Professional Documents
Culture Documents
ARTICLE
Table of Contents
Introduction
Types of Chillers
Introduction
Chillers are a key component of air conditioning systems for large buildings. They
produce cold water to remove heat from the air in the building. They also provide
cooling for process loads such as file-server rooms and large medical imaging
equipment. As with other types of air conditioning systems, most chillers extract heat
from water by mechanically compressing a refrigerant.
Chillers are complex machines that are expensive to purchase and operate.
A preventive and predictive maintenance program is the best protection for this valuable
asset.
Chillers commonly use more energy than any other piece of equipment in large
buildings. Maintaining them well and operating them smartly can yield significant energy
savings.
Types of Chillers
Mechanical Compression
During the compression cycle, the refrigerant passes through four major components
within the chiller: the evaporator, the compressor, the condenser, and a flow-metering
device such as an expansion valve. The evaporator is the low-temperature (cooling)
side of the system and the condenser is the high-temperature (heat-rejection) side of
the system.
Mechanical Compressor Chillers
Mechanical compression chillers are classified by compressor type: reciprocating, rotary
screw, centrifugal and frictionless centrifugal.
Rotary Screw: The screw or helical compressor has two mating helically grooved rotors
in a stationary housing. As the helical rotors rotate, the gas is compressed by direct
volume reduction between the two rotors. Capacity is controlled by a sliding inlet valve
or variable-speed drive (VSD) on the motor. Capacities range from 20 to 450 tons.
Centrifugal: The centrifugal compressor operates much like a centrifugal water pump,
with an impeller compressing the refrigerant. Centrifugal chillers provide high cooling
capacity with a compact design. They can be equipped with both inlet vanes and
variable-speed drives to regulate control chilled water capacity control. Capacities are
150 tons and up.
Absorption Chillers
Absorption chillers use a heat source such as natural gas or district steam to create a
refrigeration cycle that does not use mechanical compression. Because there are few
absorption machines in the Northwest U.S., this document covers only mechanical-
compression chillers. You can learn more about absorption chillers at the Energy
Solutions Center.
Key Components of Mechanical Compression
Chillers
Evaporator
Chillers produce chilled water in the evaporator where cold refrigerant flows over the
evaporator tube bundle. The refrigerant evaporates (changes into vapor) as the heat is
transferred from the water to the refrigerant. The chilled water is then pumped, via the
chilled-water distribution system to the building's air-handling units.
The chilled water passes through coils in the air-handler to remove heat from the air
used to condition spaces throughout the building. The warm water (warmed by the heat
transferred from the building ventilation air) returns to the evaporator and the cycle
starts over.
Compressor
Vaporized refrigerant leaves the evaporator and travels to the compressor where it is
mechanically compressed, and changed into a high-pressure, high-temperature vapor.
Upon leaving the compressor, the refrigerant enters the condenser side of the chiller.
Condenser
Inside the condenser, hot refrigerant flows around the tubes containing the condenser-
loop water. The heat transfers to the water, causing the refrigerant to condense into
liquid form. The condenser water is pumped from the condenser bundle to the cooling
tower where heat is transferred from the water to the atmosphere. The liquid refrigerant
then travels to the expansion valve.
Controls
Newer chillers are controlled by sophisticated, on-board microprocessors. Chiller control
systems include safety and operating controls. If the equipment malfunctions, the safety
control shuts the chiller down to prevent serious damage to the machine. Operating
controls allow adjustments to some chiller operating parameters. To better monitor
chiller performance, the chiller control system should communicate with the facility's
direct digital control (DDC).
Safety Issues
Chillers are typically located in a mechanical equipment rooms. Each type of refrigerant
used in a chiller compressor has specific safety requirements for leak detection and
emergency ventilation. Consult your local mechanical code or the International
Mechanical Code for details.
The EPA has enacted regulations regarding the use and handling of refrigerants to
comply with the Clean Air Act of 1990. All personnel working with refrigerants covered
by this act must be appropriately licensed.
Operate multiple chillers for peak efficiency: Plants with two or more chillers can
save energy by matching the building loads to the most efficient combination of one or
more chillers. In general, the most efficient chiller should be first one used.
Raise chilled-water temperature: An increase in the temperature of the chilled water
supplied to the building's air handlers will improve its efficiency. Establish a chilled-water
reset schedule. A reset schedule can typically adjust the chilled-water temperature as
the outside-air temperature changes. On a centrifugal chiller, increasing the
temperature of chilled water supply by 2-3°F will reduce chiller energy use 3-5%.
Purge air from refrigerant: Air trapped in the refrigerant loop increases pressure at the
compressor discharge. This increases the work required from the compressor. Newer
chillers have automatic air purgers that have run-time meters. Daily or weekly tracking
of run time will show if a leak has developed that permits air to enter the system.
Optimize free cooling: If your system has a chiller bypass and heat exchanger, known
as a water-side economizer, it should be used to serve process loads during the winter
season. The water-side economizer produces chilled water without running the chiller.
Condenser water circulates through the cooling tower to reject heat, and then goes to a
heat exchanger (bypassing the chiller) where the water is cooled sufficiently to meet the
cooling loads.
Maintain refrigerant level: To maintain a chiller's efficiency, check the refrigerant sight-
glass and the superheat and subcooling temperature readings, and compare them to
the manufacturer's requirements. Both low-level and high-level refrigerant conditions
can be detected this way. Either condition reduces a chiller's capacity and efficiency.
Maintain a daily log: Chiller O&M best practices begin with maintaining a daily log of
temperatures, fluid levels, pressures, flow rates, and motor amperage. Taken together,
these readings serve as a valuable baseline reference for operating the system and
troubleshooting problems. Many newer chillers automatically save logs of these
measurements in their on-board control system, which may be able to communicate
directly with the DDC. Below is an example of a daily log that can be adapted for use
with your chiller.
To effective maintain chillers, you must 1) bring the chiller to peak efficiency, and
2) maintain that peak efficiency. There are some basic steps that facilities professionals
can take to make sure their chillers are being maintained properly. Below are some of
the key practices.
Checking the water treatment of the chilled-water closed loop monthly will reduce the
frequency of evaporator tube cleaning and the possibility of a tube failure.
Inspecting and cleaning tubes: The tubes in the evaporator and condenser bundles
should be inspected once a year, typically when the chiller is taken offline for
winterizing. Alternately, for systems that operate all year to meet process loads, tube
scaling and fouling can be monitored by logging pressure drop across the condenser
and evaporator bundles. An increase in pressure from the inlet to the outlet of 3-4 PSI
indicates a probable increase in scale or fouling requiring tube cleaning.
DESCRIPTION COMMENTS
Fill out daily log Check all setpoints for proper setting and function
Check chilled water reset settings and function Check settings for approved sequence of operation
Check chiller lockout setpoint Check settings for approved sequence of operation
Clean evaporator and condenser tubes Indicated when pressure drop across the barrel (tub
Verify motor amperage load limit Motor amperage should not exceed manufacturer's
Compressor motor and assembly Conduct vibration analysis: Check all alignments t
Compressor oil system Perform analysis on oil and filter. Change if neces
Check refrigerant condition Add refrigerant if low. Record amounts and addre
Check for condenser and evaporator tube corrosion and clean as needed. Indications include: poor water quality, excessive
Cooling Towers
ARTICLE
Table of Contents
Introduction
Types of Cooling Towers
Key Components of Cooling Towers
Safety Issues
References
Introduction
Cooling towers are heat exchangers that use water and air to transfer heat from air-
conditioning systems to the outdoor environment. Most commonly, they are used to
remove heat from the condenser water leaving a chiller. Cooling towers are usually
located on rooftops or other outdoor sites. Because they are frequently out of sight, they
are often neglected by operation-and-maintenance technicians, resulting in lower
cooling-system efficiency. This document will help you adopt best practices for the
efficient operation and maintenance of cooling towers.
Types of Cooling Towers
There are two basic types of cooling towers, open and closed (sometimes called direct
and indirect).
Water Distribution
Hot water from the chilled-water system is delivered to the top of the cooling tower by
the condenser pump through distribution piping. In an open tower, the hot water is
sprayed through nozzles onto the heat transfer medium (fill) inside the cooling tower.
Some towers feed the nozzles through pressurized piping; others use a water-
distribution basin and feed the nozzles by gravity. In a closed-loop tower, the water from
the condenser loop runs through tubes in the tower and is not exposed to the outside
air. Water for cooling the tubes circulates only in the tower.
In the open tower, a cold-water collection basin at the base of the tower gathers cool
water after it has passed through the heat transfer medium. The cool water is pumped
back to the condenser to complete the cooling-water loop. In the closed tower, the
condenser water cools as it moves through the piping in the tower and returns to the
chiller plant.
Air Flow
Large volumes of air flowing through the heat-transfer medium help increase the rate of
evaporation and the cooling capacity of the tower. The cooling-tower fans generate this
airflow. The size of the cooling-tower fan and airflow rate are selected to achieve the
desired cooling at design conditions of condenser-water temperatures, water flow rate,
and wet-bulb temperature.
Cooling towers may have propeller fans or squirrel-cage blowers. Small fans may be
connected directly to the driving motor, but most designs require an intermediate speed
reduction provided by a power belt or reduction gears. The fan and drive system
operate in conjunction with the control system to control start/stop and speed. Variable-
speed drives (VSDs), when added to the fan motors, control fan speed and more
precisely regulate the temperature of the water as it leaves the tower.
Drift Eliminator
As air moves through the fill, small droplets of cooling water become entrained and can
exit the cooling tower as carry-over or drift. Devices called drift eliminators remove
carry-over water droplets. Cooling-tower drift becomes annoying when the droplets fall
on people and surfaces downwind from the cooling tower. Efficient drift eliminators
virtually eliminate drift from the air stream.
Safety Issues
Water Treatment
Cooling-tower water must be regularly treated, generally with chemicals, to prevent the
growth of harmful bacteria, minimize corrosion, and inhibit the buildup of scale (mineral
deposits) on the fill.
Maintenance Personnel
Cooling towers are often placed in precarious locations, and inspection ports can be
located in awkward or exposed locations. This can create a hazardous working
environment. Be sure to implement adequate fall-prevention measures and procedures.
In addition, always follow lock-out and tag-out safety procedures.
Consider a condenser water reset strategy: The temperature set point of the water
leaving the cooling tower should be at least 5°F (adjustable according to the design)
higher than the ambient wet-bulb temperature. If the Direct Digital Control (DDC)
system has a wet-bulb temperature sensor, this can be done automatically. Otherwise
the operator should consider manually adjusting the set point seasonally.
Close the bypass valve before starting the cooling-tower fans: Make sure the DDC
control sequence prevents the tower fans from starting before the cooling-tower bypass
valve is fully closed. If the bypass valve isn't fully closed, hot water leaving the chiller
short circuits into the water returning to the chiller, adding unnecessary load to the
compressor.
Trend log the temperature of the water leaving the tower: Use the trend
logging capability of the DDC to track the temperature of the water leaving the tower.
Higher than normal temperatures may indicate that the tower in not operating properly.
Prevent scale deposits: When water evaporates from the cooling tower, the minerals
that were dissolved in it are left behind as scale deposits on the surface of the fill. Scale
build-up inhibits heat transfer from the water to the air, which reduces the fill's
effectiveness. Excessive scale build-up is a sign of inadequate water treatment.
Prevent or clean clogged spray nozzles: Algae and sediment that collect in the water
basin as well as excessive solids that get into the cooling water can clog the spray
nozzles. This causes uneven water distribution over the fill and uneven airflow through
the fill, which reduces evaporation. These problems indicate improper water treatment
and clogged strainers. Kits are available to replace older, smaller distribution nozzles or
troughs with large-orifice, clog-free designs.
Ensure Adequate Airflow: Poor airflow through the tower reduces the transfer of heat
from the water to the air. Poor airflow can be caused by debris at the inlets or outlets of
the tower or in the fill, loose fan and motor mountings, poor motor and fan alignment,
poor gearbox maintenance, improper fan pitch, damage to fan blades, or excessive
vibration. Reduced airflow due to poor fan performance can ultimately lead to motor or
fan failure.
DESCRIPTION COMMENTS
Fan motor condition Check the condition of the fan motor through temperature or vibration analysis and
Operate make-up water float switch Operate switch manually to ensure proper operation
Check tower structure Check for loose fill, connections, leaks, etc.
Test for proper concentrations of dissolved solids, and chemistry. Adjust blowdow
Test water samples
systems.
Check lubrication Assure that all bearings are lubricated per the manufacture's recommendation
Check motor supports and fan blades Check for excessive wear and secure fastening
Motor alignment Aligning the motor coupling allows for efficient torque transfer
Check drift eliminators, louvers, and
Look for proper positioning and scale build up
fill
Inspect nozzles for clogging Make sure water is flowing through nozzles in the hot well
Clean tower Remove all dust, scale, and algae from tower basin, fill, and spray nozzles
Check bearings Inspect bearings and drive belts for wear. Adjust, repair, or replace as necessary.
Motor condition Checking the condition of the motor through temperature or vibration analysis assu
Water Distribution
ARTICLE
Table of Contents
Introduction
Types of Water Distribution Systems
Hydronic System Types
Constant- and Variable-Flow Pumping Systems
Pumping System Arrangements
Key Components of Water Distribution Systems
Safety Issues
Best Practices for Efficient Operation
Best Practices for Maintenance
References
Introduction
Many large buildings and campuses have HVAC water-distribution systems, also called
hydronic systems. Water is heated or cooled in a central plant, then pumped to air
handlers, where ventilation air is conditioned as needed.
Maintaining and optimizing the performance of pumps and valves-the key mechanical
components of water-distribution systems-can be challenging. These systems often
have hidden performance problems that waste energy and cause excessive wear on
equipment.
As with other mechanical components of the HVAC system, a preventive and predictive
maintenance plan is an excellent way to maintain an efficient system, save energy
dollars, prevent costly breakdowns, and extend equipment life.
Condenser water: Condenser water loop moves water between the chiller's condenser
and the cooling tower. These systems are usually open loops.
Constant flow: A constant flow rate is maintained throughout the hydronic loop
whenever the system is operating. Flow rates are established for a peak design
condition, which represents a small fraction of total operating hours.
Variable flow: Variable-flow pumping can be accomplished in several ways:
Valves: Manual or automatic valves regulate the flow of water throughout the piping
system. Valves perform four basic functions: 1) starting, stopping, and directing flow;
2) regulating or throttling flow; 3) preventing backflow; and 4) relieving or regulating
pressure.
Balance valves, also called circuit setters, are a special type of regulating valve that limit
flow at design conditions. This allows the system to be balanced so that every coil in the
system has adequate flow. Excessive pressure drop across these valves can waste a
considerable amount of energy.
Valve components
Pipe and other system components: Pipes connect all components and, with the
possible exception of hydronic-heat-pump loops, should be insulated per local codes.
Other system components that need to be operated and maintained properly are
expansion tanks, strainers, and gauges for pressure and temperature.
Safety Issues
Working near rotating pump shafts and couplings can be dangerous. Control panels for
electrical motors and electrical connections on pump motors present a shock hazard.
Heating-water systems are dangerous if not fully insulated, so be careful not to touch
uninsulated piping without first checking its temperature.
Always observe lock-out and tag-out procedures during maintenance.
Monitor the make-up water meter: A quick way to spot a leak in a closed-loop
hydronic system is to monitor the meter on the system make-up water inlet. Reading the
meter daily or weekly and comparing the readings to historical averages can help
identify problems.
Investigate valve chatter: Valve chatter or water hammer coming from control valves
may indicate overpressurization at the valve. High pump pressure or system imbalance
can exceed the valve's actuator shut-off rating and cause water to pass through the
"closed" valve and thereby cause the chatter. Water passing through a "closed" valve
causes overcooling or overheating, thereby destabilizing control and wasting energy.
Generally, the shut-off pressure limit for 2-way valves with vertical actuators should be
25% greater than maximum pump head. Two-way valves with rotating actuators use a
much lower torque. Three-way valves do not need as high a limit as vertical 2-way
valves since they simply divert flow. Rebalancing or, as a last resort, replacing the valve
actuator with one with a suitable higher pressure limit may fix the problem. Confirm the
correct operating parameters of the valves in your system before making any changes.
Investigate parallel pumping: Most variable-flow systems have one on-line (or lead)
pump and one standby (or lag) pump. At higher flow rates, it can be more energy
efficient to operate both pumps in parallel. A typical control sequence is for the lead
pump to operate alone until twice its minimum flow rate is reached, then the lag pump
cycles on and the two pumps operate together in parallel on the same speed-control
signal. An engineering professional should determine the best strategy for your
particular system.
Best Practices for Maintenance
Pumps are a vital part of HVAC and process-load applications. Pump efficiency directly
affects the efficiency of other system components.
Inspect system weekly: At least once a week, a building engineer should walk the
entire system and check piping, valves, and pumps for leaks and unusual noise. Noise
often indicates hidden valve or pump problems. Sources of noise include turbulence,
cavitation, release of entrained air, and water hammer.
Ensure adequate water treatment: Scale and sludge deposits reduce flow and impair
heat transfer. An ongoing water-treatment program is critical to efficient equipment
operation throughout the distribution system.
Test valve stroke: Test each automatic valve annually. Conduct a test where the valve
actuator moves the valve stem through the entire range of the stroke. Failure to move
smoothly through the entire range indicates a problem.
Test pump efficiency annually: Testing the efficiency of large pumps and comparing it
to previous benchmarking data will help spot developing problems.
DESCRIPTION COMMENTS
Test water Test for proper concentrations of dissolved solids and chemistry.
Check lubrication Ensure that all bearings are lubricated according to manufacturer'
Check packing Check packing for wear and repack as necessary. Consider replac
Check mechanical seals Check for leakage that exceeds the manufacturer's specifications.
Motor/pump alignment Align the pump/motor coupling to ensure efficient torque transfer
Check bearings Inspect bearings and drive belts for wear. Adjust, repair, or replac
Check expansion tanks Inspect these tanks to make sure that the acceptance capacity is ad
Inspect heating and cooling heat exchangers. Temperature differences may indicate air binding, clogged straine
Cycle valves Observe the valves moving through their full range from closed to
Motor condition Check the condition of the motor through temperature or vibratio
Introduction
Creating a best-practice operation-and-maintenance (O&M) program increases the
efficiency of facility staff, improves building operational practices, and reduces utility
costs. The O&M process helps sustain a building's profitability by reducing costly
equipment failure and maintaining tenant comfort and indoor air quality. Establishing an
O&M program is generally straightforward and does not significantly affect budget. It
primarily reorganizes and reallocates existing resources to be more efficient and
productive. Implementing a best-practice O&M program can reduce facility energy use
by 5-20% without significant capital investment. This document discusses the elements
essential to creating a best-practice O&M program.
Members of the leadership team should include representatives from the executive,
finance, and engineering branches of the organization. Participation of an upper-level
manager is key to sending the message that the program is supported from the top of
the organization. Appoint an O&M project manager as the project leader and focal point
for accountability. Early participation of line-level engineering staff is essential to the
long-term success of the O&M program. As with any initiative, be sure to establish roles,
responsibilities, and communication channels.
Assign someone to coordinate with the utilities. Your local utility may be the most
important source of outside assistance. They may help fund or provide technical support
for establishing an O&M program or a building tune-up.
Recognize success
Employee recognition will help sustain enthusiasm and interest for achieving energy-
use goals. Use recognition, awards, and meaningful incentives to encourage the entire
staff to develop ideas for improving building performance. Ultimately, the success or
failure of the new O&M Program lies with the line-level staff. Meeting or exceeding
building-energy-performance goals should be an occasion for sharing a sense of a job
well done by all.
What is a champion?
The champion is someone who is responsible for the overall management of a building
or system. The champion is knowledgeable of, and an advocate for, the proper design,
use, operation, and maintenance of the building or system. The champion understands
the details and knows how to meet management's goals and objectives in the safest,
and most cost-effective way possible.
Educate themselves and others on the proper design, use, operation, and
maintenance of the system to minimize the life-cycle cost, and maximize the
performance of the system.
Participate in all decisions regarding the design, use, operation, and
maintenance of the system.
Work with management to establish and track key performance indicators for the
system.
Recommend operational or maintenance changes to improve system
performance.
What does a system champion need to succeed?
Track performance
The O&M project manager and the leadership team should review and adjust energy-
use goals as necessary. The perpetual question should be, "How can we be more
energy efficient?" When operational changes (in equipment scheduling or space use, for
example) are made, or equipment is added or replaced, it is appropriate to adjust the
goals accordingly. Provide monthly feedback to building-operation staff on building-
energy use relative to goals and benchmarks. Building-energy-performance data should
be easily accessible to all employees.
Benchmarking will identify buildings with higher than normal energy use. These are the
best targets for a building tune-up. If your organization has more than one building, a
strategic approach is to identify one building that most needs improving, conduct the
building tune-up at that building, then expand the program to build on that initial
success.
Identify organizational activities that affect O&M and building-energy use, and
incorporate a long-range perspective into these related activities. For example, the
decision to purchase replacement equipment should consider long-term or life-cycle
operating costs. A low-first-cost option may have costly long-term effects. Many utilities
offer rebate programs to help offset the higher first cost of high-efficiency
equipment. Service contracts are another area where a lowest-first-cost option may
have adverse long-term effects.
Reactive: This is the "run it until it breaks" approach. In the short run, this saves
staff time and expense but over time it is costly in terms of unplanned equipment
downtime, repairs, and shorter equipment life.
Preventive: Preventive maintenance (PM) occurs at time intervals or at run-hour
milestones. Because HVAC equipment is capital intensive, this is more cost-effective
than reactive maintenance.
Predictive: This approach uses periodic measurements to detect evidence that
machinery is deteriorating, with the aim of extending service life by avoiding impending
problems. Special diagnostic equipment, which requires additional staff training, is
needed, but it will maximize equipment life and efficiency.
Most organizations use a combination of reactive and preventive maintenance with or
without maintenance-service contractors. Generally, the most cost-effective solution is a
combination of preventive and predictive maintenance that appropriately balances
prevention and repair.
While these systems go a long way toward improving the efficiency of maintenance,
there are some common pitfalls in adopting them. Chief among these is inadequate
training of administrative and maintenance staff, which leads to lack of commitment and
integration into existing practices.
A CMMS integrated into daily operation with well-trained personnel and persistent
management support will yield considerable benefits in the form of improved
maintenance, more efficient use of staff resources, better inventory control, better
maintenance of equipment performance, reduced downtime, and extended equipment
life.
Large facilities have a variety of types and complexity of HVAC and process systems.
While maintenance can be performed entirely in-house or entirely outsourced, most
organizations use a mix of in-house operating engineers and outside service
contractors. Typically, specialized and complex equipment such as building-automation
systems (BAS) or chillers are serviced by outside contractors, but a well-trained staff
may be capable of many specialized maintenance tasks that are typically outsourced.
Emergency repair work is often handled by mechanical or service contractors. Each
building or organization will have a somewhat unique balance of in-house and
outsourced tasks.
Inventorying the skills and licenses of in-house engineering staff will reveal if their skills
are being used effectively. Likewise, gaps in training may become apparent. Evaluate
how well the employee skills match the complexity of the installed systems and local,
state and federal licensing requirements. Assess the level of management and
supervisory experience required to provide the leadership needed to execute a best-
practice O&M program.
Conducting a building tune-up can provide a snapshot of the level of O&M practiced in
the facility. This will inform the future staffing and training needs.
Developing staff training plans should combine supervisory input and individual interest.
Large buildings with modern systems are sufficiently complex to encourage individual
staff members to become in-house experts in different areas. A staff with good basic
skills and diverse advanced technical skills is invaluable in maintaining and operating a
complex building, and will reduce reliance on outside contractors. Regularly update
individual and group training plans.
Conduct annual training reviews, possibly as part of annual performance reviews. The
O&M leadership team should provide input to the supervisory staff on training needs
and goals.
All large facilities use a mixture of maintenance, mechanical, electrical, and lighting
service contractors to help perform the many tasks that keep complex building systems
operating smoothly. The range of outsourced tasks will vary from building to building.
This section offers suggestions for managing contractors with ongoing service
contracts:
Most of the suggestions below apply equally to a building tune-up and to ongoing
enhanced O&M.
Evaluate providers
There are many types of service contractors. With your maintenance strategy,
outsourcing needs, and scope of work in mind, select an appropriate type of service
provider.
When you have identified the appropriate type(s) of service providers to bid on the work,
consider the selection criteria in the reference below. For a complex building, a pre-bid
contractor meeting including a building walkthrough is highly recommended. This will
help communicate the organization's requirements and should elicit similarly scoped
bids.
There are many factors to consider in describing the scope of services in a service
contract. The reference below describes contractual details that will serve the owner
best over the term of the contract.
For information on structuring service contracts, see Contract Provisions for Enhanced
Operations and Maintenance.
The reference below provides insight into effectively managing a service contractor.
When the contract is executed, establish clear lines of communication and set specific
protocols to follow. Set up a feedback system for monitoring contractor performance.
Periodically review measurable objectives with the contractor. Use a quarterly report
card as part of the feedback system and let them know when they're doing a good job.