Features
* Analysis of TCG ( Total Combustible Gas ) and 6 kinds of Gases
* High Sensitivity for C2H2 that is Key Gas in Transformer Abnormality
* Quick Measurement ( 15 minutes )
* Small amount of oil sample (50 cc)
* Compact and Light (12 kg)
* Equipped with Communication Interface
SDK-M8789(1/2)
Configuration
Configuration
Column 4Sensors
Sample loop
Stirring magnet
Sample vessel
Heater AP Flow controller Filter AP
Sample oil CPU board LCD touch panel
Magnetic stirrer
Specifications
Specifications
ITEMS CONTENTS
C 2H2 (Acetylene) 0.5-500
C 2H4 (Ethylene) 10-2,000
CO (Carbon Monoxide)
Performance Objective Gas and H2 (Hydrogen)
20∼2,000
Measurement Range (ppm) CH4 (Methane)
C 2 H6 (Ethane)
TCG 50∼10,000
Measurement Accuracy(%) ±20
Measurement Time (min) 15
Oi
l Volume of measurement(ml) 50
Extraction Method Oil Stirring Up and Circulating Air above Oil
Carrier Gas Air
Operation Pannel LCD touch panel
General Dimmension (mm) W450×D200×H355
Specifications and Mass 12kg
100-120 or 200-240V AC(50/60Hz)
Power Supply
200VA max. Single-phase
W orking Enviroment (degree C) 0- 45
One RS232C port for printer
Communication I/F
One USB port for pesonal computer
SDK-M8789(2/2)
Portable DGA (Dissolved Gas Analyzer)
Model PGA-300
TECHNICAL SHEET
SDK – M8708-C
-1-
PGA-300 Technical Sheet
SDK – M8708-C
-2-
PGA-300 Technical Sheet
2. Specifications
Table 2.1 shows the specifications of the PGA-300.
Gas extraction method Equilibrium extraction with oil stirring and circulating air above oil
section
SDK – M8708-C
-3-
PGA-300 Technical Sheet
3. Configuration
Fig 3.1 shows the piping diagram of Portable DGA. And Fig 3.2 shows the
appearance of this apparatus.
Column 4Sensors
Sample loop
Stirring magnet
Sample vessel
Heater AP Flow controller Filter AP
Sample oil CPU board LCD touch panel
Magnetic stirrer
SDK – M8708-C
-4-
PGA-300 Technical Sheet
SDK – M8708-C
-5-