AUDITORIUM- PASILLO
Date: 25-11-2010
The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixed relationship
to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminaire positioning, reflection
properties and electrical supply.
Table of Contents
1. Summary 3
2. Calculation Results 4
3. Luminaire Details 6
4. Installation Data 7
4.1 Legends 7
4.2 Luminaire Positioning and Orientation 7
1. Summary
Code Qty Luminaire Type Lamp Type Power (W) Flux (lm)
A 4 TBS133/236 M2 2 * TL-D36W 72.0 2 * 3200
(Il)luminance Calculations:
Calculation Type Unit Ave Min/Ave Min/Max Result
Grid Surface Illuminance lux 225 0.74 0.63 Total
2. Calculation Results
X (m) 0.63 1.90 3.16 4.43 5.70 6.97 8.23 9.50 10.77 12.04 13.30 14.57
Y (m)
1.53 165 224 214 220 246 223 223 246 220 214 224 165<
1.40 170 230 219 225 252 228 228 252 225 219 230 170
1.26 173 234 223 229 257 232 232 257 229 223 234 173
1.13 176 237 226 232 260 235 235 260 232 226 237 176
1.00 177 239 228 233 262 236 236 262 233 228 239 177
0.87 178 239 228 234 262 236 236 262 234 228 239 178
0.73 178 239 228 234 262 236 236 262> 234 228 239 178
0.60 177 239 228 233 262 236 236 262 233 228 239 177
0.47 176 237 226 232 260 235 235 260 232 226 237 176
0.34 173 234 223 229 257 232 232 257 229 223 234 173
0.20 170 230 219 225 252 228 228 252 225 219 230 170
0.07 165 224 214 220 246 223 223 246 220 214 224 165<
220
200
180
260
260
1
Y(m)
240
240
A A A A
180
200
220
0
-1
-2
-3
-4
-5
-6
-7
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
X(m)
A TBS133/236 M2
3. Luminaire Details
200
30o 0o 30o
C = 180o Imax C = 0o
C = 270o C = 90o
4. Installation Data
4.1 Legends
Project Luminaires:
Code Qty Luminaire Type Lamp Type Flux (lm)
A 4 TBS133/236 M2 2 * TL-D36W 2 * 3200