Pry 20 00026 MC Eal 2 A1 - Sala Eléctrica 1
Pry 20 00026 MC Eal 2 A1 - Sala Eléctrica 1
6 Page: 1
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_7_3 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020
Project description:
2 x 1.5" 180° Sidewall Nozzles 10109 - 10111
2 x 0.5" 180° Sidewall Nozzles 10117 - 10119
Pipesystem data:
Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers
No: node [m] [m] [inch] ** * code coefficient FK-5-1-12 quantity
Legend of pipetypes
Type Pipeclass Pipe roughness
10 schedule 40 smooth
13 schedule 40 black pipe
Legend of components
Code Type Resistance coefficient
323 SEVO 322 LB/2 1/2" (CV140057) W/ 2 1/2" Flex Hose 6.300
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 4
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_7_3 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020
Nozzle data:
Legend of nozzles:
Type Number of C1 C2 C3 C4 C5 C6
orifices
1 Nozzle 1 1 0.10652 0.26900 0.23203 -0.20251 0.00000 0.00000
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 5
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_7_3 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020
Zone Total Volume of Calculated Total Max. Over- Design Extinguish- Design Design Design
volume building volume surface pressure temp. conc. factor conc. quantity
[m3] parts [m3] [m3] [mbar] [°C] [% Vol] [% Vol] [kg]
1 Ambiente 247.5 0.0 247.5 257.9 1.000 20.0 3.3 1.35 4.5 114.24
2 Piso falso 39.9 0.0 39.9 130.9 1.000 20.0 3.3 1.35 4.5 18.41
Regulation rule for calculation of FK-5-1-12 quantities: NFPA 2001, Edition 2018
Calczone no. 1: Class C Fire, NFPA 2001 (Edition 2018)
Calczone no. 2: Class C Fire, NFPA 2001 (Edition 2018)
Altitude above sealevel: 2600.0 m
Atmospheric correction factor: 0.704
Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 6
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_7_3 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020
Calculation results:
Discharge time:
Discharge time air: 0.2 s
Total gas discharge time: 0.6 s
Two-phase discharge time: 7.9 s
Total discharge time: 8.5 s
System information:
Container working pressure: 12.0 bar abs
Container working temperature: 18.7 °C
Total network volume: 35.7 l
Medium pipe content: 43.8 kg FK-5-1-12
Filling portion in pipe system: 0.33 kg FK-5-1-12 /kg FK-5-1-12 -storage
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 7
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_7_3 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020
Pipe system:
Section- Starting- Endnode Pressure Flowrate Pipedimension
No: node [bar abs] [kg/s] Di [mm] DN
Nozzle data:
Concentrations:
Component list:
Nozzle-type Number C1 C2 C3 C4 C5 C6
10 52.50 2 0.800
13 62.70 2 1/2 0.300
13 52.50 2 8.400
13 40.90 1 1/2 6.200
13 26.60 1 9.600
13 15.80 1/2 6.800
1 2 1 0 2
1 2 1 1/2 1 1/2 0
1 1 1/2 1/2 0