You are on page 1of 10

MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Link Corridor / Room summary

Link Corridor

Clearance height: 3.500 m, Reflection factors: Ceiling 62.1%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average (Target) Min Max Min/average Min/max

1 Workplane (Link Corridor) Perpendicular illuminance (adaptive) [lx] 23.0 (≥ 500) 0.67 373 0.029 0.002
Height: 0.000 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

13 ZALUX - ACQUA PC 258 2706 38.0 71.2

Total via all luminaires 35178 494.0 71.2

Lighting power density: 0.66 W/m² = 2.87 W/m²/100 lx (Floor area of room 745.95 m²)

Consumption: 1350 kWh/a of maximum 26150 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 1
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Link Corridor / Luminaire layout plan

Link Corridor

ZALUX ACQUA PC 258

No. X [m] Y [m] Mounting height [m] Light loss factor


1 39.572 1.195 1.000 0.80
2 25.292 74.084 2.000 0.80
3 16.870 74.011 2.000 0.80
4 8.406 73.956 2.000 0.80
5 4.106 77.777 2.000 0.80
6 39.572 17.512 1.000 0.80
7 39.572 32.436 1.000 0.80
8 39.567 47.328 1.000 0.80
9 39.567 47.328 1.000 0.80
10 39.575 59.249 1.000 0.80
11 39.575 59.249 1.000 0.80
12 39.572 72.998 1.000 0.80
13 33.760 73.894 1.000 0.80

Page 2
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Link Corridor / Workplane (Link Corridor) / Perpendicular illuminance (adaptive)

Workplane (Link Corridor) / Perpendicular illuminance (adaptive)

Workplane (Link Corridor): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 23.0 lx (Target: ≥ 500 lx), Min: 0.67 lx, Max: 373 lx, Min/average: 0.029, Min/max: 0.002
Height: 0.000 m, Wall zone: 0.000 m

Page 3
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Link Corridor / Workplane (Link Corridor) / Perpendicular illuminance (adaptive)

Isolines [lx]

Scale: 1 : 500

Page 4
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Link Corridor / Workplane (Link Corridor) / Perpendicular illuminance (adaptive)

False colors [lx]

Scale: 1 : 500

Page 5
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Link Corridor / Workplane (Link Corridor) / Perpendicular illuminance (adaptive)

Value grid [lx]

Scale: 1 : 500

Page 6
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Plant Room / Room summary

Plant Room

Clearance height: 3.500 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average (Target) Min Max Min/average Min/max

1 Workplane (Plant Room) Perpendicular illuminance (adaptive) [lx] 5.88 (≥ 500) 0.00 316 0.00 0.00
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

9 ZALUX - ACQUA PC 258 2706 38.0 71.2

Total via all luminaires 24354 342.0 71.2

Lighting power density: 0.11 W/m² = 1.82 W/m²/100 lx (Floor area of room 3188.47 m²)

Consumption: 940 kWh/a of maximum 111600 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 7
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Plant Room / Luminaire layout plan

Plant Room

ZALUX ACQUA PC 258

No. X [m] Y [m] Mounting height [m] Light loss factor


1 11.403 9.163 2.100 0.80
2 10.096 19.399 2.100 0.80
3 18.572 23.897 2.100 0.80
4 38.907 19.473 2.100 0.80
5 72.801 24.995 3.500 0.80
6 78.487 24.805 2.100 0.80
7 49.014 5.156 2.100 0.80
8 100.772 20.096 2.100 0.80
9 109.896 15.836 2.100 0.80

Page 8
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Plant Room / Workplane (Plant Room) / Perpendicular illuminance (adaptive)

Workplane (Plant Room) / Perpendicular illuminance (adaptive)

Workplane (Plant Room): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 5.88 lx (Target: ≥ 500 lx), Min: 0.00 lx, Max: 316 lx, Min/average: 0.00, Min/max: 0.00
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 750

False colors [lx]

Scale: 1 : 750

Page 9
MZ 11/4/2020

Site 1 / Building 1 / Storey 1 / Plant Room / Workplane (Plant Room) / Perpendicular illuminance (adaptive)

Value grid [lx]

Scale: 1 : 750

Page 10