II-282/1198
Page 1 of 8
Initiating Initiating
TFX-400 Device Device System Block Diagram
Circuit Circuit
Line
Addressable
Loop #1 Isolator
(SLC)
(4B/6B)
IXA- IXA-
500CMA 500DMA CAA-500LI IXA-RMS 912I 912P 912HP 912H 900D/900DR
Notification
Appliance Relay Output Agent
Circuit Circuit Releasing
Addressable
Loop #2
(SLC) OXA-
506SDA 504SDA IXA-RMS GAR-1 OXA-502RM GARA-1 506SDA/RM
TFXnet
(IBN-552/553/554)
ISN- ISN- IHN- IHN-
550I 550P 135 200 ISN-550DI/DP/R
TFX-500
TFX-400
Remote Bus
and
DC Power
Graphic Annunciator
TFX-800
Up to 7
Remote
Operator
Control
Panels
FireGraph
RS-232
II-282/1198
Page 2 of 8
Addressable Manual Analog Addressable Relay Base - IBN-553
Stations - IXA-RMS Duct Smoke • Provides a single form
Series Detectors - 900 Series C relay contact output
for auxiliary control (2A
• Die cast metal construc- • Ionization or photo- @ 30VDC, 400mA @
tion electric 125VAC)
• Low profile, functional design • Integral alarm LED • Individual and zonal activation
• Terminals for field wiring • Remote LED output Sounder Base - IBN-554
• Powered directly by signaling circuit • Rugged steel backbox with clear
(no additional power required) plastic cover • Produces 85db audible signal
• Programmable for one second alarm • Detector address in the base pro- • Modulated sound for increased audi-
reporting vides easy device identification bility
• Dual action option • Analog reporting of measured smoke • Individual and zonal activation
• Break glass option density
Analog Addressable
• Hex screw or key lock reset option • Pre-alarm and alarm threshold Duct Smoke
• Automatic compensation prevents Detectors -
Analog Addressable Smoke sensitivity drift
Detectors and Heat Detectors - • Detector service/cleaning messages 550 Series
900 Series • Chamber design provides high sta- • Ionization or photo-
electric
• Detector address in bility (photoelectronic models)
• Polling/alarm LED
the base is visible • 2 sets of form C alarm relay contacts
from the floor (10A @ 24VDC/120VAC) • Remote LED output
• Complete service and maintenance • Rugged steel backbox with clear
from the floor; no ladders required Analog Addressable Smoke plastic cover
• Low profile appearance Detectors and Heat Detectors - • Xpert address card provides easy
• Attractive design 550 Series device identification
• Interchangeable 4" and 6" bases • Detector address in the base visible • Analog reporting of measured smoke
from the floor density
• Designed for fast and easy installa- • Complete service and maintenance • Installation without cover removal
tion
from the floor - no ladders required • Automatic compensation prevents
• Integral alarm LED • Low profile appearance sensitivity drift
• Remote alarm LED output • Plug-in interchangeable 2-wire base • Detector service/cleaning messages
• Nonpolarized wire connections • Tamper resistant locking head • Detector with 2 auxiliary relays avail-
• Optional locking kit • Remote LED output able (10A @ 24VDC/120VAC)
Smoke Detector - 912 Series • Nonpolarized wire connections • LED indicates relay operation
• Ionization or photo- • High EMF/RFI noise immunity
electric Smoke Detector - 550 Series
• Analog reporting of • Ionization or photoelectric
measured smoke den- • Analog reporting of
sity measured smoke den-
• Detector service/cleaning messages sity
• Pre-alarm and alarm threshold • Detector service/cleaning
messages
• Automatic compensation prevents • Pre-alarm and alarm threshold
sensitivity drift
• Chamber design provides high sta- • Automatic compensation prevents
bility (models 912P and 912HP) sensitivity drift
• Meets NFPA 72 Chapter 7 Annual • Interchangeable bases
Sensitivity Testing Requirements • Fine mesh insect screen
Heat Detector - 912H Series • RFI/EMI immunity
• Analog reporting of • Removable cover for field cleaning
alarm level tempera- Heat Detector - 550 Series
ture • Analog reporting of
• Two temperature se- alarm level temperature
lections • Two temperature selec-
tions
II-282/1198
Page 3 of 8
Addressable Field Modules Notification Appliance Agent Releasing Kits -
Module - OXA-504SDA 506SDA/RM
Contact Monitor Module -
IXA-500CMA and IXA-501CM
• Provides a Class B (Style • Provides a Class B
Y) or Class A (Style Z) noti- (Style Y) releasing cir-
• Supervises and monitors fication appliance circuit cuit
dry contact devices • Supervises 24VDC appliance power • LED annunciation at each device for
• Normally open and normally closed without supervisory relay normal, activated, and trouble condi-
programmable options (IXA- • 2.5 amp output rating tions
500CMA) • 2 Amp output rating
• IXA-500CMA mounts on stan- • Silenceable and non-silenceable op-
dard 2-gang electrical box
eration • High EMF/RFI noise immunity
• High EMF/RFI noise immu- • High EMF/RFI noise immunity • Power-limited
nity Notification Appliance Addressable Agent Releasing
• Powered directly by signaling Module - 506SDA Stations
circuit (no additional power required)
• Provides a Class B (Style
• Programmable for normal or fast Y) or Class A (Style Z) au- Agent Releasing Station - GAR-1
(polling interrupt) alarm reporting dio or DC, notification ap- Series
• IXA-501CM fits inside standard elec- pliance circuit • Releasing station con-
trical Box • LED annunciation at each device for structed of die-cast metal
Detector Monitor Module -
normal, activated, and trouble condi- • Low profile, functional de-
tions sign
IXA-500DMA • Supervises 24VDC appliance power • Dual action
• Supervises and monitors without the need for a supervisory
Agent Releasing Station - GARA-1
2-wire smoke and heat de- relay
tectors Series
• 2 A @ 24VDC, 50W @ 25/70VRMS • Same features as
• Supervises 24VDC detector power on output rating
2-wire loop GAR-1 series
• Silenceable and non-silenceable op- • Abort switch
• Resets detectors on command from eration
control panel • High EMF/RFI noise immunity • System activated
• Class B (Style B) and Class A (Style indication
• Will not operate into a short circuit
D) initiating circuits fault • System normal indication
• Contains bicolored LEDs to display • Plug-in power-limiting option
alarm fault status
• High EMF/RFI noise immunity Line Isolator Module -
CAA-500LI
Relay Module - OXA-502RM
• Provides one form C pro- • Isolates short circuits on
signaling circuit to prevent
grammable relay contact failure of entire circuit
(2A @ 24VDC, 0.6A @
120VAC) • Automatically resets on correction of
short circuit
• Monitored and controlled from a sig- • Status LED indicates short circuit de-
naling line circuit (addressable loop)
tection
• Powered by signaling line circuit. No • No external power required
external power
• LED indicates relay operation • High EMF/RFI noise immunity
• High EMF/RFI noise immunity • Can be configured to meet NFPA
Style 7 requirements
II-282/1198
Page 4 of 8
Remote Operator Control Panel Remote Reporting Options TFX Panel Operation
Option Digital Alarm Communicator Transmitter • Each panel can be configured to re-
• Up to seven SK5128 spond to events from all or any subset of
remote an- • 4 reporting other panels
nunciators channels • Up to 3 panels can be configured to pro-
per TFX-400 • Dual phone line vide full system annunciation, control and
• Red fire monitor with line seizure logging; configuring two panels as identi-
alarm LEDs cal receiving units provides hot backup
• Field configurable to transmit in one of central monitoring equipment
• Yellow supervisory LED of eight different formats
• Yellow fault LED • “Virtual Front Panel” (VFP) feature allows
• Used with SRA-550 supplemental operator interrogation and control of any
• Yellow isolate LED relay assembly panel from any other panel
• Green power-on LED City Box Transmitter - CEB-500 • All TFX-500 and TFX-800 features and
• Enable key switch • NFPA 72 Auxiliary capabilities are retained
• Panel silence button and yellow LED Protective Signaling • TFX panels can be configured with inte-
• Alarm silence button and yellow LED Systems grated single and multiple channel voice
Reverse Polarity Trans- and audio evacuation equipment when
• System reset button and yellow LED required.
• Drill button and red LED mitter - CVB-500
• Three programmable yellow LEDs • NFPA 72 Remote Sta- FireGraph
tion Protective Signaling Systems Option
• Lamp test
• Internal buzzer AUTOCALL TFXnet Option • FireGraph PC
• Seven optional sockets accept red, yel- based graphi-
Grinnell’s AUTOCALL TFXnet is a fault resil- cal user inter-
low or green LEDs for special require- ient and flexible peer-to-peer communi- face connects
ments cations network. Up to 62 AUTOCALL directly to the
Optional Operator Display Module TFX series fire panels connect to a single network
• 80 charac- AUTOCALL TFXnet network; supports up • PC based multi-
ter (40 pro- to 61,380 analog, addressable points. user head end sys-
gram- The TLI-530 module operates as the in- tem provides security integration and
mable) terface between a TFX panel and the virtually unlimited expansion; supports
alphanu- TFXnet Network. One TLI-530 is required multiple 62 panel networks
meric dis- per TFX and is installed onto the TFX
play Printer Option
main processor board.
• Numeric touch-pad • Panels maintain full • Hard-copy text printing
• No/delete button of alarm and trouble
stand-alone functionality events
• Scroll up button
• Scroll down button Communications • Convenient, versatile paper han-
dling
• Yes/enter button • True peer-to-peer communications; no
host or master controller • High speed printing
• Quit button • Node failure does not affect remainder of • Quiet operation
• Fast access button network • Simple control panel
Optional 16-Indicator Module • Groups of nodes isolated due to circuit • Compact design
• Red zone faults continue to communicate within the
alarm LEDs group Video Display Option
• Yellow zone • Supported communication media - com- • Displays system status
trouble binations of fiber optic, twisted/shielded and events
LEDs pair and dedicated telephone line ca- • 25, 42, or 53 data lines
bling • 14" flat-profile, antiglare
• Supported topologies - combinations of screen
star, bus, and ring connections • Selectable page size - 24, 25, 36, 42, 48,
• Token-passing, non-collision (determinis- 50, and 72
tic) communications protocol with pat- • Tilt and swivel adjustments
ented half-bit communications delay
• Plug-in module connects equipment any- • Self test
where on the network
II-282/1198
Page 5 of 8
Specifications
AUTOCALL TFX-400 is intended for use within a building interior, free from
exposure to moisture, condensation and excessive dust.
Temperature Range: 32°F (0°C) to 122°F (49°C)
Relative Humidity: 85% (noncondensing)
Battery Space Available in Cabinet: 7 1/4"H x 14" W x 4 7/8" D
Analog, Addressable Signaling Lines
Loop Styles: NFPA 72 Style 4 and 6. Line isolators optional
for short circuit isolation.
Maximum Addresses per Loop: 99
Maximum Loops per System: Two (2)
Voltage: 26VDC, 300mA
Supervisory Current: 20mA per loop (plus load)
Alarm Current: 24mA per loop (plus load)
Resistance: Maximum 75 Ohms
Capacitance: Maximum 0.5 microfarad (mutual)
Inductance: Maximum 1.5 millihenry (total)
Maximum Continuous Distance: 6500 feet
II-282/1198
Page 6 of 8
3/4" AND 1" CONDUIT
KNOCKOUTS
TOP AND BOTTOM
(TYPICAL)
SURFACE
14.25"
MOUNTING
1.50"
WALL LINE
SEMIFLUSH
MOUNTING
WALL LINE
2.00" 2.00"
1.50"
14.75"
19.875" 20.25"
5.25"
5.13"
Cabinet Dimensions
Ordering Information
Part No. Model Description
976422 TFX-400 Fire alarm control panel
Addressable Manual Stations
976277 IXA-RMS Addressable pull station
976407 IXA-RMS-KL Addressable manual station, single action, keylock reset
Smoke, Duct, and Heat Detectors
515462 912I Ionization smoke detector head, amalog, addressable
515463 912P Photoelectronic smoke detector head, analog, addressable
515464 912HP High performance photoelectronic smoke detector head, analog, addressable
515461 912H Heat detector head, analog, addressable with programmable setting (135°F fixed
temperature/rate-of-rise or 200°F fixed temperature)
515467 4B 4" base, low profile w/remote LED output
515468 6B 6" base, low profile w/remote LED output
515472 900K Detector address key, unprogrammed, package of 10
515476 600/900LK Detector head locking kit, package of 100
515465 900D Duct detector housing, analog, addressable, less detector head
515466 900DR Duct detector housing, analog, addressable, with relay, less detector head
920095 ISN-550I Analog ionization smoke detector head, low profile
920096 ISN-550P Analog photoelectric smoke detector head; low profile
920097 IHN-135 Analog heat detector head, 135 degree F, low profile
920098 IHN-200 Analog heat detector head, 200 degree F; low profile
920192 IBN-552 6" low profile addressable base with remote LED output
920194 IBN-553 6" addressable relay base with remote LED output
920195 IBN-554 6" addressable sounder base with remote LED output
920102 ISN-550DI Duct housing with analog ionization smoke detector head
920103 ISN-550DP Duct housing w/analog photoelectric smoke detector head
920353 ISN-550DPR Duct housing w/analog photoelectric head and auxiliary relays
920354 ISN-550DIR Duct housing w/analog ionization head and auxiliary relays
II-282/1198
Page 7 of 8
ANALOG, ADDRESSABLE
FIRE ALARM SYSTEM
AUTOCALL ®
TFX-400 Series
This literature does not cover all the variations in the equipment described, nor does it provide for every possible contingency to be met in connection with installation, operation and
maintenance. All specifications and listings are subject to change without notice. If you need more information on this product, or have a question, contact Grinnell Fire Protection Systems Com-
pany, Westlake, Ohio 44145. © 1998 Grinnell Fire Protection Systems Company, a Division of the Grinnell Corporation. AUTOCALL® is a registered trademark of the Grinnell Corporation.
835 Sharon Drive, Westlake, Ohio 44145
Phone: (440) 899-5445; FAX (440) 871-2301
http://www.grinnellfire.com
A tyco INTERNATIONAL LTD. COMPANY
II-282/1198