Professional Documents
Culture Documents
Series
1900 CompactLowDifferentialPressureSwitches
Set Points from 0.07" to 20" W.C. Repetitive Accuracy within 3%
®
®
Our most popular series combines advanced design and precision SPECIFICATIONS
construction to make these switches able to perform many of the tasks Service: Air and non-combustible, Electrical Connections: 3 screw
of larger, costlier units. Designed for air conditioning service, they also compatible gases. type, common, normally open and
serve many fluidics, refrigeration, oven and dryer applications. For air Wetted Materials: Consult normally closed.
Factory. Process Connections: 1/8˝ female
and non combustible compatible gases, Series 1900 switches have set NPT.
Temperature Limits: -30 to 180°F
points from 0.07 to 20˝ (1.8 to 508 mm) w.c. Set point adjustment is (-34 to 82.2°C). Mounting Orientation: Diaphragm
easy with range screw located inside conduit enclosure. Internal loca- Pressure Limits: 45˝ w.c. (11.2 in vertical position. Consult factory
tion helps prevent tampering. UL, CE, CSA listed, and FM approved. kPa) continuous, 10 psig (68.95 for other position orientations.
kPa) surge. Set Point Adjustment: Screw type
Switch Type: Single-pole double- inside conduit enclosure.
throw (SPDT). Weight: 1lb, 4.5 oz (581 g).
SPECIAL MODELS AND ACCESSORIES Repeatability: ±3%. Agency Approvals: CE , UL, CSA,
MANUAL RESET MODEL 1900 MR includes special snap switch which Electrical Rating: 15 A @ 120- FM.
latches on pressure increase above the setpoint. Switch must be manually 480 VAC, 60 Hz. Resistive 1/8 HP
reset after pressure drops below the setpoint. To order, change base model @125 VAC, 1/4 HP @ 250 VAC, 60
to 1900 and add MR suffix after range number. Example: 1900-10-MR. Hz. Derate to 10 A for operation at
Available on -1, -5,-10 or -20 ranges only. Option is not UL, CSA or FM list- high cycle rates.
ed
A-399 Duct Pressure Monitor Kit — For use with standard or manual reset CAUTION: FOR USE ONLY WITH AIR OR COMPATIBLE GASES.
model switches. Includes mounting flange, tubing and adapters
ATEX (Approval Pending) Housing,
A-329 Street Ell — Brass adapter for applications requiring right angle con- Model 1911- CN. Explosion-proof
nections. Two required for differential pressures housing, EExd II B T6 IP6S. Change
base number to 1911 and add -CN
suffix.
Example: 1911-1-CN.
Weatherproof Housing
WEATHERPROOF ELECTRIC 1-1/8
16 ga. steel enclosure with gasketed CONNECTION HUB
4 [101.6] SQ. [28.58]
cover (NEMA 4, IP66) for wet or oily 7/8 1/2⬙ NPT FEMALE
conditions. Withstands 200 hour salt [22.23] (4) 5-16 [7.94] DIA.
MTG. HOLES
spray test. Wt. 5 Ibs. (2.3 kg). Switch
must be factory installed. Change 1910 SERIES 1910 SWITCHES — STOCKED MODELS
2 [50.8]
3 [76.2]
62 Dwyer Instruments, Inc./P.O. Box 373/Michigan City, IN 46361/Phone 219 879-8000/Fax 219 872-9057 • U.K. Phone (+44) (0)1494-461707 • Australia Phone 61 2 4272-2055