You are on page 1of 12

FACULTY : UniKL MICET EDITION: 1

LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020

SECTION OF CHEMICAL PROCESS


MALAYSIAN INTITUTE OF CHEMICAL & BIOENGINEERING TECHNOLOGY

PROCESS CONTROL LABORATORY


LABORATORY INSTRUCTION SHEETS

COURSE CODE
EXPERIMENT NO. EXPERIMENT 2

EXPERIMENT TITLE Gas Flow Process Control Plant


DATE
GROUP NO.
1)
LECTURER/INSTRUCTOR/TUTOR
2)
DATE OF REPORT SUBMISSION
ATTENDANCE/PARTICIPATION/DISIPLINE: /5%

INTRODUCTION: /5%

PROCEDURE: /5%
RESULTS& CALCULATIONS /15%
ANALYSIS /15%
DISTRIBUTION OF MARKS FOR DISCUSSIONS: /20%
LABORATORY REPORT: ADDITIONAL QUESTIONS /15%
CONCLUSION /10%
SUGGESTIONS& RECOMENDATIONS /5%

REFERENCES: /5%

TOTAL: /100%

EXAMINER COMMENTS: RECEIVED DATE AND STAMP:


FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020

STUDENT CODE OF ETHICS

SECTION OF CHEMICAL PROCESS TECHNOLOGY

MALAYSIAN INSTITUTE OF CHEMICAL & BIO


ENGINEERING TECHNOLOGY

I hereby declare that I have prepared this report with my own efforts. I also admit to

not accept or provide any assistance in preparing this report and anything

that is in it is true.

1) Group Leader: ………………………………………….. (Signature)


Name : __________________________________
Matrix No. : __________________________________

2) Group Member 1: ………………………………………. (Signature)


Name : __________________________________
Matrix No : __________________________________

3) Group Member 2:……………………………………….. (Signature)


Name :__________________________________
Matrix No. : __________________________________

4) Group Member 2:……………………………………….. (Signature)


Name :__________________________________
Matrix No. : __________________________________
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020
1.0 OBJECTIVES
a) To study gas volumetric flow rate measurement using orifice plate.
b) To study gas mass flow rate measurement using orifice plate and perfect gas
law to compute the gas density from the pressure and temperature
measurements.
c) To study gas mass flow rate (Fm) control using PID controller.

2.0 LEARNING OUTCOMES


At the end of the study, student will be able to:
a) To be familiar with the basic steps of machine from start-up to shut-down
with proper handling and setting.
b) To gain knowledge about pressure and temperature variation using Perfect
Gas Law
3.0 INTRODUCTION
The air flow process control training system uses air to simulate a gas or
vapor phase flow process. Gas/vapor volumetric flow can be measured either by
the differential pressure across orifice or by a variable area flow meter.
Compensation for pressure and temperature variation using Perfect Gas Law
can be made to the flow measurement by the differential pressure
measurement.

4.0 INSTRUMENTS /APPARATUS / CHEMICAL / REAGENTS


4.1 Gas volumetric/mass flow measurement system
a) Integral orifice flow element, FE91.
b) Differential pressure flow transmitter with square root function, FT91.
c) Absolute pressure transmitter, PT91.
d) RTD temperature transmitter, TE91/TIT911.
4.2 Apparatus
a) Air Flow process control training system. The schematic diagram is shown in
Figure 1.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020

Figure 1: Schematic diagram of Air Flow Process Control Training System


FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020
5.0 PROCEDURE
The following steps constitute the start-up procedure. Go through these
steps before starting any experiment:

1. Switch the "PANEL, SCADA/DDC" selector switch at the front of the cubicle
to "PANEL, SCADA" position. Switch ON the main power supply at the front
of the cubicle. All the panel instruments will lit up.
2. From the process air supply, trace the two pipelines, PLI and PLII as follows:

Pipeline I (PLI):
AR900-MV900A-T90-MV900D-PLI-FI911-TE911-FE91/FT91-FCV91-FCV1-VF
Pipeline II (PLII):
AR900-MV900A-T90-MV900D-PLII-FCV90-PG902-V

3. Open valves of the pipelines PLI and PLII at their various STATUS. Close the
manual by-pass valve of the control valve FCV91 and the ON/OFF control
valve FCV90.
4. The pipeline PLI has two discharge manual valves, VF and MV901. Open the
vent VF and close the valve MV901.
5. Make sure the valves MV900A and MV900D are open and valves MV900B
and MV900C are shut.
6. Place the panel controller FIC91 in the Manual (M) mode. Open fully the
control valve FCV91 by setting the MV of FIC91 to -6.3%.
7. Adjust the manual valve MV900A till the air flow rate is about 50 kg/hr
(Read the flow rate from PV of FIC91).
8. Check that vent valve and bottom drain valve of vessel T90 are shut. Set MV
= 106.3% at FIC91 to fully shut the control valve FCV91.
9. Check control valve FCV91 (in the plant) is fully shut and FI911 reads the
air volumetric flow rate as ZERO. Also check the mass flow rate Fm at FIC91
is ZERO.
10. Now set the MV = 50% at FIC91 and check control valve FCV91 (in the plant)
is 50% opened.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020
11. Note the variables that are recorded in each channel of the recorder FPTR91.
Red Pen - Mass flow rate (kg/hr)
Green Pen - Volumetric flow rate (m3/hr)
Blue Pen - Temperature (°C)

A. AIR FLOW MEASUREMENT


1. Set the MV = -6.3% (in Manual mode) so that control valve
FCV91 is fully opened. Record the reading/data in Table 1.
shown in results section.
2. Data to be taken AT THE CONTROL PANEL:
i) Access the following data by pressing the corresponding
push buttons in FIC91 and FIC90:
FIC91
PID1(main page): PV - Fm, kg/hr
I/O DATA: X1 - FT91, % of , 0 - 100
X2 - TIT911, % of 0 - 120°C
X3 - PT911, % of 0 - 60 psia
FIC90
P/T REGISTER: PO1 - Fv, m3/hr
ii) At the Recorder: Fv (Channel 2, Green) and Fm (Channel
1, Red)
3. Data to be taken AT THE PLANT:

Locate the rotameter FI911 and pressure gauge PG900. Take both
instruments’ readings and also note the units used. (Rotameter
reading should be taken as ±0.5 Nm3/hr)

Now, take another sets of readings for MV = 50% and MV = 70% and
record them in the Table 1 in the results section.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020

B. CONTROL OF AIR FLOW SYSTEM


1. With FIC91 in Manual (M) mode, open the control valve FCV91
fully with MV = -6.3%. (For confirmation, check the stem position
indicator of control valve FCV91. FCV91 is an Air-To-Close (ATC)
valve)
2. With FIC91 still in Manual mode, adjust its setpoint, SV = 25
kg/hr.
3. Access the PID parameters of FIC91 and set the first (I) PID trial
values:
PB = 200%, TI = 6 s, TD = 0 s
4. Start the recorder chart drive by pressing “RCD” pushbutton at
FPTR91.
5. Switch FIC91 to Auto (A) mode and watch the recorder
response (i.e. air flow response) until the air flow (red pen) is
fairly steady.
6. Introduce a pulse disturbance by quickly opening and shutting
fully the by-pass valve at control valve FCV91. Observe the
response till it becomes fairly steady.
7. Repeat step (6) (i.e. introducing pulse disturbance) with the
second (II) and third (III) sets of PID trial values:

II III
PB = 150% PB = 100%
TI = 6s TI = 6s
TD = 0s TD = 0s

DO NOT FORGET TO MARK THE PID VALUES AND THE SET-


POINT ON THE CHART PAPER WHENEVER THE VALUES
ARE CHANGED. ALSO MARK ON THE CHART THE
BEGINNING OF EACH PART OF THE EXPERIMENT.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020
8. Repeat the experiment for another 3 sets of PID trial values
with step change in setpoint for the mass flow rate by
changing the present setpoint of FIC91 from SV= 25kg/hr to
SV = 30 kg/hr. Observe and record the response till it becomes
fairly steady.
9. Switch back the setpoint SV = 25 kg/hr. Use the first (I) PID
trial value but now with TD = 20 s. Mark the PID values on
the chart paper simultaneously.
10. Apply the disturbance by opening and shutting fully the by-
pass valve at control valve FCV91 and observe the response.

C. PID CONTROLLER TUNING


1. Set FIC91 in Manual (M) mode with setpoint SV = 25 kg/hr.
Adjust the PID values to the following:
PB = about 100%, TI = 9999 s (Maximum), TD = 0 s
(Minimum)
2. By setting TI to maximum value and TD to minimum value, we
can eliminate these two modes in a PID controller (use PB only).
3. Manually adjust MV in FIC91 until the PV value closes to the
setpoint SV value (SV = 25 kg/hr).
4. Transfer FIC91 to Auto (A) mode. Introduce a setpoint pulse
disturbance as follows:
i) Set increase SV to 28 kg/hr
ii) Hold the value for 5 seconds
iii)Bring back the SV to 25 kg/hr
5. Observe the mass flow rate (red pen) response. Repeat the
Closed Loop Tuning Method as above with a decreasing PB
value until uniform oscillation (constant amplitude) is observed.
(To increase oscillation, decrease PB value and vice versa)

Figure 1: Uniform oscillation


FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020

6. Examine the chart response for the uniform oscillation.


7. New PID value from tuning procedures can be obtained as
follows:
i. PB corresponds to uniform oscillation = PB* ultimate
(corresponds to ultimate gain, Kcu)
ii. Distance between two adjacent peaks = Tn* ultimate
(ultimate period, Pu) Tn* can be calculated from this formula:

measurement (mm)x 3600


𝑇𝑛 ∗ = 500mm
chartspeed( hr
)

iii. The approximate PI controller settings by using Ziegler


Nichols formula are:
PB = 2 X PB*, TI = Tn*/1.2
8. To test this new PI controller settings, set this value into FIC91
(in Auto mode) perform the test with a pulse disturbance.
Increase PB value to damp the oscillation and fine tune the PB
and TI values to get as close to Quarter Amplitude Damping
response.

Figure 2: Quarter Amplitude Damping Response (Blue pen)


FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020
D. SHUTDOWN PROCEDURE
1. Stop the recorder chart by pressing ”RCD” button at recorder
FPTR91.
2. Switch FIC91 to Manual mode with MV = 0%.
3. Switch off the main power supply.
4. Shut off the process air supply at AR900.
5. Shut off the instrument air supply.

6.0 RESULTS & CALCULATIONS


A. The recorder FPTR91 records the results of the experiments. Suitable
portions of the recorder chart paper should be submitted as RESULTS of
the experiment.
B. The report should contain:
i) The P&I Diagram with all major components marked clearly.
ii) The instruments readings taken simultaneously and recorded for
different valve opening positions.
iii) Comparison between direct instrument data with calculated data for
Fvb and Fm
iv) The PID flow control responses for disturbances and setpoint changes
for different controller settings.
v) Discussion on the response characteristics for different controller
settings.
vi) Tuning by Ziegler Nichols method and its response.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020
Instrument Reading Controller I II III
MV=6.3% MV=50% MV=70%
At the panel FIC91, I/O Data
FT91, √ℎ X1 - %of 0-100mm
TIT911, T X2 - %of 0-120oc
PT911, P X3 - %of 0-60psia
FIC91, Main Face plate
Fm PV, kg/Hr
FIC91, Main Face plate
Fv PO1, m3/Hr
Recorder FPTR91
Channel 1(Red) Fm , kg/Hr
Channel 2(Green) Fvb , m3/Hr

By Calculation Fvb , Nm3/Hr


Fm , kg/Hr
At the Plant
FI911, Nm3/Hr
PG900 , psig

7.0 ANALYSIS OF THE RESULTS

Analysed critically each results obtain in section 6.0 by referring to the


theory/introduction parts. Find reasons (suggested reasons) on each
occurrence shown in the results.

8.0 DISCUSSIONS
Discuss the overall experiment on data obtain based on your understanding.
Discussion should relate reasons for the phenomena/results obtained,
theoretical parts, suggested reasons (if necessary but back with sound
theoretical knowledge) and your overview understanding.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 2
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: GAS FLOW 2014
PROCESS CONTROL AMENDMENT 20 FEB
DATE: 2020
9.0 ADDITIONAL QUESTIONS
i. Water has been analysed for pH, conductivity and dissolve oxygen. What
does each of this measurement tell you about the water?
ii. Includes short essay on your understanding on pH, conductivity and
dissolve oxygen. Relate your discussion on the requirement of industrial
effluent released (if applicable).

9.0 CONCLUSION
Conclusion is merely a summary of the important findings already reported
in the discussion section. It also relates to the objectives stated earlier.

10.0 SUGGESTIONS & RECOMMENDATIONS


Your ideas of suggestion & recommendation to improve the learning process
for this experiment or anything related to the experimental procedure etc.

11.0 REFERENCES
Minimum of at least 5 references (with 3 of them are paper/book/chapter
based)

You might also like