You are on page 1of 12

NEMA Manual Starters 38-1

February 2007

NEMA Manual
Starters
Contents
Description Page
Starters and Switches
Types B230, B330, Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-2
MS Series, Single-Phase Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-4
Type B100, Single- and Three-Phase Starters . . . . . . . . . . . . . . . . . . . . . . 38-6
Type 9441, Reversing Drum Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-10

38

CA08102001E For more information visit: www.eaton.com


38-2 NEMA Manual Starters
Starters and Switches
February 2007
Types B230, B330, Switches

Contents Product Description Features


Description Page Manual Motor Switches are available ■ Compact size
in two- or three-pole configurations ■ Easy installation
Manual Motor Switches rated at 30A. ■ Simple operation
Product Description . . . . . . . 38-2
Optional NEMA 1 aluminum enclosure ■ Padlockable NEMA 1 enclosure
Application Description. . . . 38-2 is supplied with a padlock guard for available
Features . . . . . . . . . . . . . . . . 38-2 locking in the OFF or STOP position.
Instructional Leaflet. . . . . . . 38-2 Instructional Leaflet
Standards and Application Description
Certifications . . . . . . . . . . . 38-2 Pub25371
Manual Motor Switches provide man-
Wiring Diagrams . . . . . . . . . 38-2
ual control of single- and three-phase
Dimensions . . . . . . . . . . . . . 38-2 motors where overload protection is Standards and Certifications
Product Selection . . . . . . . . 38-3 not required or provided separately. ■ UL File No. E146654, Category NLRV
Applications include:
38 ■ CSA File No. LR710828,
■ Fans Class 3211-05
■ Blowers
■ Pumps
■ Wood Working Equipment
■ Machine Tools

Wiring Diagrams
B230AN L1 L2 B230BN B330AN
L1 T1
L1 T1
L2 T2
L2 T2
L3 T3
T2
T1 T2 T1 T2 T1 T3
2-Pole B230BN 1-Ph. 1-Ph. 3-Ph.
Motor Motor Motor
3-Pole B330AN

Figure 38-1. Wiring Diagrams


Dimensions
1.30 1.11 2.25 1.44
(33.0) (28.2) (57.2) (36.6)
1.12 (28.4) .06
(1.5)

4 – #6-32
4.06 3.28 2.38 2.27 3.78 3.28 2.38 Tap 2.75
(103.1) (83.3) (60.5) (57.7) (96.0) (60.5) (69.9)

2 – .20 (5.1)
Dia. Mtg. Holes
2 – #6-32 Tapped
Holes for Wall Plate
Catalog Numbers B230BN and B330AN
Catalog Number B230AN Ship. Wt. 4 oz. (.11 kg) Ship. Wt. 6 oz. (.17 kg)

3.20 1.50 2 Holes


(81.3) (38.1) .13 (3.3)
Dia. 0.68
(17.3)

.91
4.72 2.75 2.44 (23.1)
(119.9) (69.9) (62.0) 2.41
(61.2)

2 Holes
.27 (6.9) .5 (12.7) x .75 (19.1)
2 – .5 (12.7) Dia. Knockout Each End
Knockouts
Front View Back View End View
Catalog Numbers B230AG, B230BG, B330AG Ship. Wt. 14 oz. (.40 kg)

Figure 38-2. Approximate Dimensions in Inches (mm) and Shipping Weights

For more information visit: www.eaton.com CA08102001E


NEMA Manual Starters 38-3
Starters and Switches
February 2007
Types B230, B330, Switches

Product Selection
When Ordering Specify
■ Catalog Number of Manual Motor
Switch

2-Pole B230AN 3-Pole B330AN 2-Pole


NEMA 1 Enclosure
B230BG

Table 38-1. Manual Motor Switches without Overload


Maximum Horsepower Ratings Open Price NEMA 1 Price
120V 240V 480V 600V U.S. $ Enclosed U.S. $ 38
2-Pole — Manual Motor Switches
2 5 — — B230AN B230AG
2 5 10 15 B230BND B230BGD
3-Pole — Manual Motor Switches
3 7-1/2 15 20 B330AND B330AGD

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-1C

CA08102001E For more information visit: www.eaton.com


38-4 NEMA Manual Starters
Starters and Switches
February 2007
MS Series, Single-Phase Starters

Contents ■ Standard with large pressure type Instructional Leaflet


terminals, straight-through wiring
Description Page and a trip-free handle mechanism IL12987G
Manual Motor Starters ■ The “plug-in” heater element is
keyed to ensure proper positioning
Product Description . . . . . . . 38-4
and an adjustable knob allows a
Standards and Certifications
Application Description. . . . 38-4 setting of plus or minus ten percent ■ UL File No. E19222, Category NLRV
Features . . . . . . . . . . . . . . . . 38-4 of the nominal heater rating
■ CSA File No. LR39402-6, Class
Instructional Leaflet. . . . . . . 38-4 3211-05
Application Description
Standards and
Certifications . . . . . . . . . . . 38-4 The MS Manual Motor Starter pro-
vides manual control and overload
Accessories . . . . . . . . . . . . . 38-4 protection to single-phase motors.
Dimensions . . . . . . . . . . . . . 38-4 By utilizing the interchangeable heater
Product Selection . . . . . . . . 38-5 elements, the starter can protect Accessories
motors ranging from .40 amps up to
38 16.0 amps. Ideal for HVAC applications. Table 38-2. MS Accessories
Description Catalog Price
Features Number U.S. $
■ Compact size Pilot Light Kit (NEMA 1 MSPT
■ Trip-free handle mechanism Enclosure and Flush Plates)
Box, 1 Unit (NEMA 1 MS1BN
■ Keyed heater elements to ensure Enclosure)
proper installation Cover, 1 Unit (NEMA 1 MS1CN
■ Starters available with red pilot light Enclosure)
Flush Plate, 1 Unit (Steel) MS1FN
■ The operating handle of the Flush Plate, 1 Unit (Stainless MS1DN
enclosed units can be locked in the Steel)
Modular Toggle Operated Starter OFF position Handle Guard (Padlockable MSLG
for NEMA 1 Enclosure and
■ Enclosures are offered in NEMA 1, 3,
Product Description 4 and 5
Flush Plates)

■ The MS Motor Starter is a compact, ■ Hazardous locations cast aluminum


versatile unit featuring heavy sliding enclosures are available rated for
contacts as well as “quick-make” Type 7, Class I, Group D (vapors)
and “quick-break” mechanism and Type 9, Class II, Groups E, F an
G (dust).
Dimensions
Mounting 1.52 1.64 3.63
Purposes (38.6) (41.7) (92.2) 2.91
(2) Holes .75 (73.9)
1.06 (19.1)
2.75 (26.9) .78
(69.9) (19.8)
1.38 3.28 .66
(35.1)
(83.3) (16.8) .34
.19 (4.8) (8.6)
.31 3.28 .22 Handle 5.81
(7.9) (83.3) (5.6) 4.5 1.64 (147.6)
.36 (9.1) (114.3) (41.7) Guard
Dia. 5.13
1.25 1.19 (130.3)
1.36 (31.8) (30.2) .22
(34.5) (5.6) 2.25
20°
Typ. (57.2)
.75 1.53
(19.1) (38.9)
.31 Indicating Light
1.64 (7.9) 1 Unit .75 (19.1) Pipe Tap
3.81 (41.7)
(96.8) Flush Plates Watertight (Cast Aluminum)
2.72 2.38
(69.1) (60.5) 3.94 3.5 (88.9)
1.91 .31 3.28 (83.3) (100.1)
.06 (1.5) 2.83 (71.9) 2.63
(48.5) (7.9) .81
.11 (2.8) .14-32 2.55 (66.8)
Height 1 Unit (20.6)
.73 Tap (64.8)
of Handle (18.5) 2.38 2.47
(60.5) .55 (62.7)
.41 1.56 (14.0) 2.11
1.70 (10.4) (39.6) (53.6)
(43.2)
6.72
Indicating (170.7)
Light
1.58 5.88
Handle (149.4)
(40.1) 4.16 3.06 Guard
(105.7) (77.7)
MS Motor Starter
Toggle Operated Open Units
.30 (7.6) Dia.
Lockout Hole
.20 (5.1) 1.97 .44
Diameter (2) (50) .75 (19.1) .34 (8.6) Dia. (11.2)
Mounting Hole Pipe Tap (2) Mounting Holes
Type 1 Enclosures
(Boxes and Covers) Hazardous Location (Cast Aluminum)

Figure 38-3. Approximate Dimensions in Inches (mm)


Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-1C

For more information visit: www.eaton.com CA08102001E


NEMA Manual Starters 38-5
Starters and Switches
February 2007
MS Series, Single-Phase Starters

Product Selection
When Ordering Specify
■ Catalog Number of Manual Motor
Starter
■ Heater Pack selection
■ Any required Accessories
■ Heater Coil selection according to the
motor full load current requirements
Switch and Pilot Light
Table 38-3. Product Selection — MS Series Starters Mounted on Flush Plate
Number of Horsepower Voltage Catalog Price
Poles Number  U.S. $
Open Type
1 1 120/240V, 277V AC MST01
1/4
1/4
120/240V DC
32V DC
38
2 1 120/240V, 277V AC MST02
1 120/240V DC
1/4 32V DC
Flush Plate (No Enclosure Included)
1 Flush Plate Type Switch Only MST01FN
Switch with Pilot Light MST01FN1P Switch and Pilot Light
General Mounted in Type 1 Enclosure
2 Purpose Switch Only MST02FN
Switch with Pilot Light MST02FN1P
1 Stainless Switch Only MST01DN
Steel Switch with Pilot Light MST01DN1P
2 Switch Only MST02DN
Switch with Pilot Light MST02DN1P
Enclosed Types
1 Enclosure Type Switch Only MST01SN
General Switch with Pilot Light MST01SN1P
2 Purpose Switch Only MST02SN
Type 1 Switch with Pilot Light MST02SN1P
1 Waterproof Through Hub MST01AH
2 Type 3, 4 & 5 Through Hub MST02AH Waterproof
Type 3, 4 & 5
1 Hazardous Location  Through Hub MST01EH
2 Types 7D, 9E, 9F & 9G Through Hub MST02EH
 Does not include heater. Select heater from Table 38-4.
 Type 7D = Type 7, Class I, Group D; Type 9E, 9F and 9G = Type 9, Class II, Groups E, F and G.

Hazardous Location
Typical Heater Heater Element Installation Type 7D, 9E, 9F & 9G
Table 38-4. Heater Selection for MS Starters
Motor Catalog Price Motor Catalog Price Motor Catalog Price Motor Catalog Price
Full Load Number U.S. $ Full Load Number U.S. $ Full Load Number U.S. $ Full Load Number U.S. $
Current Current Current Current

.4 – .43 MSH-5A 1.04 – 1.15 MSH1-3A 2.72 – 2.95 MSH3-4A 7.04 – 7.74 MSH8-8A
.44 – .48 MSH-55A 1.16 – 1.27 MSH1-45A 2.96 – 3.27 MSH3-7A 7.75 – 8.46 MSH9-7A
.49 – .53 MSH-61A 1.28 – 1.35 MSH1-6A 3.28 – 3.59 MSH4-1A 8.47 – 9.35 MSH10-6A
.54 – .58 MSH-67A 1.36 – 1.51 MSH1-7A 3.60 – 3.99 MSH4-5A 9.36 – 10.30 MSH11-7A
.59 – .64 MSH-74A 1.52 – 1.67 MSH1-9A 4.00 – 4.39 MSH5-0A 10.31 – 11.35 MSH12-9A
.65 – .71 MSH-81A 1.68 – 1.83 MSH2-1A 4.40 – 4.79 MSH5-5A 11.36 – 12.47 MSH14-2A
.72 – .78 MSH-89A 1.84 – 1.99 MSH2-3A 4.80 – 5.26 MSH6-0A 12.48 – 13.67 MSH15-6A
.79 – .87 MSH-98A 2.00 – 2.23 MSH2-5A 5.27 – 5.83 MSH6-6A 13.68 – 15.12 MSH17-1A
.88 – .95 MSH1-1A 2.24 – 2.47 MSH2-8A 5.84 – 6.39 MSH7-3A 15.13 – 16.00 MSH18-6A
.96 – 1.03 MSH1-2A 2.48 – 2.71 MSH3-1A 6.40 – 7.03 MSH8-0A

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-1C

CA08102001E For more information visit: www.eaton.com


38-6 NEMA Manual Starters
Starters and Switches
February 2007
Type B100, Single- and Three-Phase Starters

Contents Features Instructional Leaflet


Description Page ■ Includes three-pole bimetallic over- IL14890
load relay
Manual Motor Starters
■ Straight-through wiring
Product Description . . . . . . . 38-6 Standards and Certifications
■ Field mounted auxiliary contacts
Application Description. . . . 38-6 ■ Available in NEMA 1, 4, 7, 9 and 12 ■ UL File No. E19222, Category NLRV
Features . . . . . . . . . . . . . . . . 38-6 enclosures with toggle operation ■ CSA File No. LR39402-6, Class
Instructional Leaflet. . . . . . . 38-6 (NEMA 1 enclosure for pushbutton 3211-05 (Open Starters)
operator) ■ CSA File No. LR54517-1, Class
Standards and
Certifications . . . . . . . . . . . 38-6 ■ Standard with a lockout device to 3211-05 (Closed Starters)
lock motor in the OFF position
Technical Data . . . . . . . . . . . 38-6
Options . . . . . . . . . . . . . . . . . 38-6
Accessories . . . . . . . . . . . . . 38-6
38 Dimensions . . . . . . . . . . . . . 38-7 Technical Data
Product Selection . . . . . . . . 38-8
Table 38-5. Specifications
NEMA Maximum hp for AC Ratings  Maximum hp for DC Ratings
Size 120V AC 208 – 240V AC 480 – 600V AC 115V DC 230V DC
2-Pole, Single-Phase
M-0 1 2 — 1 1-1/2
M-1 2 3 — 1-1/2 2
3-Pole, Three-Phase
M-0 2 3 5 — —
M-1 3 7-1/2 10 — —
 Ratings up to 3 hp, 3-phase are suitable for group fusing.

Options Accessories
Pushbutton Operated Table 38-6. Factory Modifications Table 38-7. Accessories
Description Catalog Adder Description Catalog Price
Product Description Number  U.S. $ Number U.S. $
Suffix Field Mounting Kits
The B100 Manual Motor Starters can Pushbutton operator A 1NO elect. auxiliary B1A
be used in single-phase applications (open and NEMA 1 only) 1NC elect. auxiliary B1B
rated 3 hp at 240V AC or 2 hp at 230V Without lockoff X Red pilot light 120/60 LK-21
DC. The starter can also be rated for (open only) (NEMA 1 Enc. Only)
three-phase applications up to 10 hp at  Red pilot light 208-240/6 LK-22
Add Suffix letter to starter Catalog Number
(NEMA 1 Enc. Only)
600V AC. Ex: B100MOCA.
Red pilot light 480-600/60 LK-26
(NEMA 1 Enc. Only)
There are two methods of operation for
the B100 Manual Starter. It can be For Type 4 and 12 Enclosures Only
ordered with a toggle switch operator Red pilot light 120V LK-41
or a START/STOP pushbutton operator. Red pilot light 240V LK-42

Application Description
The B100 family of Manual Motor
Starters provides manual control, as
well as overload protection, to both
single-phase and three-phase motors.
The starter protects motors up to
38.9 amp single-phase and 26.8 amp
three-phase with the appropriate
heater selection.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-1C

For more information visit: www.eaton.com CA08102001E


NEMA Manual Starters 38-7
Starters and Switches
February 2007
Type B100, Single- and Three-Phase Starters

Dimensions
4.72 4.98 5.13
(119.9) (126.5) (130.3)
1.02 2.56 5
2.36 3.98 (127)
1.05 (101.1) (25.9) (65.0)
(59.9) (26.7)

.92
(23.4) 9.19
7.59 OFF (233.4)
(192.8)
6.0
.22 (5.6) Dia. (152.4)
4 Mtg. Holes

.09 8.28
1.63
.92
(23.4)
1.5
(38.1) 10.16
(2.3) (210.3) 38
.63 (41.4) 3.0
3.25 (76.2) (258.1)
(16.0) (82.6) 1/2 x 3/4 Conduit K.O.
2 in Each Side

1/2 x 3/4 Conduit K.O.


2 in Bottom and 2 in 6.0
Top End (152.4)
3/16-32 Mounting Screw 2.05
(52.1)
5.28 5.84
1.25 (134.1) (148.3) .17 .63
1.02 (4.3) (16.0)
(31.8) (25.9)
2.5 Type 4 Enclosed
(63.5)
Type 1 Enclosed

3.19 4.59
(81.0) (116.6)
Open, Non-reversing Starter
7.13 (181.1)
3.56
(90.4)
5.13 5
(130.3) (127)
2.56 .27
6.03 (65.0) (6.9)
(153.2)
5.13
(130.3)
8.38
12.06 (212.9)
(306.3) 4.19 9.19 8.28
10.25 (106.4) (233.4) (210.3)
(260.4)
9.41
OFF ON (239.0)

4.06 .41 (10.4) Slot


(130.1) 2 Req'd.
8.25 (209.6) 1.5
(38.1) 3.0

1 (25.4)-11.50 NPSK
2 Holes 7.77
(197.4)
1.38
(35.1) 6.31 5.97
(160.3) (151.6)

.88 2.33
.5 (22.4) (59.2)
(12.7) 4.78
6.0 (152.4) (121.4)
Type 7 & 9 Enclosed Type 12 Enclosed

Figure 38-4. Approximate Dimensions in Inches (mm)

CA08102001E For more information visit: www.eaton.com


38-8 NEMA Manual Starters
Starters and Switches
February 2007
Type B100, Single- and Three-Phase Starters

Product Selection
When Ordering Specify
■ Catalog Number of Starter with
application modifications
■ Heater Pack selection — A three-
phase starter requires three heaters,
and a single-phase starter requires
two heaters
■ Any required Accessories

Toggle Operated Type 1 Enclosure

Table 38-8. Product Selection — Toggle and Pushbutton Operated Starters


38 NEMA
Size
Open Type
Toggle
Enclosed
NEMA 1 NEMA 4 NEMA 7D, NEMA 12
Handle General Watertight, 9E, 9F & 9G for Dust-Tight
Purpose Stainless Steel  Hazardous
Locations 
Catalog Price Catalog Price Catalog Price Catalog Price Catalog Price
Number  U.S. $ Number  U.S. $ Number  U.S. $ Number  U.S. $ Number  U.S. $
Type B100 Non-reversing 2-Pole (For Single-Phase Motors and DC)
M-0 B100M0B B100S0B B100W0B B100U0B B100J0B
M-1 B100M1B B100S1B B100W1B B100U1B B100J1B
Type B100 Non-reversing 3-Pole (For Polyphase Motors) 
M-0 B100M0C B100S0C B100W0C B100U0C B100J0C
M-1 B100M1C B100S1C B100W1C B100U1C B100J1C
 One 1-inch chrome hub supplied on each end.
 NEMA 7D = NEMA 7, Class I, Group D. NEMA 9E, 9F and 9G = NEMA 9, Class II, Groups E, F and G.
 Starter does not include heaters. Select Catalog Numbers of heaters from Table 38-9.
 Tapped for 1-inch conduit on each end.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-1C

For more information visit: www.eaton.com CA08102001E


NEMA Manual Starters 38-9
Starters and Switches
February 2007
Type B100, Single- and Three-Phase Starters

Table 38-9. Heater Selection


Motor Max. Catalog Price Motor Max. Catalog Price
Full Load Fuse Number U.S. $ Full Load Fuse Number U.S. $
Current Amps Current Amps
Single-Phase Enclosed Starters  Three-Phase Enclosed Starters 
.28 – .29 1 FH03 .25 – .26 1 FH03
.30 – .33 1 FH04 .27 – .29 1 FH04
.34 – .36 1 FH05 .30 – .32 1 FH05
.37 – .40 1 FH06 .33 – .35 1 FH06
.41 – .45 1 FH07 .36 – .39 1 FH07
.46 – .50 1 FH08 .40 – .44 1 FH08
.51 – .56 1 FH09 .45 – .49 1 FH09
.57 – .63 2 FH10 .50 – .55 1 FH10
.64 – .70 2 FH11 .56 – .61 2 FH11
.71 – .78 2 FH12 .62 – .68 2 FH12
.79 – .86 2 FH13 .69 – .75 2 FH13
.87 – .95 3 FH14 .78 – .83 2 FH14
.96 – 1.04 3 FH15 .84 – .91 3 FH15
1.05 – 1.14 3 FH16 .92 – 1.00 3 FH16 38
1.15 – 1.25 4 FH17 1.01 – 1.10 3 FH17
1.26 – 1.39 4 FH18 1.11 – 1.22 4 FH18
1.40 – 1.54 5 FH19 1.23 – 1.35 4 FH19
1.55 – 1.71 5 FH20 1.36 – 1.50 5 FH20
1.72 – 1.89 6 FH21 1.51 – 1.66 5 FH21
1.90 – 2.10 7 FH22 1.67 – 1.84 6 FH22
2.11 – 2.32 8 FH23 1.85 – 2.03 7 FH23
2.33 – 2.54 8 FH24 2.04 – 2.23 7 FH24
2.55 – 2.79 9 FH25 2.24 – 2.45 8 FH25
2.80 – 3.07 10 FH26 2.46 – 2.69 9 FH26
3.08 – 3.36 10 FH27 2.70 – 2.95 10 FH27
3.37 – 3.68 10 FH28 2.96 – 3.23 10 FH28
3.69 – 4.03 10 FH29 3.24 – 3.53 10 FH29
4.04 – 4.40 15 FH30 3.54 – 3.85 10 FH30
4.41 – 4.81 15 FH31 3.86 – 4.22 10 FH31
4.82 – 5.26 15 FH32 4.23 – 4.61 15 FH32
5.27 – 5.74 15 FH33 4.62 – 5.03 15 FH33
5.75 – 6.26 20 FH34 5.04 – 5.49 15 FH34
6.27 – 6.83 20 FH35 5.50 – 5.99 20 FH35
6.84 – 7.45 25 FH36 6.00 – 6.53 20 FH36
7.46 – 8.11 25 FH37 6.54 – 7.11 25 FH37
8.12 – 8.81 30 FH38 7.12 – 7.73 25 FH38
8.82 – 9.58 30 FH39 7.74 – 8.40 25 FH39
9.59 – 10.40 35 FH40 8.41 – 9.12 30 FH40
10.41 – 11.30 35 FH41 9.13 – 9.89 35 FH41
11.40 – 12.20 40 FH42 9.90 – 10.70 35 FH42
12.30 – 13.50 45 FH43 10.80 – 11.80 40 FH43
13.60 – 14.90 50 FH44 11.90 – 13.00 45 FH44
15.00 – 16.00 50 FH45 13.10 – 14.00 50 FH45
16.10 – 17.10 60 FH46 14.10 – 15.00 50 FH46
17.20 – 18.30 60 FH47 15.10 – 16.10 50 FH47
18.40 – 19.70 70 FH48 16.20 – 17.30 60 FH48
19.80 – 21.20 70 FH49 17.40 – 18.60 60 FH49
21.30 – 22.80 80 FH50 18.70 – 20.00 70 FH50
22.90 – 24.50 88 FH51 20.10 – 21.50 70 FH51
24.60 – 26.40 90 FH52 21.60 – 23.20 80 FH52
26.50 – 28.50 90 FH53 23.30 – 25.00 80 FH53
28.60 – 30.80 100 FH54 25.10 – 26.80 90 FH54
30.90 – 33.30 110 FH55
33.40 – 36.00 125 FH56
36.10 – 38.90 125 FH57
 Single-Phase Starters require two overload heaters.
 Three-Phase Starters require three overload heaters.

Note: FH Series heaters are for Type B100 When motor and overload relay are in the
manual motor starters. Heater element same ambient and the service factor of the
selection is based on motor nameplate’s motor is 1.15 to 1.25, select heaters from the
listed full load amperes. Trip rating of this heater selection table. If the service factor is
series of elements is 125% of minimum 1.0 or less (including zero), or a maximum
motor full load amperes listed for the of 115% protection is desired, select a
element. heater one size smaller than indicated for
the amperage range required.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-1C

CA08102001E For more information visit: www.eaton.com


38-10 NEMA Manual Starters
Starters and Switches
February 2007
Type 9441, Reversing Drum Switches

Contents Application Description Operation


Description Page These drum switches are designed All of the operators may be rotated
primarily for use with single-phase 360° in 22-1/2° increments without los-
Reversing Drum Switches and squirrel cage, single-speed revers- ing the indication of the drum position.
Application Description. . . . 38-10 ible motors which may be connected A red-lined pointer is permanently ori-
Features . . . . . . . . . . . . . . . . 38-10 directly across-the-line. Typical appli- entated to the legend markings and
cations would be hoists and machine clearly indicates the selected drum
Operation . . . . . . . . . . . . . . . 38-10 tools. function regardless of the selected set-
Standards and ting for the operator. This enables the
Certifications . . . . . . . . . . . 38-10 user to “offset” the operator to afford
Wiring Diagrams . . . . . . . . . 38-10
Features the most comfortable operating posi-
■ Compact size tion. This is accomplished simply by
Dimensions . . . . . . . . . . . . . 38-11
loosening and retightening one screw.
Product Selection . . . . . . . . 38-11 ■ Front mounting — easily installed
■ Terminals front accessible —
slanted 45° for extra convenience Standards and Certifications
38 ■ Captive pressure clamps on ■ UL File No. E37316, Category NLRV
terminal screws back off with
■ CSA Guide No. 184-N-13.13A,
screw — no prying with screwdriver
necessary Class 3211
■ Choice of operators
❑ Large
❑ Lever
❑ Knob
■ Orientation of operator indepen-
dent of legend — 360° positioning in
22-1/2° increments — pointer
Type DB and DD remains oriented to legend
■ Field convertible from maintained to
momentary operation
■ Replaceable, large volume, silver
plated contacts
■ Oiltight machine cavity or surface
mounting types
■ Modern attractive appearance

Wiring Diagrams

Single-Phase Motors Single-Phase Motors Polyphase Motors F1 DC Motors


L2
F1 F2
L2 1 2 S2 T5 1 2 T4 L2 1 2 T5 L2 1 2 T5 L1 1 2 T1 L1 1 2 A1 Shunt Field
S1 3 4 A2 3 4 T8 T8 3 4 T8 3 4 T4 T3 3 4 L3 A2 3 4 S1 S1 S2
L1 5 6 A1 L1 5 6 T1 L1 5 6 T1 L1 5 6 T1 L2 5 6 T2 L2 5 6 S2 Series Field
A1 A2
A1 A2 T1 T4 T5 T1 T4 T1 T2 T3 Arm
Arm T1 F2
T8 T5 T8 T8 T5
S1 S2 For Shunt Motor
Split- Split- M Add Jumper
Universal Phase Capacitor
3-Wire 4-Wire 3-Phase 3-Wire Series, Compound, Shunt
Capacitor-Start
Repulsion-Start Induction,
Repulsion, Repulsion-Induction

Figure 38-5. Wiring Diagrams

For more information visit: www.eaton.com CA08102001E


NEMA Manual Starters 38-11
Starters and Switches
February 2007
Type 9441, Reversing Drum Switches

Dimensions
Table 38-10. Approximate Dimensions and Shipping Weights
Size Type of Dimensions in Inches (mm) Shipping
Operator Wide High Deep Mounting Lever Weights
A B C F Lbs. (kg)
D E
Surface Mounting
DB1 & Lever 2.50 (63.5) 5.88 (149.4) 4.38 (111.3) 2.00 (50.8) 2.25 (57.2) 1.88 (47.8) 3.0 (1.4)
DB2 Knob 2.50 (63.5) 5.38 (136.7) 3.00 (76.2) 2.00 (50.8) 2.25 (57.2) 1.38 (35.1) 3.0 (1.4)
DD1 & Lever 3.38 (85.9) 6.88 (174.8) 4.75 (120.7) 2.63 (66.8) 2.75 (69.9) 2.00 (50.8) 4.0 (1.8)
DD2 Knob 3.38 (85.9) 6.25 (158.8) 3.63 (92.2) 2.63 (66.8) 2.75 (69.9) 1.38 (35.1) 4.0 (1.8)
Cavity Mounting
DB1 & Lever 4.00 (101.6) 4.75 (120.7) 5.00 (127.0) 3.50 (88.9) 4.00 (101.6) 1.88 (47.8) 3.0 (1.4)
DB2 Knob 4.00 (101.6) 4.50 (114.3) 4.50 (114.3) 3.50 (88.9) 4.00 (101.6) 1.38 (35.1) 3.0 (1.4)
DD1 & Lever 4.50 (114.3) 5.75 (146.1) 5.25 (133.4) 4.00 (101.6) 4.50 (114.3) 2.00 (50.8) 4.0 (1.8)
DD2 Knob 4.50 (114.3) 5.13 (130.3) 4.63 (117.6) 4.00 (101.6) 4.50 (114.3) 1.38 (35.1) 4.0 (1.8)
38
F 3.50 (88.9)
Size DB1 and DB2
3.88 (98.6)
EB Size DD1 and DD2
E B

3.00 (76.2)
D F Size DB1 and DB2
D C A C 3.25 (82.6)
A Size DD1 and DD2

Figure 38-6. Approximate Dimensions Figure 38-7. Approximate Dimensions Figure 38-8. Approximate Dimensions
Surface Mounting Cavity Mounting Panel Cutout Cavity Mount

Product Selection
When Ordering Supply
■ Catalog Number

Type DB1 Type DB and DD Type DB1 Type DB and DD


Flush Mount Surface Mounting Flush Mount Surface Mounting
Standard Lever Standard Lever Knob Operator Knob Operator

Table 38-11. Reversing Drum Type without Overload Relay


Maximum Horsepower Size Type of Surface Mounting Flush or Cavity Mounting
Operation General Purpose — NEMA 1 (Oiltight Mounting
on Sizes DB and DD)
3-Phase Single- DC Lever Knob Price Lever Knob Price
Phase Operator U.S. $ Operator U.S. $
200 – 230V 380 – 575V 115V 230V 115V 230V Catalog Number Catalog Number
3-Pole
2 2 1-1/2 2 1 1 DB 1 Maintained  9441H268 9441H269 9441H274 9441H275
Maintained and 9441H271 9441H272 9441H276 9441H277
Momentary 
3 5 1-1/2 2 1 1 DB 2 Maintained  9441H353 9441H354 9441H347 9441H348
Maintained and 9441H356 9441H357 9441H349 9441H350
Momentary 
5 7-1/2 1-1/2 3 2 3 DD 1 Maintained  9441H284 9441H285 9441H388 9441H287
7-1/2 10 2 5 2 3 DD 2 Maintained  9441H361 9441H363 9441H362 9441H364
 These devices are field convertible from maintained both positions to momentary both positions.
 These devices are field convertible from maintained FORWARD and momentary REVERSE to momentary FORWARD and maintained REVERSE.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-1C

CA08102001E For more information visit: www.eaton.com


38-12 NEMA Manual Starters
February 2007

38

For more information visit: www.eaton.com CA08102001E

You might also like