PARQUE INDUSTRIAL LA PAZ

ESTACION DE TRANF. - DEPOSITO


Date: 25-11-2010

The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixed relationship
to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminaire positioning, reflection
properties and electrical supply.

CalcuLuX Indoor 4.5b


PARQUE INDUSTRIAL LA PAZ
ESTACION DE TRANF. - DEPOSITO Date: 25-11-2010

Table of Contents

1. Summary 3

1.1 Room Summary 3


1.2 Project Luminaires 3
1.3 Calculation Results 3

2. Calculation Results 4

2.1 Grid: Textual Table 4


2.2 Grid: Iso Contour 5

3. Luminaire Details 6

3.1 Project Luminaires 6

4. Installation Data 7

4.1 Legends 7
4.2 Luminaire Positioning and Orientation 7

CalcuLuX Indoor 4.5b Philips Lighting B.V. Page: 2/7


PARQUE INDUSTRIAL LA PAZ
ESTACION DE TRANF. - DEPOSITO Date: 25-11-2010

1. Summary

1.1 Room Summary

Room Dimensions Surface Reflectance


Width 8.62 m Ceiling 0.70
Length 11.69 m Left Wall 0.50
Height 3.71 m Right Wall 0.50
Working Plane Height 0.80 m Front Wall 0.50
Back Wall 0.50
Floor 0.10
Room Position (Front Bottom Left)
X 0.00 m
Y 0.00 m
Total Average Room Surface Luminance (cd/m2):
Ceiling Left Right Front Back Floor
9.3 19.5 19.5 17.0 17.1 8.6

Unified Glare Rating (CIE): 20


The overall maintenance factor used for this project is 1.00.

1.2 Project Luminaires

Code Qty Luminaire Type Lamp Type Power (W) Flux (lm)
A 9 TBS133/236 M2 2 * TL-D36W 72.0 2 * 3200

The total installed power: 0.65 (kWatt)

Number of Luminaires Per Arrangement:


Luminaire
Arrangement Code Power (kWatt)
A
Room Block 9 0.65

1.3 Calculation Results

(Il)luminance Calculations:
Calculation Type Unit Ave Min/Ave Min/Max Result
Grid Surface Illuminance lux 295 0.61 0.49 Total

CalcuLuX Indoor 4.5b Philips Lighting B.V. Page: 3/7


PARQUE INDUSTRIAL LA PAZ
ESTACION DE TRANF. - DEPOSITO Date: 25-11-2010

2. Calculation Results

2.1 Grid: Textual Table

Grid : Grid at Z = 0.80 m


Calculation : Surface Illuminance (lux)
Result Type : Total

X (m) 0.36 1.08 1.80 2.51 3.23 3.95 4.67 5.39 6.11 6.82 7.54 8.26
Y (m)
11.20 181 224 246 248 254 267 267 254 248 246 224 181
10.23 207 263 287 284 291 310 310 291 284 287 263 207
9.25 228 286 313 311 318 339 339 318 311 313 286 228
8.28 247 308 339 341 350 369 369 350 341 339 308 247
7.31 250 310 341 344 353 371> 371> 353 344 341 310 250
6.33 237 297 324 322 330 351 351 330 322 324 297 237
5.36 237 297 324 322 330 351 351 330 322 324 297 237
4.38 250 310 341 344 353 371 371 353 344 341 310 250
3.41 247 308 338 341 350 369 369 350 341 338 308 247
2.44 227 286 313 310 318 339 339 318 310 313 286 227
1.46 207 262 287 284 291 310 310 291 284 287 262 207
0.49 181 223 245 247 253 266 266 253 247 245 223 181<

Average Min/Ave Min/Max Project maintenance factor


295 0.61 0.49 1.00

CalcuLuX Indoor 4.5b Philips Lighting B.V. Page: 4/7


PARQUE INDUSTRIAL LA PAZ
ESTACION DE TRANF. - DEPOSITO Date: 25-11-2010

2.2 Grid: Iso Contour

Grid : Grid at Z = 0.80 m


Calculation : Surface Illuminance (lux)
Result Type : Total
11.5

250
200
10.5

200
A 300 A A
9.5
8.5

250
7.5

300
6.5

350

350
Y(m)

A A A
5.5

250
4.5
3.5
2.5

30
0

A A A
1.5

0
200

30
200

250
0.5
-0.5

-2.5 -1.5 -0.5 0.5 1.5 2.5 3.5 4.5 5.5 6.5 7.5 8.5 9.5 10.5
X(m)

A TBS133/236 M2

Average Min/Ave Min/Max Project maintenance factor Scale


295 0.61 0.49 1.00 1:75

CalcuLuX Indoor 4.5b Philips Lighting B.V. Page: 5/7


PARQUE INDUSTRIAL LA PAZ
ESTACION DE TRANF. - DEPOSITO Date: 25-11-2010

3. Luminaire Details

3.1 Project Luminaires

TBS133/236 M2 2 x TL-D36W / 830 Luminous Intensity Diagram (candela/1000 lumen)


120o 150o 180o 150o 120o
Light output ratios
DLOR : 0.60
ULOR : 0.00
TLOR : 0.60
Ballast : Electronic 90o 90o
Lamp flux : 3200 lm
Luminaire wattage : 72.0 W
Measurement code : LVN7043200
60o 60o

200

30o 0o 30o
C = 180o Imax C = 0o
C = 270o C = 90o

CalcuLuX Indoor 4.5b Philips Lighting B.V. Page: 6/7


PARQUE INDUSTRIAL LA PAZ
ESTACION DE TRANF. - DEPOSITO Date: 25-11-2010

4. Installation Data

4.1 Legends

Project Luminaires:
Code Qty Luminaire Type Lamp Type Flux (lm)
A 9 TBS133/236 M2 2 * TL-D36W 2 * 3200

4.2 Luminaire Positioning and Orientation

Qty and Position Aiming Angles


Code
X (m) Y (m) Z (m) Rot. Tilt90 Tilt0
1*A 1.44 1.95 3.71 0.00 0.00 0.00
1*A 1.44 5.85 3.71 0.00 0.00 0.00
1*A 1.44 9.75 3.71 0.00 0.00 0.00
1*A 4.31 1.95 3.71 0.00 0.00 0.00
1*A 4.31 5.85 3.71 0.00 0.00 0.00

1*A 4.31 9.75 3.71 0.00 0.00 0.00


1*A 7.18 1.95 3.71 0.00 0.00 0.00
1*A 7.18 5.85 3.71 0.00 0.00 0.00
1*A 7.18 9.75 3.71 0.00 0.00 0.00

CalcuLuX Indoor 4.5b Philips Lighting B.V. Page: 7/7