
Grids,” in Proc. 19th Int. Conf. Electricity Distrib., 2007, pp. 1–4.
[9] M. Saradarzadeh, S. Farhangi, J. Schanen, P.-O. Jeannin, and D. Frey,
“Application of cascaded H-bridge distribution-static synchronous series
compensator in electrical distribution system power flow control,” IET
Power Electron., vol. 5, no. 9, p. 1660–1675, 2012.
[10] B. Pan, H. Yu, K. Li, Z. Zhao, Y. Jiang, and L. Yuan, “A hierarchical Qusay Salem received the B.Sc. degree from the
control strategy for cascaded H-bridge multilevel static synchronous series University of Mutah, Mutah, Jordan, in 2009, and
compensator,” in Proc. 19th Int. Conf. Elect. Mach. Syst., 2016, pp. 1–5. the M.Sc. degree from Yarmouk University, Irbid,
[11] Q. Salem and J. Xie, “Decentralized power control management with series Jordan, in 2012, both in in electrical power engineer-
transformerless H-bridge inverter in low-voltage smart microgrid based ing. He is currently working toward the Ph.D. degree
P/V droop control,” Int. J. Elect. Power Energy Syst., vol. 99, pp. 500– in electrical power and energy engineering at the In-
515, 2018. stitute of Energy Conversion and Storage, University
[12] T. Ghanbari and E. Farjah, “Unidirectional fault current limiter: An ef- of Ulm, Ulm, Germany.
ficient interface between the microgrid and main network,” IEEE Trans. His research interests include power control and
Power Syst., vol. 28, no. 2, pp. 1591–1598, May 2013. energy management in low-voltage smart microgrids,
[13] T. Ghanbari and E. Farjah, “A multiagent-based fault-current limiting Islanding detection schemes, modeling and control of
scheme for the microgrids,” IEEE Trans. Power Del., vol. 29, no. 2, power converters, reactive power support by using FACTS devices, applications
pp. 525–533, Apr. 2014. of power electronics in power Systems.

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.
SALEM et al.: DUAL OPERATION MODE OF A TRANSFORMERLESS H-BRIDGE INVERTER IN LOW-VOLTAGE MICROGRID 5299

Libo Liu received the B.Sc. degree in electrical engi- Jian Xie received the B.Sc. degree from Jiao-
neering from Shanghai Jiaotong University (SJTU), Tong University, Shanghai, China, in 1985, and the
Shanghai, China in 2012, and the dual master’s degree Diploma and Ph.D. degree from the Technical Uni-
in electrical engineering from SJTU and the Technical versity of Darmstadt, Darmstadt, Germany, in 1987
University of Berlin, Berlin, Germany, in 2015. Since and 1993, all in electrical engineering.
2015, he has been working toward the Ph.D. degree at Since 1998, he has been a Full Professor with
the Institute of Energy Conversion and Storage, Uni- the Institute of Energy Conversion and Storage, Uni-
versity of Ulm, Ulm, Germany. versity of Ulm, Ulm, Germany. He has two regis-
His current research interests include the multi- tered patents. His research interests include advanced
level inverter design and motor drive techniques for power converters, battery management systems, high
electric vehicles. frequency harmonics in railways, cascaded H-bridge
inverters, smart grid and smart meters, and decentralized control in microgrids.

Authorized licensed use limited to: Princess Sumaya University for Technology. Downloaded on November 14,2022 at 12:20:49 UTC from IEEE Xplore. Restrictions apply.

You might also like