You are on page 1of 23

Saad Group Head Office Lighting Calculations Page No.

( 1 ) of ( 23 )
Design Office / Electrical Dept.

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Male Prayer- 1-st Level/1st Floor Total Area : 38.5 m². Net Working Height : 4.5 m.
Standard Required Illuination (E) : 300 Lux rc : 0.8 rw : 0.3 rf : 0.1 X: 1.3 K : 0.684444

Light Unit : Made by : AS will be Supplied Cat. No.: Chandelier (Big Size) Refrance : Our Standard Page No. --
Light Type : Led Colour : Normal Each Unit has : 1 X 24 W Uf : 0.4211

The Avarege no. of Units : 15 The Avarege Luminance : 328.10 Lux


Luminaire Spacing : Along Length : 1.000 m. (From Center-to-Center) The Space Height Ratio : Along Length : 0.2222
Along Width : 2.750 m. (From Center-to-Center) Along Width : 0.6111

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Male Prayer- 1-st Level/2nd Floor Total Area : 121.545 m². Net Working Height : 4.5 m.
Standard Required Illuination (E) : 300 Lux rc : 0.8 rw : 0.3 rf : 0.1 X: 1.3 K : 1.127766

Light Unit : Made by : AS will be Supplied Cat. No.: Chandelier (Big Size) Refrance : Our Standard Page No. --
Light Type : Incndescent Colour : Normal Each Unit has : 9 X 100 W Uf : 0.4253

The Avarege no. of Units : 10 The Avarege Luminance : 290.72 Lux


Luminaire Spacing : Along Length : 8.325 m. (From Center-to-Center) The Space Height Ratio : Along Length : 1.8500
Along Width : 1.460 m. (From Center-to-Center) Along Width : 0.3244

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Mosque -Female Prayer- 2nd Floor Total Area : 338.625 m². Net Working Height : 2.65 m.
Standard Required Illuination (E) : 300 Lux rc : 0.8 rw : 0.3 rf : 0.1 X: 1.3 K : 3.430417

Light Unit : Made by : AS will be Supplied Cat. No.: Chandelier (Big Size) Refrance : Our Standard Page No. --
Light Type : Incndescent Colour : Normal Each Unit has : 9 X 100 W Uf : 0.7572

The Avarege no. of Units : 15 The Avarege Luminance : 278.66 Lux


Luminaire Spacing : Along Length : 5.250 m. (From Center-to-Center) The Space Height Ratio : Along Length : 1.9811
Along Width : 4.300 m. (From Center-to-Center) Along Width : 1.6226

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : A/C Room - 2nd & 3rd Floor Total Area : 20.4597 m². Net Working Height : 2.92 m.
Standard Required Illuination (E) : 150 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.33 K : 0.763262

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 5735A/2 36XF.61 Refrance : Cat. 2002/2003 Page No. A-37
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 36 W Uf : 0.3435

The Avarege no. of Units : 1 The Avarege Luminance : 141.37 Lux


Luminaire Spacing : Along Length : 5.370 m. (From Center-to-Center) The Space Height Ratio : Along Length : 1.8390
Along Width : 3.810 m. (From Center-to-Center) Along Width : 1.3048

Copyright@25/12/2006
By: Eng. Mohammed S. El-Refaey
516572341.xls - Results 03/30/2021 11:15:08
Saad Group Head Office Lighting Calculations Page No. ( 2 ) of ( 23 )
Design Office / Electrical Dept.

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Lift Lobby - 2nd & 3rd Floor Total Area : 29.2802 m². Net Working Height : 2.92 m.
Standard Required Illuination (E) : 250 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.33 K : 0.757934

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 5735A/2 36XF.61 Refrance : Cat. 2002/2003 Page No. A-37
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 36 W Uf : 0.3053

The Avarege no. of Units : 3 The Avarege Luminance : 263.39 Lux


Luminaire Spacing : Along Length : 3.473 m. (From Center-to-Center) The Space Height Ratio : Along Length : 1.1895
Along Width : 2.810 m. (From Center-to-Center) Along Width : 0.9623

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Service Area - 2nd&3rd Floor Total Area : 30 m². Net Working Height : 2.65 m.
Standard Required Illuination (E) : 300 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.33 K : 0.984413

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 5735A/4 18XF.61 Refrance : Cat. 2002/2003 Page No. A-37
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 18 W Uf : 0.4430

The Avarege no. of Units : 4 The Avarege Luminance : 191.85 Lux


Luminaire Spacing : Along Length : 3.750 m. (From Center-to-Center) The Space Height Ratio : Along Length : 1.4151
Along Width : 2.000 m. (From Center-to-Center) Along Width : 0.7547

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Stairs Lobby - 2nd&3rd Floor Total Area : 37.1 m². Net Working Height : 3.57 m.
Standard Required Illuination (E) : 150 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.33 K : 0.737032

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 6035A/4 18XF.61 Refrance : Cat. 2002/2003 Page No. A-06
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 18 W Uf : 0.1880

The Avarege no. of Units : 10 The Avarege Luminance : 164.56 Lux


Luminaire Spacing : Along Length : 2.120 m. (From Center-to-Center) The Space Height Ratio : Along Length : 0.5938
Along Width : 1.750 m. (From Center-to-Center) Along Width : 0.4902

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Ladies Cafeteria - 2nd Floor Total Area : 581.184 m². Net Working Height : 2.77 m.
Standard Required Illuination (E) : 250 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.33 K : 4.283661

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 6035A/4 18XF.61 Refrance : Cat. 2002/2003 Page No. A-06
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 18 W Uf : 0.4300

The Avarege no. of Units : 108 The Avarege Luminance : 259.54 Lux
Luminaire Spacing : Along Length : 2.400 m. (From Center-to-Center) The Space Height Ratio : Along Length : 0.8664
Along Width : 2.242 m. (From Center-to-Center) Along Width : 0.8095

Copyright@25/12/2006
By: Eng. Mohammed S. El-Refaey
516572341.xls - Results 03/30/2021 11:15:08
Saad Group Head Office Lighting Calculations Page No. ( 3 ) of ( 23 )
Design Office / Electrical Dept.

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Males Cafeteria - 3rd Floor Total Area : 607.4827 m². Net Working Height : 2.77 m.
Standard Required Illuination (E) : 250 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.33 K : 4.375655

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 6035A/4 18XF.61 Refrance : Cat. 2002/2003 Page No. A-06
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 18 W Uf : 0.4300

The Avarege no. of Units : 108 The Avarege Luminance : 248.31 Lux
Luminaire Spacing : Along Length : 2.466 m. (From Center-to-Center) The Space Height Ratio : Along Length : 0.8902
Along Width : 2.281 m. (From Center-to-Center) Along Width : 0.8235

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Left Corridor - 2nd&3rd Floor Total Area : 97.477 m². Net Working Height : 3.57 m.
Standard Required Illuination (E) : 200 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.330 K : 1.158442

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 6035A/4 36XF.61 Refrance : Cat. 2002/2003 Page No. A-06
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 36 W Uf : 0.2717

The Avarege no. of Units : 9 The Avarege Luminance : 211.24 Lux


Luminaire Spacing : Along Length : 18.220 m. (From Center-to-Center) The Space Height Ratio : Along Length : 5.1036
Along Width : 0.594 m. (From Center-to-Center) Along Width : 0.1665

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Left Open Area - 2nd Floor Total Area : 75.555 m². Net Working Height : 2.72 m.
Standard Required Illuination (E) : 350 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.330 K : 1.5738

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 6035A/2 18XF.61 Refrance : Cat. 2002/2003 Page No. A-06
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 18 W Uf : 0.3244

The Avarege no. of Units : 24 The Avarege Luminance : 334.73 Lux


Luminaire Spacing : Along Length : 1.725 m. (From Center-to-Center) The Space Height Ratio : Along Length : 0.6342
Along Width : 1.825 m. (From Center-to-Center) Along Width : 0.6710

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No. : 54
Area Name : Printing Area - 3rd Floor Total Area : 424.96 m². Net Working Height : 2.72 m.
Standard Required Illuination (E) : 750 Lux rc : 0.8 rw : 0.3 rf : 0.1 X : 1.330 K : 3.702258

Light Unit : Made by : ‫شركة إنــارة الســـعودية‬ Cat. No.: 6035A/2 36XF.61 Refrance : Cat. 2002/2003 Page No. A-06
Light Type : Fluorescent Colour : Warm White Each Unit has : 4 X 36 W Uf : 0.4140

The Avarege no. of Units : 96 The Avarege Luminance : 787.66 Lux


Luminaire Spacing : Along Length : 2.133 m. (From Center-to-Center) The Space Height Ratio : Along Length : 0.7843
Along Width : 2.075 m. (From Center-to-Center) Along Width : 0.7629

Copyright@25/12/2006
By: Eng. Mohammed S. El-Refaey
516572341.xls - Results 03/30/2021 11:15:08
Saad Group Head Office Page No. (4) of (23)
Design Office / Electrical Dept.

Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54 Room Name : Male Prayer- 1-st Level/1st Floor
Data : Standard Required Illuination (E) : 300 Lux
Length : 7 m. Width : 5.5 m Height : 5.5 m. Total Area : 38.5 m².
Falls Ceiling (Y/N) : N 0 Suspention Height : 1 m.
Working Plane Height : 0 m. Net Height : 4.5 m
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.300
Wall Colour : White Wall Reflecting Factor (rw): 0.3 LXW
Room Index (k) = = 0.684444
Floor Colour : White Floor Reflecting Factor (rf): 0.1 Hnet X (L + W)
Lighting Unit Data :
Luminaire Manufacture : AS will be Supplied Refrance : Our Standard Page no.: -- Luminaire Unit Cat. No. Chandelier (Big Size)
Each Unit has : 1 X 24 Watts Type of Light : Led Collour of Light : Normal
Unit Dimensions : Length : 0 Cm Width : 0 Cm
Luminous / Lamp (Φn) : 2600 Lumens Total Luminus / Unit (Φt) : 2600 Lumens
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data At (k1) : 1.5 Utilization Factor (Uf1): 0.47
At (k2) : 2 Utilization Factor (Uf2): 0.5
Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.421067
K2 - K1
Calculations :
Actual No. of Units for this Area : 13.715 » 14 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X Lroom / Wroom) 4.2212 » 4 Columns
Along Width (Nw) : = Sqrt (N X Wroom / Lroom) 3.3166 » 3 Rows
Avarege Used No. of Units for this Area : 12 Units Luminaire Spacing : Along Length : 1.750 m. (From Center-to-Center)
Along Width : 1.833 m. (From Center-to-Center)
Check :
Avarege Luminance by Using ( 12 ) Units : 262.4831 Lux
The Space Height Ratio : Along Length : 0.388889
Along Width : 0.407407

Do You Need Chang The No. of Units? (Y/N) Y Please; Enter the No. of units : 15
The No. of Luminaire along Length (NL) : 7 Columns The No. of Luminaire along Width (Nw) : 2 Rows
Average Used No. of Units for this Area will be : 14 Units Luminaire Spacing along Length : 1 m. (From Center-to-Center)
Luminaire Spacing along Width : 2.75 m. (From Center-to-Center)
Avarege Luminance by Using ( 14 ) Units : 328.1039 Lux
The Space Height Ratio will be : Along Length : 0.222222
Along Width : 0.611111

Copyright@25/12/2006
516572341.xls - Area#1 03/30/2021 - 11:15:08
By: Eng. Mohammed S. El-Refaey
Saad Group Head Office
Page No. ( 5 ) of ( 23 )
Design Office / Electrical Dept.

Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54 Room Name : Male Prayer- 1-st Level/2nd Floor
Data : Standard Required Illuination (E) : 300 Lux
Length : 16.65 m. Width : 7.3 m Height : 9.5 m. Total Area : 121.545 m².
Falls Ceiling (Y/N) : N 0 Suspention Height : 5.00 m.
Working Plane Height : 0 m. Net Height : 4.5 m
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.300
Wall Colour : White Wall Reflecting Factor (rw): 0.3 LXW
Room Index (k) = = 1.127766
Floor Colour : White Floor Reflecting Factor (rf): 0.1 Hnet X (L + W)
Lighting Unit Data :
Luminaire Manufacture : AS will be Supplied Refrance : Our Standard Page no.: -- Luminaire Unit Cat. No. Chandelier (Big Size)
Each Unit has : 9 X 100 Watts Type of Light : Incndescent Collour of Light : Normal
Unit Dimensions : Length : 0 Cm Width : 0 Cm
Luminous / Lamp (Φn) : 1200 Lumens Total Luminus / Unit (Φt) : 10800 Lumens
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data At (k1) : 1 Utilization Factor (Uf1): 0.41
At (k2) : 1.25 Utilization Factor (Uf2): 0.44
Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.425332
K2 - K1
Calculations :
Actual No. of Units for this Area : 10.319 » 10 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X Lroom / Wroom) 4.7758 » 5 Columns
Along Width (Nw) : = Sqrt (N X Wroom / Lroom) 2.0939 » 2 Rows
Avarege Used No. of Units for this Area : 10 Units Luminaire Spacing : Along Length : 3.330 m. (From Center-to-Center)
Along Width : 3.650 m. (From Center-to-Center)
Check :
Avarege Luminance by Using ( 10 ) Units : 290.7176 Lux
The Space Height Ratio : Along Length : 0.74
Along Width : 0.811111

Do You Need Chang The No. of Units? (Y/N) Y Please; Enter the No. of units : 10
The No. of Luminaire along Length (NL) : 2 Columns The No. of Luminaire along Width (Nw) : 5 Rows
Average Used No. of Units for this Area will be : 10 Units Luminaire Spacing along Length : 8.325 m. (From Center-to-Center)
Luminaire Spacing along Width : 1.46 m. (From Center-to-Center)
Avarege Luminance by Using ( 10 ) Units : 290.7176 Lux
The Space Height Ratio will be : Along Length : 1.85
Along Width : 0.324444

Copyright@25/12/2006
03/30/2021 11:15:08
By: Eng. Mohammed S. El-Refaey
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54 Room Name : Mosque -Female Prayer- 2nd Floor
Data : Standard Required Illuination (E) : 300 Lux
Length : 15.75 m. Width : 21.5 m Height : 3.65 m. Total Area : 338.625 m².
Falls Ceiling (Y/N) : N 0 Suspention Height : 1 m.
Working Plane Height : 0 m. Net Height : 2.65 m
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.300
Wall Colour : White Wall Reflecting Factor (rw): 0.3 LXW
Room Index (k) = = 3.430417
Floor Colour : White Floor Reflecting Factor (rf): 0.1 Hnet X (L + W)
Lighting Unit Data :
Luminaire Manufacture : AS will be Supplied Refrance : Our Standard Page no.: -- Luminaire Unit Cat. No. Chandelier (Big Size)
Each Unit has : 9 X 100 Watts Type of Light : Incndescent Collour of Light : Normal
Unit Dimensions : Length : 0 Cm Width : 0 Cm
Luminous / Lamp (Φn) : 1200 Lumens Total Luminus / Unit (Φt) : 10800 Lumens
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data At (k1) : 3 Utilization Factor (Uf1): 0.74
At (k2) : 4 Utilization Factor (Uf2): 0.78
Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.757217
K2 - K1
Calculations :
Actual No. of Units for this Area : 16.149 » 16 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X Lroom / Wroom) 3.4236 » 3 Columns
Along Width (Nw) : = Sqrt (N X Wroom / Lroom) 4.6735 » 5 Rows
Avarege Used No. of Units for this Area : 15 Units Luminaire Spacing : Along Length : 5.250 m. (From Center-to-Center)
Along Width : 4.300 m. (From Center-to-Center)
Check :
Avarege Luminance by Using ( 15 ) Units : 278.6588 Lux
The Space Height Ratio : Along Length : 1.981132
Along Width : 1.622642

Do You Need Chang The No. of Units? (Y/N) Y Please; Enter the No. of units : 15
The No. of Luminaire along Length (NL) : 3 Columns The No. of Luminaire along Width (Nw) : 5 Rows
Average Used No. of Units for this Area will be : 15 Units Luminaire Spacing along Length : 5.25 m. (From Center-to-Center)
Luminaire Spacing along Width : 4.3 m. (From Center-to-Center)
Avarege Luminance by Using ( 15 ) Units : 278.6588 Lux
The Space Height Ratio will be : Along Length : 1.981132
Along Width : 1.622642

Copyright@25/12/2006
516572341.xls - Area#3 03/30/2021 - 11:15:08
By: Eng. Mohammed S. El-Refaey
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54 Room Name : A/C Room - 2nd & 3rd Floor
Data : Standard Required Illuination (E) : 150 Lux
Length : 5.37 m. Width : 3.81
m Height : 3.57 m. Total Area : 20.4597 m².
Falls Ceiling (Y/N) : Y Height : 0.65 m.
Working Plane Height : 0 m. Net Height : 2.92 m
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.330
Wall Colour : White Wall Reflecting Factor (rw): 0.3 LXW
Room Index (k) = = 0.763262
Floor Colour : White Floor Reflecting Factor (rf): 0.1 Hnet X (L + W)
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance : Cat. 2002/2003 Page no.: A-37 Luminaire Unit Cat. No. 5735A/2 36XF.61
Each Unit has : 4 X 36 Watts Type of Light : Fluorescent Collour of Light : Warm White
Unit Dimensions : Length : 120 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 2800 Lumens Total Luminus / Unit (Φt) : 11200 Lumens
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data At (k1) : 0.6 Utilization Factor (Uf1): 0.27
At (k2) : 0.8 Utilization Factor (Uf2): 0.36
Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.343468
K2 - K1
Calculations :
Actual No. of Units for this Area : 1.061 » 1 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X Lroom / Wroom) 1.1872 » 1 Columns
Along Width (Nw) : = Sqrt (N X Wroom / Lroom) 0.8423 » 1 Rows
Avarege Used No. of Units for this Area : 1 Units Luminaire Spacing : Along Length : 5.370 m. (From Center-to-Center)
Along Width : 3.810 m. (From Center-to-Center)
Check :
Avarege Luminance by Using ( 1 ) Units : 141.3687 Lux
The Space Height Ratio : Along Length : 1.839041
Along Width : 1.304795

Copyright@25/12/2006
516572341.xls - Area#4 03/30/2021 - 11:15:08
By: Eng. Mohammed S. El-Refaey
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54
Data : Standard Required Illuination (E) : 250 Lux
Length : 10.42 m. Width : 2.81
m Height :
Falls Ceiling (Y/N) : Y Height : 0.65
Working Plane Height : 0 m.
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc):
Wall Colour : White Wall Reflecting Factor (rw):
Floor Colour : White Floor Reflecting Factor (rf):
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance : Cat. 2002/2003 Page no.:
Each Unit has : 4 X 36 Watts Type of Light :
Unit Dimensions : Length : 120 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 2800 Lumens Total Luminus / Unit (Φt) :
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data

Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.305277
K2 - K1
Calculations :
Actual No. of Units for this Area : 2.847 » 3 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X L
Along Width (Nw) : = Sqrt (N X W
Avarege Used No. of Units for this Area : 3 Units Luminaire Spacing

Check :
Avarege Luminance by Using ( 3 ) Units : 263.395 Lux
The Space Height Ratio : Along Length : 1.189498
Along Width : 0.962329

Do You Need Chang The No. of Units? (Y/N) N


alculations

54 Room Name : Lift Lobby - 2nd & 3rd Floor

3.57 m. Total Area : 29.2802 m².


m.
Net Height : 2.92 m

eflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.330


flecting Factor (rw): 0.3 LXW
Room Index (k) = = 0.757934
eflecting Factor (rf): 0.1 Hnet X (L + W)

Page no.: A-37 Luminaire Unit Cat. No. 5735A/2 36XF.61


Fluorescent Collour of Light : Warm White

11200 Lumens

r The Primary Data At (k1) : 0.6 Utilization Factor (Uf1): 0.25


At (k2) : 0.8 Utilization Factor (Uf2): 0.32

= Sqrt (N X Lroom / Wroom) 3.3353 » 3 Columns


= Sqrt (N X Wroom / Lroom) 0.8995 » 1 Rows
Luminaire Spacing : Along Length : 3.473 m. (From Center-to-Center)
Along Width : 2.810 m. (From Center-to-Center)
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54
Data : Standard Required Illuination (E) : 300 Lux
Length : 7.5 m. Width : 4
m Height :
Falls Ceiling (Y/N) : Y Height : 0.45
Working Plane Height : 0.85 m.
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc):
Wall Colour : White Wall Reflecting Factor (rw):
Floor Colour : White Floor Reflecting Factor (rf):
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance : Cat. 2002/2003 Page no.:
Each Unit has : 4 X 18 Watts Type of Light :
Unit Dimensions : Length : 60 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 1080 Lumens Total Luminus / Unit (Φt) :
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data

Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.442986
K2 - K1
Calculations :
Actual No. of Units for this Area : 6.255 » 6 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X L
Along Width (Nw) : = Sqrt (N X W
Avarege Used No. of Units for this Area : 6 Units Luminaire Spacing :

Check :
Avarege Luminance by Using ( 6 ) Units : 287.7744 Lux
The Space Height Ratio : Along Length : 0.943396
Along Width : 0.754717

Do You Need Chang The No. of Units? (Y/N) Y Please; Enter the No. of units :
The No. of Luminaire along Length (NL) : 2 Columns The No. of Luminaire
Average Used No. of Units for this Area will be : 4 Units

Avarege Luminance by Using ( 4 ) Units : 191.8496 Lux


The Space Height Ratio will be : Along Length : 1.415094
Along Width : 0.754717
alculations

54 Room Name : Service Area - 2nd&3rd Floor

3.95 m. Total Area : 30 m².


m.
Net Height : 2.65 m

eflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.330


flecting Factor (rw): 0.3 LXW
Room Index (k) = = 0.984413
eflecting Factor (rf): 0.1 Hnet X (L + W)

Page no.: A-37 Luminaire Unit Cat. No. 5735A/4 18XF.61


Fluorescent Collour of Light : Warm White

4320 Lumens

r The Primary Data At (k1) : 0.6 Utilization Factor (Uf1): 0.27


At (k2) : 0.8 Utilization Factor (Uf2): 0.36

= Sqrt (N X Lroom / Wroom) 3.3541 » 3 Columns


= Sqrt (N X Wroom / Lroom) 1.7889 » 2 Rows
Luminaire Spacing : Along Length : 2.500 m. (From Center-to-Center)
Along Width : 2.000 m. (From Center-to-Center)

lease; Enter the No. of units : 4


The No. of Luminaire along Width (Nw) : 2 Rows
Luminaire Spacing along Length : 3.75 m. (From Center-to-Center)
Luminaire Spacing along Width : 2 m. (From Center-to-Center)
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54
Data : Standard Required Illuination (E) : 150 Lux
Length : 10.6 m. Width : 3.5 m Height :
Falls Ceiling (Y/N) : N 0
Working Plane Height : 0 m.
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc):
Wall Colour : White Wall Reflecting Factor (rw):
Floor Colour : White Floor Reflecting Factor (rf):
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance : Cat. 2002/2003 Page no.:
Each Unit has : 4 X 18 Watts Type of Light :
Unit Dimensions : Length : 60 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 1080 Lumens Total Luminus / Unit (Φt) :
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data

Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.187961
K2 - K1
Calculations :
Actual No. of Units for this Area : 9.115 » 9 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X L
Along Width (Nw) : = Sqrt (N X W
Avarege Used No. of Units for this Area : 10 Units Luminaire Spacing :

Check :
Avarege Luminance by Using ( 10 ) Units : 164.5609 Lux
The Space Height Ratio : Along Length : 0.593838
Along Width : 0.490196

Do You Need Chang The No. of Units? (Y/N) N


alculations

54 Room Name : Stairs Lobby - 2nd&3rd Floor

3.57 m. Total Area : 37.1 m².


Suspention Height : m.
Net Height : 3.57 m

eflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.330


flecting Factor (rw): 0.3 LXW
Room Index (k) = = 0.737032
eflecting Factor (rf): 0.1 Hnet X (L + W)

Page no.: A-06 Luminaire Unit Cat. No. 6035A/4 18XF.61


Fluorescent Collour of Light : Warm White

4320 Lumens

r The Primary Data At (k1) : 0.6 Utilization Factor (Uf1): 0.14


At (k2) : 0.8 Utilization Factor (Uf2): 0.21

= Sqrt (N X Lroom / Wroom) 5.2208 » 5 Columns


= Sqrt (N X Wroom / Lroom) 1.7239 » 2 Rows
Luminaire Spacing : Along Length : 2.120 m. (From Center-to-Center)
Along Width : 1.750 m. (From Center-to-Center)
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54
Data : Standard Required Illuination (E) : 250 Lux
Length : 28.8 m. Width : 20.18 m Height :
Falls Ceiling (Y/N) : N 0
Working Plane Height : 0.8 m.
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc):
Wall Colour : White Wall Reflecting Factor (rw):
Floor Colour : White Floor Reflecting Factor (rf):
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance : Cat. 2002/2003 Page no.:
Each Unit has : 4 X 18 Watts Type of Light :
Unit Dimensions : Length : 60 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 1080 Lumens Total Luminus / Unit (Φt) :
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data

Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.43
K2 - K1
Calculations :
Actual No. of Units for this Area : 104.029 » 104 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X L
Along Width (Nw) : = Sqrt (N X W
Avarege Used No. of Units for this Area : 108 Units Luminaire Spacing

Check :
Avarege Luminance by Using ( 108 ) Units : 259.5438 Lux
The Space Height Ratio : Along Length : 0.866426
Along Width : 0.809467

Do You Need Chang The No. of Units? (Y/N) N


alculations

54 Room Name : Ladies Cafeteria - 2nd Floor

3.57 m. Total Area : 581.184 m².


Suspention Height : m.
Net Height : 2.77 m

eflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.330


flecting Factor (rw): 0.3 LXW
Room Index (k) = = 4.283661
eflecting Factor (rf): 0.1 Hnet X (L + W)

Page no.: A-06 Luminaire Unit Cat. No. 6035A/4 18XF.61


Fluorescent Collour of Light : Warm White

4320 Lumens

r The Primary Data At (k1) : 5 Utilization Factor (Uf1): 0.43


At (k2) : 6 Utilization Factor (Uf2): 0.43

= Sqrt (N X Lroom / Wroom) 12.1829 » 12 Columns


= Sqrt (N X Wroom / Lroom) 8.5365 » 9 Rows
Luminaire Spacing : Along Length : 2.400 m. (From Center-to-Center)
Along Width : 2.242 m. (From Center-to-Center)
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54
Data : Standard Required Illuination (E) : 250 Lux
Length : 29.59 m. Width : 20.53 m Height :
Falls Ceiling (Y/N) : N 0
Working Plane Height : 0.8 m.
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc):
Wall Colour : White Wall Reflecting Factor (rw):
Floor Colour : White Floor Reflecting Factor (rf):
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance : Cat. 2002/2003 Page no.:
Each Unit has : 4 X 18 Watts Type of Light :
Unit Dimensions : Length : 60 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 1080 Lumens Total Luminus / Unit (Φt) :
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data

Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.43
K2 - K1
Calculations :
Actual No. of Units for this Area : 108.736 » 109 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X L
Along Width (Nw) : = Sqrt (N X W
Avarege Used No. of Units for this Area : 117 Units Luminaire Spacing

Check :
Avarege Luminance by Using ( 117 ) Units : 269 Lux
The Space Height Ratio : Along Length : 0.821716
Along Width : 0.823506

Do You Need Chang The No. of Units? (Y/N) Y Please; Enter the No. of units
The No. of Luminaire along Length (NL) : 12 Columns The No. of Luminair
Average Used No. of Units for this Area will be : 108 Units

Avarege Luminance by Using ( 108 ) Units : 248.3078 Lux


The Space Height Ratio will be : Along Length : 0.890193
Along Width : 0.823506
alculations

54 Room Name : Males Cafeteria - 3rd Floor

3.57 m. Total Area : 607.4827 m².


Suspention Height : m.
Net Height : 2.77 m

eflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.330


flecting Factor (rw): 0.3 LXW
Room Index (k) = = 4.375655
eflecting Factor (rf): 0.1 Hnet X (L + W)

Page no.: A-06 Luminaire Unit Cat. No. 6035A/4 18XF.61


Fluorescent Collour of Light : Warm White

4320 Lumens

r The Primary Data At (k1) : 5 Utilization Factor (Uf1): 0.43


At (k2) : 6 Utilization Factor (Uf2): 0.43

= Sqrt (N X Lroom / Wroom) 12.5340 » 13 Columns


= Sqrt (N X Wroom / Lroom) 8.6963 » 9 Rows
Luminaire Spacing : Along Length : 2.276 m. (From Center-to-Center)
Along Width : 2.281 m. (From Center-to-Center)

lease; Enter the No. of units : 108


The No. of Luminaire along Width (Nw) : 9 Rows
Luminaire Spacing along Length : 2.465833 m. (From Center-to-Center)
Luminaire Spacing along Width : 2.281111 m. (From Center-to-Center)
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54
Data : Standard Required Illuination (E) : 200 Lux
Length : 18.22 m. Width : 5.35 m Height : 3.57
Falls Ceiling (Y/N) : N 0
Working Plane Height : 0 m. Net Height :
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc):
Wall Colour : White Wall Reflecting Factor (rw):
Floor Colour : White Floor Reflecting Factor (rf):
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance Cat. 2002/2003 Page no.:
Each Unit has : 4 X 36 Watts Type of Light : Fluorescent
Unit Dimensions : Length : 120 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 2800 Lumens Total Luminus / Unit (Φt) : 11200
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data

Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.271688
K2 - K1
Calculations :
Actual No. of Units for this Area : 8.521 » 9 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X Lroom / W
Along Width (Nw) : = Sqrt (N X Wroom
Avarege Used No. of Units for this Area : 12 Units Luminaire Spacing :

Check :
Avarege Luminance by Using ( 12 ) Units : 281.6545 Lux
The Space Height Ratio : Along Length : 0.850607
Along Width : 0.7493

Do You Need Chang The No. of Units? (Y/N) Y Please; Enter the No. of units :
The No. of Luminaire along Length (NL) : 1 Columns The No. of Luminaire a
Average Used No. of Units for this Area will be : 9 Units Luminaire Spacin
Luminaire Spac
Avarege Luminance by Using ( 9 ) Units : 211.2408 Lux
The Space Height Ratio will be : Along Length : 5.103641
Along Width : 0.166511
Room Name : Left Corridor - 2nd&3rd Floor

m. Total Area : 97.477 m².


Suspention Height : m.
Net Height : 3.57 m

0.8 Maintenance Factor (x) : 1.330


0.3 LXW
Room Index (k) = = 1.158442
0.1 Hint X (L + W)

A-06 Luminaire Unit Cat. No. 6035A/4 36XF.61


Fluorescent Collour of Light : Warm White

Lumens

At (k1) : 1 Utilization Factor (Uf1): 0.24


At (k2) : 1.25 Utilization Factor (Uf2): 0.29

N X Lroom / Wroom) 5.5363 » 6 Columns


(N X Wroom / Lroom) 1.6256 » 2 Rows
Luminaire Spacing : Along Length : 3.037 m. (From Center-to-Center)
Along Width : 2.675 m. (From Center-to-Center)

ter the No. of units : 9


he No. of Luminaire along Width (Nw) : 9 Rows
Luminaire Spacing along Length : 18.22 m. (From Center-to-Center)
Luminaire Spacing along Width : 0.594444 m. (From Center-to-Center)
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54
Data : Standard Required Illuination (E) : 350 Lux
Length : 10.35 m. Width : 7.3 m Height :
Falls Ceiling (Y/N) : N 0
Working Plane Height : 0.85 m.
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc):
Wall Colour : White Wall Reflecting Factor (rw):
Floor Colour : White Floor Reflecting Factor (rf):
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance : Cat. 2002/2003 Page no.:
Each Unit has : 4 X 18 Watts Type of Light :
Unit Dimensions : Length : 60 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 1080 Lumens Total Luminus / Unit (Φt) :
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data

Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.324428
K2 - K1
Calculations :
Actual No. of Units for this Area : 25.095 » 25 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X L
Along Width (Nw) : = Sqrt (N X W
Avarege Used No. of Units for this Area : 24 Units Luminaire Spacing

Check :
Avarege Luminance by Using ( 24 ) Units : 334.733 Lux
The Space Height Ratio : Along Length : 0.634191
Along Width : 0.670956

Do You Need Chang The No. of Units? (Y/N) N


alculations

54 Room Name : Left Open Area - 2nd Floor

3.57 m. Total Area : 75.555 m².


Suspention Height : m.
Net Height : 2.72 m

eflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.330


flecting Factor (rw): 0.3 LXW
Room Index (k) = = 1.5738
eflecting Factor (rf): 0.1 Hnet X (L + W)

Page no.: A-06 Luminaire Unit Cat. No. 6035A/2 18XF.61


Fluorescent Collour of Light : Warm White

4320 Lumens

r The Primary Data At (k1) : 1.5 Utilization Factor (Uf1): 0.32


At (k2) : 2 Utilization Factor (Uf2): 0.35

= Sqrt (N X Lroom / Wroom) 5.9536 » 6 Columns


= Sqrt (N X Wroom / Lroom) 4.1991 » 4 Rows
Luminaire Spacing : Along Length : 1.725 m. (From Center-to-Center)
Along Width : 1.825 m. (From Center-to-Center)
Illumination Calculations

Project Name : Saad Head Office Ext. Bldg. (Portion H) Project No.: 54
Data : Standard Required Illuination (E) : 750 Lux
Length : 25.6 m. Width : 16.6 m Height :
Falls Ceiling (Y/N) : N 0
Working Plane Height : 0.85 m.
Standard :
Reflicing Factors : Ceill Colour : White Ceiling Reflecting Factor (rc):
Wall Colour : White Wall Reflecting Factor (rw):
Floor Colour : White Floor Reflecting Factor (rf):
Lighting Unit Data :
Luminaire Manufacture : ‫شركة إنــارة الســـعودية‬ Refrance : Cat. 2002/2003 Page no.:
Each Unit has : 4 X 36 Watts Type of Light :
Unit Dimensions : Length : 120 Cm Width : 60 Cm
Luminous / Lamp (Φn) : 2800 Lumens Total Luminus / Unit (Φt) :
Tables Data:
Are There Actual Value of (Uf)? (Y/N) N Please Enter The Primary Data

Uf2 - Uf2
So, The Avarege (Uf) = Uf1 + X ( K - K1 ) = 0.414045
K2 - K1
Calculations :
Actual No. of Units for this Area : 91.410 » 91 Units
The No. of Luminaire : Along Length (NL) : = Sqrt (N X L
Along Width (Nw) : = Sqrt (N X W
Avarege Used No. of Units for this Area : 96 Units Luminaire Spacing

Check :
Avarege Luminance by Using ( 96 ) Units : 787.6573 Lux
The Space Height Ratio : Along Length : 0.784314
Along Width : 0.762868

Do You Need Chang The No. of Units? (Y/N) N


alculations

54 Room Name : Printing Area - 3rd Floor

3.57 m. Total Area : 424.96 m².


Suspention Height : m.
Net Height : 2.72 m

eflecting Factor (rc): 0.8 Maintenance Factor (x) : 1.330


flecting Factor (rw): 0.3 LXW
Room Index (k) = = 3.702258
eflecting Factor (rf): 0.1 Hnet X (L + W)

Page no.: A-06 Luminaire Unit Cat. No. 6035A/2 36XF.61


Fluorescent Collour of Light : Warm White

11200 Lumens

r The Primary Data At (k1) : 3 Utilization Factor (Uf1): 0.4


At (k2) : 4 Utilization Factor (Uf2): 0.42

= Sqrt (N X Lroom / Wroom) 11.8464 » 12 Columns


= Sqrt (N X Wroom / Lroom) 7.6817 » 8 Rows
Luminaire Spacing : Along Length : 2.133 m. (From Center-to-Center)
Along Width : 2.075 m. (From Center-to-Center)

You might also like