You are on page 1of 1

Project 1

05 / 30 / 2022

Operator
Telephone
Fax
e-Mail

B3 LV ROOM / Single Sheet Output

Height of Room: 17.000 ft, Mounting Height: 17.000 ft, Light loss factor: 0.80 Values in Lux, Scale 1:106

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 151 129 169 0.855
Floor 20 138 116 153 0.843
Ceiling 80 73 41 693 0.558
Walls (4) 50 153 67 3272 /

Workplane:
Height: 2.493 ft
Grid: 32 x 32 Points
Boundary Zone: 0.000 ft
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.088, Ceiling / Working Plane: 0.481.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) [lm] P [W]


1 11 Pierlite Hydralux 06E 40W (1.000) 3510 39.6
Total: 38614 435.6

Specific connected load: 0.52 W/sq ft = 0.34 W/sq ft/100 lx (Ground area: 838.51 sq ft)