WATER COOLING TOWER OPTIMIZATION

SYSTEM

As part of our firm’s mission, Real Time Service’s Advanced-Control Group offers its Water
Cooling Tower Optimization System - a system that can achieve energy savings and reduce
the environmental impact of your heat dissipation equipment.

Cooling towers: your process cooling sources

Industrial process and machines generate most important variables are air temperature
enormous amounts of heat, which must be and air relative humidity. However,
dissipated continuously if these equipments barometric pressure and wind velocity can
are required to work in a proper, efficient cause strong effects. Both temperature and
fashion. Cooling towers allow the control of humidity have daily cycles due night and
the cooling process by means of controlled day, and seasonal cycles in the year. The
evaporation, thus reducing the amount of effect of both variables is condensed in the
water which is consumed. When the outer wet bulb temperature, which is the
film of the water drops in contact with air is dynamic equilibrium temperature achieved
evaporated, it requires some heat at the water surface when the heat flow
absorption which comes from the water transferred to the surface by convection
drops, and so the drops get cooler. Cooling equals the mass flow which exits the
is made by sensible heat, as well as by surface. Tower performance is affected by
latent heat. So, the main goal pursued by weather conditions, but there are more
the cooling tower is that the drops keep in effects to overcome. Actually, the tower is
contact with air as long as possible. This is part of an energy interchanging circuit, so
achieved by placing obstacles and fillings whenever production levels are changed or
which facilitate the cooling process even new cooling services are enabled, hot water
more. temperature will vary. Water quality is also a
As in any heat exchanger, a weather major issue, because heat exchange
variation affects the tower performance. The depends strongly on this value.

An optimum solution for your plant

Each plant has its own singularities singularities, the degree of automation
regarding to instrumentation and automation wanted and the economical benefits that are
level. That is why our solution is almost expected to be attained, our customers may
tailored-made. Depending on these choose among the different proposed

Cooling Water Optimization System Page 1 of 6


systems. The main control goal is to meet Control Technologies, Fuzzy Logic and
the cooling demand from the plant. This Neural Networks).
demand may be expressed by the product of Finally, as there can be various final control
cold water temperature and flow, though outputs like fan motors and pumps, and
many times only the cold water temperature many measurements, several possible
is demanded. Various implementation solutions may arise. Then, an on-line
solutions are given including different optimization for the whole system may be
automation control system, instrumentation viable, in order to make the control system
and final control elements. capable of responding in the best way and
attaining net energy savings.
Control system As seen, the proposed architecture is very
First, plants where no automation is present flexible, and it can adapt itself ton ay feature
for its cooling towers are highly benefited required in each particular plant.
when an automatic control is introduced
either optimized or not. Automatic control Instrumentation
systems are always more efficient than The amount of information available about
manual control operation. In this scheme, the process variables is strongly related to
the single measurement of cold water the degree of control effectiveness. Here,
temperature and comparing it to a given set the degree of control effectiveness includes
point can decide if more or less air is the concepts of efficacy, efficiency, quality,
needed in order to meet the actual cooling availability and safety. According to the
demand. Of course, the more efficient the improvement program, the instrumentation
control, the higher energy saving. The needed for facing a cooling water
control strategy can be implemented at optimization may consist in just a
different layers, from a software advising the measurement of the cold water temperature
operator what to do, a PC-based control with and a fan actuator mechanism. Of course, a
OPC communication capabilities, in order to great amount of added value can be
get data from the DCS, to a single PLC attained with the complete measurement of
commanding the tower performance all variables — hot and cold water
interacting with the DCS. Actually, as there temperatures, air wet bulb temperature or
may be several engines, a non-trivial relative humidity, barometric pressure, inlet
decision has to be made about how many of and outlet water flows, fan and pumps
them should be on or off, or what the speed states, electrical power consumed in the
should be. That is why the only way to engines, and so. Obviously, investments
improve the capability of a cooling tower cost must be justified by the economical
control system is the implementation of a improvement expected. In most cases, the
smart control algorithm with the ability to current tower instrumentation can be fully
select the optimum speed for each fan. exploited, so the initial cost is greatly
reduced. Anyway, any system claiming
Measurement of the more important cooling tower optimization capabilities
disturbances leads to a control system with should have the following elements:
improved capacities for responding to cold - ambient dry bulb temperature
water temperature deviations. An - inlet air wet bulb temperature
identification of the effects which the hot - cold water flow
water temperature, the water flow, the wet - cold water temperature
bulb temperature, and the air flow have on - fan actuators
the cold water temperature produced by the
tower, it is possible to obtain a faster, more
reliable control. Here we can apply the Final control elements
classical control technologies (PID, cascade,
feed forward, lead-lag), as well as the most In cooling tower optimization, these are the
advanced multi-variable loop control (RGA, main goals:
IMC, Robust Multi-variable Predictive • minimization of cooling water

Cooling Water Optimization System Page 2 of 6


consumption more pressure is needed for the air to
• minimization of electrical power flow through the system. Near the
consumption in fans damper closure, fan gets stalled and the
• minimization of electrical power power consumption at the engine goes
consumption in water pumps even higher, so special care should be
taken to avoid this situation.
Each of these problems is related to the kind Nevertheless, actual instantaneous
of control actuators. The control actions may savings can be as much as a 40%,
be classified into two types: when compared to the non-control, full-
speed fan case.
Actions regulating water flow: Water flow - IGV: IGV (Inlet Guide Vanes) are
circulation in the tower is determined by accessories mounted at the fan air inlet.
design constraints. An energy savings Essentially, they are a set of radial,
opportunity arises whenever the actual mobile blades. Pressure needed to
water flow can be less than the design flow, attain the air flow circulation is much
because the lower the amount of water to be lower than the pressure needed when
cooled, the lower amount of fresh air needed using dampers, because the blades help
and so the lower power consumption in the air to rotate in the direction of the fan
fans. If water flow must be sustained, a blades. The power consumed / air flow
water bypass configuration can be ratio is better than the dampers case,
implemented in order to reduce the amount though the costs are similar.
of water passing through the tower. - Multi-speed engines: Usually, the fans
However, an optimization algorithm is act like variable-torque loads, so the
needed in order to determine the operation power consumption is proportional to
point where actual savings occur. the cube of fan speed. As this speed is
proportional to the air flow, the best way
Actions regulating air flow: Air flow is the to control power consumption is to
more important manipulated variable. The control fan speed. Therefore, several
tower has one or more cells containing cooling tower systems contain double-
electrical fans. The power consumption in or multi-speed engines in order to
these devices is the cause of energy costs. control power consumption in a more
Different control alternatives are show efficient fashion. The most common
below: engines are double-speed engines with
4/8 poles or 4/6 poles. Such engines are
capable of operating at maximum or half
- Single-speed engines: Usually, air flow velocity (4/8) or at maximum or two-
control is manual in these devices, and thirds speed (6/8). This is a very
the operator sets them on or off effective control system for tower with
depending on the cooling demand. three or more cells, and the maximum
Many cooling tower automation possible instantaneous savings are
strategies are based on this method. about a 70%, when compared to the
However, there can be an intrinsic non-control, full-speed fan case. In spite
energy waste and too much cooling, of this, a major level of intelligence at
since power consumption is not the control system is needed in order to
proportional to the demand explore the best savings opportunities
compensation, but fixed — when a fan while keeping the cooling demand
is running, it is consuming its maximum satisfied.
power. - Variable-speed engines: As said, the
- Dampers: The use of automatic most efficient way to obtain energy
dampers is a choice for modulating the savings is to vary fan speed directly.
air flow and thus the power consumed. This can be automatically adjusted
In this case, there are energy savings using a variable frequency drive, which
but also an energy waste, because can convert power from 50 Hz (60 Hz)

Cooling Water Optimization System Page 3 of 6


to a 0 to 100 Hz frequency. By doing drives allow a soft start, by eliminating
this, the synchronization speed of an the power peaks during motor starts.
induction engine is determined. This

Get direct benefits...

Today, economical success for any world, and of course by energy prices.
business requires an efficient use of energy An optimized cooling tower system must
consumed in their respective processes. meet this constraint. Energy savings needs
Energy conservation faces a strong not only a basic automation like turning fans
incentive for examining common designing on and off according water temperature, but
criteria and building and operation features. also an effective control involving every
Energy savings are not only a strictly variable of interest, each uncertainty source
economic matter. Nowadays, energy as a and an optimization system for getting the
scarce resource which must be conserved is highest economical benefits, while taking
becoming a popular concept, and this is care of the environment and keeping your
reflected by several regulations around the plant as cool as it needs to be.

... And get additional advantages

Our cooling tower optimization system will environmental reasons, but there are other
also lead you to a series of additional effects that should be mentioned. Air exiting
advantages: the tower is warm and very humid, and
these characteristics are ideal for
Environment Care: reduction of industrial microorganisms to develop. These can
waste water into natural watersheds. affect vegetal, animal and human life by
Pouring industrial water into rivers or lakes causing diseases. Our cooling tower
may be cheap but it can lead to dangerous optimization system is aware of this potential
situations. Natural water temperature may problem, and thus limits the amount of water
grow, so the local flora and fauna will be evaporated.
exposed. More concerned to human life,
water used in cooling circuits is usually Operation & Maintenance Improvement:
fresh, drinkable water, which is perhaps the Elimination of floods and blockages
most important natural resource. An One of the most common problems in
optimized cooling water system keeps an cooling tower modulation is caused by the
eye on the water consumed, so it can filling. If this filling is dirty, water circulation
regulate the amount of water used for through the tower may be stopped, causing
cooling the industrial processes in a smart, floods. When this occurs, air cannot move in
safe way. the tower, so no cooling is produced.
Additionally, as the fans are on, power
Environment Care: reduction of water consumed by them will actually grow, and
consumed by evaporative cooling. there can be damages.
Cooling water are evaporative cooling Another problem is water blockage. This
devices. Part of the hot water entering the happens when water flow is very high, so
tower gets evaporated and exits the tower the area where air can move through gets
with the air. This is a loss of water to the smaller and so the air flow is reduced. A
refrigerant system, so more water should be different problem is air blockage. When air
added in order to replace it. This amount of flow gets very high, water will not flow
water must be minimized for economical and across the filling in a proper way, so the heat

Cooling Water Optimization System Page 4 of 6


exchange is reduced strongly. are needed. On the other hand, changes in
There is a lack of diagnosis for these plant production can have impact in cooling
problems in common control systems. But in water temperature, so it can be necessary to
our system this situation is rapidly identified, switch on or off some fans. There can be
corrected and reported before they have filtrations or leaks and water composition
actual consequences in plant production. may change, leading to algae formation,
scalding, corrosion or oxidation. This can
Operation & Maintenance Improvement: lower remarkably the heat transfer in the
Reduction in Equipment Maintenance tower and degrade the equipments.
Tasks. This is why cooling tower needs supervision.
A smart control system is a system that In a system without automation, operator
takes into account all the characteristics of learns to work with the cooling tower,
its components. Most of the reactive activating or deactivating fans as the plant
maintenance tasks are produced by demands. Wet bulb temperature is neither
equipment faults due to operation at ranges measured nor considered in the control
outside the manufacturer specifications. decision. Most automated system free the
Many maintenance engineers often say that operator of control decision taking, but they
it is not possible to keep in good condition do not consider the effect of wet bulb
something that cannot be seen. temperature either. As a result, automatic
In a cooling tower system, equipment control may not work as expected, thus
requiring maintenance is fans, pumps, requiring some sort of supervision. Our
engines, the water distribution system and optimized cooling tower system can take
so. It is true that inspection at operation into account all variables involved in the
condition of this equipment may be a cooling process, and take always the right
complex task. However, a smart control decision, so reliability is better and
system can realize when any of these supervisory actions are less frequent.
elements is being used outside its
specification range or when it is degrading. Improved Quality
For instance, a reduction in the heat transfer If the area in charge of cooling tower
coefficient, which can be estimated indirectly management is engaged to its services
from measured variables at operation quality, then a series of policies ensuring
conditions, is a clear sign that the water service uniformity should be implemented.
distribution system is degrading by Not only should cooling towers cool the plant
corrosion, scalding, or that filling is water, but also should do it well. Quality is
corrupted, or that there can be obstructions an inherent property of an optimized cooling
at the air inlet or outlet. The control system tower system, because in each control
is not likely to overcome these problems by decision, a major care is taken in order to
itself, but it can report this situation to the meet all the requirements: plant cooling
maintenance staff before the effects of this demands, tower’s own constraints, and
degrading affect plant production, telling atmospheric conditions. In addition, all non-
what and where to find out. So, a reliability- measured variables are indirectly monitored,
centered maintenance policy can be and possible dangerous situations for
implemented, reducing the reactive equipments, environment and human life are
maintenance tasks. discovered before they can affect them. This
also prevents unwanted shutdowns in the
Operation & Maintenance Improvement: cool water supply. The overall system then
Reduction in Supervisory Tasks by effect boosts improved quality.
of improved reliability
Atmospheric variations make cooling tower
performance change. In hot, humid days, As a result, control system robustness
operators must activate more fans than in ensures stability of flows, temperatures and
cold, dry days. Also, at night there is always cooling water composition, while
a decrement in temperature, so fewer fans optimization techniques allow the choice of

Cooling Water Optimization System Page 5 of 6


the best control decision, involving both maintenance, energetic demand penalties or
direct costs (electric power costs, production environment penalties) and keeping your
demand) and indirect costs (reactive plant cooling demand always satisfied.