Professional Documents
Culture Documents
A S H R A E C t l 27-ENGL L977 H 0 7 5 7 b 5 0 0 5 3 L b 7 2 T 3 2 I
CHAPTER 27
27.1
COPYRIGHT American Society of Heating, Refrigerating and Air-Conditioning
Licensed by Information Handling Services
27.2 1997 ASHRAE Fundamentals Handbook
load establishes the size of the fan-coil and air distribution system In application, the area of each window is multiplied by the
for each apartment. One of the methods discussed in Chapter 28 appropriate GLF. The effectsof permanent outside shading devices
may be used to calculate the block load. should be considered separately in determining the cooling load.
Shaded glass is considered the same as north-facing glass. The
Indoor TemperatureSwing shade line factor (SLF) is the ratio of the distance a shadow falls
beneath the edge an of overhang to the width of the overhang (Table
For hour-by-hourloadcalculations,allowingforaswingin 6). Therefore, assuming the overhang is at the top of the window,
indoor temperature results in lower peak loads. Because the indoor the shade line equals the SLF times the overhang width. The shaded
temperature does swing, such an allowance gives a more reasonable and sunlit glass areas may then be computed separately. The tabu-
equipmentcapacity.Thetables in thissectionarebased on an lated values are the average of the shade line values for 5 h of max-
assumed indoor temperature swingof no more than3°F on a design imum solar intensity on each wall orientation shown. Northeast-
day, when the residence is conditioned h24 per day and the thermo- and northwest-facing windows are not effectively protected by roof
stat is set at 75°F. overhangs; in most cases, they shouldnot be considered shaded.
Cooling Load Due to Heat Gain Through Structure Infiltration
The sensible cooling load due to heat gains through the walls, Natural air leakage in residential structures is less in summer
floor, andceilingofeachroomiscalculatedusingappropriate than in winter, largely because wind velocities are lower in most
cooling load temperature differences (CLTDs) (Tables 1 and 2) localities. The data in Tablesand7 8 showing space air changesper
and U-factors for summer conditions. For ceilings under naturally
vented attics or beneath vented flat roofs, the combined U-factor Table 2 CLTD Values for Multifamily Residencesa
for the roof, vented space, and ceiling should be used. The mass of
the walls is a variable in Table 2 and is important in calculating Desim Temperature, F '
energy use, but it is not used in Table 1 because of the averaging Daily Temperature 85 90 --- 95 100 10.5 -
110
technique required to develop the CLTDs. Values in Tables 1 and 2 Rangeb L M L M H L M H M HH
assume a dark color because color is an unpredictable variable in Wulls und doorsc
any residence. 14 11 1916122421172622 32
27
Light
Daily range (outdoor temperature swing on a design day) signif- N Medium 13 10 1815 I I 2320162521 26 31
icantly affects the equivalent temperature difference. Tables 1 and 2 Heavy 9 6 15 I I 7 20 16 12 27
22
17
21
list daily temperature ranges classified as high, medium, and low.
Lieht
23
17
2822
17 33 2722 32 26 31 36
Tables 1,2, and 3 in Chapter 26 list outdoor daily ranges of dry-bulb
NE
Medium20 15 16
20
25 30 34
29
25
21
25
temperature for different locations. Heavy
1612
21
17 13 26 22
18 262226 31
Cooling Load Due to Heat Gain Through Windows Light
32
2737 32 27 43
38
32
42 37 42 47
E Medium 30 24 34 24
29 40 29
34 39 33 44
39
Direct application of procedures for calculating cooling load due Heavy23
182823
18
34
29
23 33 28 33 38
to heat gain for flat glass (discussed in Chapters 28 and 29) results Light 31 27 35 31 26
41
37
31 42 37 42 47
in unrealistically high cooling loads for residential installations. SE Medium22
28 32 37
22
27 32 38
33
37
27 43
Window glass load factors(GLFs), modified for single- and mul- Heavy2116 26 22
17 32 27
22 31 27 32 37
tifamily residential cooling load calculations and including solar
Light
252229
2622 35 31 26
36 32 37 43
heat load plus air-to-air conduction, are given in Tables 3 and 4.
S Medium
18
22 26 18
22 31 22
26 31 27 32 38
Table 5 lists the shading coefficients (SCs) and U-factors used to Heavv
16 II 20 16
12 26 21 17 26 21
27
33
compile Tables 3 and 4.
Light
39364440 35 50 46 40 51 47 52 58
Table 1 CLTD Values for Single-Family Detached Residencesa sw Medium33
29
37
34
29
44
40
35
45
40 46
52
Heavy
231828
24 19 36 31 25 35 30 36 42
Design Temperature, T Light
44414845
40 54 51 46 56 52 57 63
Daily Temperature 85 -90 - 95 - 100 -
105 -
110 Medium
W 37 33 38
41 33
46 48
38
42 43
49 55
Rangeb L M L M H L M H MM H
H Heavy
2622 31 27
23
37
32
27 31 32
38 44
All wulls und doors Light 33 30 37
34 30 43 39 34 44 40 45 50
North 8 3 13 8 3 18 13 8 18 13 18 23 NW Medium28
25 32 29 24 37 33 2939 35 40 45
NE and NW 14 9 1914 9 241914 2419 24
29 Heavy
2016
25
20
16 31 26
21 31 2632 37
East and West 18 13 2318 13 28 23 18 2823 28
33 Roof und ceiling
SE and SW 16 I I 21
16 I I 26 21 16 2621 26 31 Attic or Light
58 53 65 60 55 70 65 60 70
65 72 77
South 11 6 16 I I 6 21 16 I I 21 16 26
21 flat built-up
Roo$? und ceilings Flatbuilt-upMedium2118 23 2118252321 252325 28
Atticor flat built-up423747 42 37 51 4742 51 47 51 56 or heavy
Floors und ceilings Floors und ceiling
Under
conditioned 949124 12
14 9 19
14
12
14 Under
over
or 144 9124 9 12 9 19
14
12
14
space, over uncondi- unconditioned space,
tioned room, over crawl space
crawl space Purtitions
Purtitions Inside or shaded
49 12 49 12
14 9 19
14
12
14
Inside19
14
12
14
912
144shaded
or 9124 9 'Cooling load temperature differences (CLTDs) for multifamily low-rise or single-
"Cooling load temperature differences (CLTDs) for single-family detached houses, family detachedif zoned with separate temperature control for each zone,"F.
duplexes, or multifamily, with both east and west exposed walls or only north and hL denotes low daily range, lessthan 16°F: M denotes medium daily range,16 to 25°F;
south exposed walls, "F. and H denotes high daily range, greaterthan 25°F.
hLdenotes low daily range, lessthan 16°F; M denotes medium daily range,16 to 25°F; 'Light denoteslightweight;mediumdenotesmedium-weight; andheavy denotes
and H denotes high daily range, greaterthan 25°F. heavyweight construction.
Cooling
Residential and Heating Load Calculations 27.3
Table 3 Window Glass Load Factors (GLFs) for Single-Family Detached Residencesa
Regular Regular Heat-Absorbing
Triple Clear
Design Single Glass Double Glass Double Glass Glass
Temaerature. T' 85 90 95 110
105
100 85 90 95 110
105
100 85 90 95 110
105
100 85 90 95
N o inside shuding
North 34 36 41 47 48 50 30 30 34 37 38 41 20 20 23 25 26 28 27 27 30
NE and N W 63 65 70 75 77 83 55 56 59 62 63 66 36 37 39 42 44 44 50 53
50
East and West 88 90 95 100 102 107 77 78 81 84 85 88 51 51 54 56 59 59 70 70 73
SE and SWh 79 81 86 91 92 98 69 70 73 76 77 80 45 46 49 51 54 54 62 63 65
Southh 53 55 60 65 67 72 46 47 50 53 54 57 31 31 34 36 39 39 42 42 45
Horizontalskylight 156 156 161 166 167 171 137 138 140 143 144 147 90 91 93 95 96 98 124 125 127
Druperies, venetiun blinds,trunslucent roller shades, fully druwn
North 18 19 23 27 29 33 16 16 19 22 23 26 13 14 16 18 19 21 15 16 18
NE and NW 32 33 38 42 43 47 29 30 32 35 36 39 24 24 27 29 29 32 28 28 30
East and West 45 46 50 54 55 59 40 41 44 46 47 50 33 33 36 38 38 41 39 39 41
SE and SWh 40 41 46 49 51 55 36 37 39 42 43 46 29 30 32 34 35 37 35 36 38
Southh 27 28 33 37 38 42 24 25 28 31 31 34 20 21 23 25 26 28 23 24 26
Horizontal skylight 78 79 83 86 87 90 71 71 74 76 77 79 58 59 61 63 63 65 69 69 71
Opuyue roller shades, jully druwn
North 14 15 20 23 25 29 13 14 17 19 20 23 12 12 15 17 17 20 13 13 15
NE and NW 25 26 31 34 36 40 23 24 27 30 30 33 21 22 24 26 27 29 23 23 26
East and West 34 36 40 44 45 49 32 33 36 38 39 42 29 30 32 34 35 37 32 32 35
SE and SWh 31 32 36 40 42 46 29 30 33 35 36 39 26 27 29 31 32 34 29 29 31
Southh 21 22 27 30 32 36 20 20 23 26 27 30 18 19 21 23 24 26 19 20 22
Horizontal skylight 60 61 64 68 69 72 57 57 60 62 63 65 52 52 55 57 57 59 56 57 59
"Glass loadfactors(GLFs)forsingle-familydetachedhouses,duplexes, or multifam- To obtainGLFforothercombinations of glass and/orinsideshading: GLF, =
ilyresidences, with botheast and westexposedwalls or only north and south (SCJSC,)(GLF,- Up,)+ U,,D,, where the subscriptsU and I refer to the alternate
exposed walls, Btu/h.ft2. and table values, respectively. SC, and U , are given in Table 5 . D, = (I,, - 751,
hCorrect by +30% for latitude of 48" and by -30% for latitude of 32". Use linear where I(, = r, - (DWZ); r,, is the outdoor design temperature and DR is the daily
interpolation
latitude
for
from 40 to 48from
and range.
32".to
40
because most residences have exhaust fans and clothes dryers that Outdoor design condirions. Temperature of 96°F dry bulb with a
ventmost of themoisturefromthesesources.This vent air is 24°F daily range and a humidity ratio of 0.0136 lb vaporflb dry air
accounted for in the infiltration calculation. McQuiston(1984) esti- (74.6"F wet bulb).
mated latent load factors for typical houses located in geographic U-fucror.s for all external surfaces are based on a 7.5mphwind
velocity.
regions ranging fromvery dry tovery wet using the transfer function Indoor design conditions. Temperature of 75°F dry bulb and 50% rh.
method (Figure 1). A latent factorLF (LF= l/SHF) of 1.3 or asen- Occupuncy. Four persons, based on two for the master bedroom
sible heat factor SHF (SHF = sensible loadtotal load) of 0.77 and one for each additional bedroom. Assignto the living room.
matches the performance of typical residential vapor compression Appliances und lights. Assume1600Btulh forthekitchen,and
cooling systems. Homes in almost all other regions of North America assign 50% to the living room. Assume 1600 B t u h for the utility room,
have cooling loads with an SHF greater than 0.77 and latent factors and assign 25% to the kitchen and25% to the storage room.
less than 1.3. Figure 1 may be used to estimate the total cooling load The conditioning equipment is located in the garage, and the con-
by readingLF as a functionof the design humidity ratio and airtight- struction of the houseis considered medium.
ness. ThenqtOtal = (LF)qsensihle.
If the humidity ratio is less 0.01,
than Find the sensible, latent, and total cooling load; size the cooling
unit; and compute theair quantityfor each room.
set LF = 1.O.
Solution: The cooling load must be made on a room-by-room basis to
determine the proper distribution of air. The calculations follow the
LOAD CALCULATION procedure outlined in the section on Load Components.
Thecoolingloadcalculationproceduresaresummarizedin
Table 9.
Plan 230Btuh per person. Divide occupants evenly among rooms not used as bedrooms. If number of
occupants is not known, assume two people for first bedroom and one person
for each additional bedroom.
The appliance and light load of 1600Btdh is divided between the kitchen and
adjoining room and the laundry and adjoining room. Use 1200 Btu/hfor multi-
family units.
Total loads Total cooling load= LF x Load factors are from FigureI according to outdoor design humidity ratio and
(Sum of individual sensible airtightness classification.
cooling load components)
y =sensible
load,
cooling Bhdh cfm Q rate.
= volumetric
airflow
Ar =design temperature. difference between outsideand inside ACH = air changes per hour, I / h
air, "F = glass load factor,
GLFBtu/h.fr2
A =area of applicable
surface,
ft2 CLTD = cooling load temperature
difference, "F
U =U-factors
appropriate
for construction,
Btu/h.ft2. "F LF = multiplier
latent
load
Wulls, rot$ windr~ws.und doors. Thecalculationsfortheliving design of the air distribution system, heat losses from the supply and
room and the kitchen, where q = UA(CLTD) for the walls, roof, and return ducts may add to the cooling load. These may be more accu-
door and q = A(GLF) for the windows, are outlined in Table 10. The rately estimated after designing the system; however, to size the cool-
glass shaded by the overhang is treated as north-facing glass, with the ing unit, duct losses should be included initially. If all ducts are in the
shaded area computed using Table6. attic space, a duct loss of 10% of the space sensible cooling load is rea-
loud.^. Compute as follows.
Internul und injjltrution sensible cooling sonable. For a counterflow system, with ducts below the slab, a 5%
For the living room: loss is more reasonable.
Infiltration. Using Table 8, An infiltration rate of0.5 ACH may not be adequate for good indoor
Q = ACH (room volume)/60 air quality, so some outdoor air should be introduced. This additional
Q = 0.5 X 3840/60 = 32 cooling load maybe estimated in the same wayas the infiltration load.
= I.lQ(t,-ti) = 1,IQAI Assume that the entire duct system is in the attic; that is, the total
q = l.IX32(96-75)=740Btu/h sensible cooling load with a 10% duct loss is 1. I x 19,679 = 21,647
Occupants. Assuming 230 Btu/hper person, Btdh. Also, assume that additional outdoorair is needed to assure good
q = 230 x (persons) indoor air quality, so the total infiltration and outdoor ventilation air is
q = 230 X 4 = 920 Btdh 0.75 ACH. This increases the infiltration rate by 50%, or about 1600
Appliances. Assuming that 50% of the kitchen appliance load is Btu/h. The total sensible cooling load is then increased to 23,247 Btu/h
picked up in the living room, (Table I I).
q = 0.5 x (kitchen appliance load) The total cooling load (sensible plus latent) may be estimated by
q = 0.5x 1600 = 800 Btulh applying the latent factor (LF) from Figure I. For a design humidity
For the kitchen: ratio of 0.0136 Ib vapor per Ib dry air, =LF1.15 for a house of medium
Infiltration. construction.Hence,thetotalcoolingloadequals 1.15 x 23,247 =
Q = 0.5 X 1920/60 = 16 26,734 Btuih.
= 1.1 X 16(96-75) = 370Btuih The load raises the temperature of the cooling air 18 to 21°F as it
No occupants. leaves the rooms. The total design flow from the air conditioner can be
q=o estimated by the following equation:
Appliances.Assumingthat25%oftheutilityapplianceloadis
Q =- Y
picked up in the kitchen, I. I At
y = (1600/2) + (1600/4) = 1200 Btu/h where
For the total sensible cooling load for these two rooms and the Q,,,t = total airflow, cfm
cooling load for the remaining rooms, see Table 11. At this point, the y = total sensible load, Btuih
sensible cooling load for the house is 19,679 Btulh. Depending on the I . 1 = density times specific heat of cooling air times m
60i d
At = temperature difference of air entering arid leaving room,"F
Table 10 Transmission Cooling Load for Example 1 For a temperature difference of 18°F. the total airflow is estimated
Net Cooling from Equation(1) as
Area,
GLF,
U-Factor, CLTD,
Load,
Item ft2 Btulh*ft2
Btu/h*ft2*"F "F Reference
Btu/h
Living Room
The exact design flow can be determined only after the cooling unit
06 91 wall West 1 has been selected. Then, the supply air quantities can be computed. Air
Partition should be supplied to each room on the basis of the room sensible cool-
2 0.07 192 (garage) 1 ing load:
Roof 480 Table 0.05
1152 48 1
32 21 door West 1 Q m = QrJqrrn'q)
West glass 35 44 Table 1540 3 where
ShadedTable
elass 247
13 19 3 Q, = airflow to each room, cfm
Kitchen y,., = room sensible cooling load, Btu/h
East wall 135 0.06 194 24 Table 1 Thus, for the example,
Roof 240 0.05 576 48 Table 1
Q,, = (994/19,679jyr,
East glass 14 44 616 Table 3
Shaded glass I I 19 209 Table 3 If the living spacein Example 1 were a multifamily unit (assume
that the north, south, and east walls are not exposed surfaces), the
Table 11 Summary of Sensible Cooling Load Estimate calculation procedure would be the same, except that 2Table would
for Example 1 have been used for the CLTDs and Table 4 for the GLFs. Assump-
tions regarding infiltration, ventilation, and appliance loads are dif-
Total Room
Roof, Walls, Appli- Infil- Btuh cfm ferent for smaller multifamily units.
Room and
Doors Glass People
ances
tration (qm) (Q,,,,)
5,852
296
740
800
Living
1,605
room
1,787
920 HEATING LOAD
825 770Kitchen 3,165 370
1,200 160
1,2001,404 and Utility 154 Calculating a residential heating load involves estimating the
storage maximum (block) heat loss of each room or space to be heated and
Bedroom No.1 559 544 1,381
70
278 the simultaneous maximum (block) heat loss for the building, while
Bedroom No.2 686 848 1,812
91
278 maintaining a selected indoor air temperature during periods of
Master bedroom 1,682 8 16 813 3,311
167 design outdoor weather conditions. Heat losses are mainly
and bath
Transmission losses or heat transferred through the confining
Bath 540 276 295 1,111 56
walls, glass, ceiling,floor, or other surfaces
Total 7.246 5,096 920
3.200
3.217
19.679
994 Infiltration losses or energy required to warm outdoor air leaking
Duct loss (10%) 1,968 inthroughcracksandcrevicesarounddoorsandwindows,
Outdoor ventilation air 1,600 through open doors and windows, and through porous building
Total23.247 Btuh materials
Theoretically, on a design basis, the most unfavorable combina- and the corresponding overall heat transfer coefficients are 0.10 and
tion of temperature and wind speed should be chosen. A building 0.30 Btun.ft2."F. Thesixthsurfaceisonthegroundandcanbe
may require more heat on a windy day with a moderately low out- neglected for this example, as can the effect of introduction of outdoor
door temperature than on a quiet day with a much lower outdoor air into the unheated space. Assume f i = 70°F and I , = -10°F.
temperature. The worst combination of wind and temperature varies Solution: Substituting into Equation (2),
by building because wind speed has a greater effect on buildings
with relativelyhigh infiltration rates. The building heating load may tu = [70( 100 X 0.15 + 120 X 0.20 + 140 X 0.25)
be calculated for several combinations of temperature and wind + (-10)(100 x 0.10 + 140 x 0.30)]
speed on record, and the worst combination may be selected; how- i (100 x 0.15 + 120 x 0.20 + 140 x 0.25
ever, except for critical applications, designers generally find such
a degree of refinement unnecessary. No correlation has been shown
+ 1 0 0 x O. 10 + 140 x 0.30)
between the design temperatures in Chapter 26 and the simulta- I, = 4660/126 = 37'F
neous maximum wind speed. If a designer prefers the air change
methodforcomputinginfiltrationrates,suchcorrelationis not Temperatures in unheated spaces with large glass areas and two
important. Designers who use the crack method can use a leakage or more surfaces exposed to the outdoors (e.g., sleeping porches and
rate at a wind speed of 15 mph, unless local experience has estab- sun parlors)are generally assumedto be the same as that of the out-
lished that another speed is more appropriate. Abnormally high doors.
wind speeds may have an effect on infiltration and the U-factor of
the building components (see Chapter 22). Attic Temperature
An attic is a space having an average distance of 1 ft or more
Indoor Design Temperature between a ceiling and the underside of the roof. Estimating attic
The indoor temperature for comfort heating may vary depending temperature is a special case of estimating temperature in an adja-
on building use, typeof occupancy, or code requirements. Chapter cent unheated space and can be done using
8 andASHRAE Standards 55 and55adefinetherelationship
between temperature and comfort. A,Uctc+t,(60pc,,AcVc+ArUr+AwUw+AgUg)
ta =
Ac(Uc+60pc,,Vc)+ArU,+AwU,+AgU~ (3)
ESTIMATING TEMPERATURES IN
ADJACENT UNHEATED SPACES where
Heat loss from heated rooms to unheated rooms or spaces must PC,,= air density times specific heat= 0.018 Btu/ft3.'T for standard air
bebasedontheestimated or assumedtemperatureinsuch attic temperature, OF
I,, =
unheated spaces. This temperature will be in between the indoor C, indoor temperature near topfloor ceiling, "F
=
and outdoor temperatures.If the surface area adjacent to the heated I, =outdoor temperature, "F
room and that exposed to the outdoors are equal and if the heat A, = area of ceiling, ft2
transfercoefficientsareequal,thetemperature in theunheated A,. = area of roof, ft2
space may be assumed equal tothe mean of the indoor and outdoor A, = area of net vertical attic wall surface, ft2
design temperatures. If, however, the surface areas and coefficients A, = area of attic glass, ft2
are unequal, the temperature in the unheated space should be esti- U, = heat transfer coefficient of ceiling, Bhdh.ft2. "F,based on surface
mated by conductance of 2.2 Btu/h.ft2.0F (upper surface, see Table 2 in
Chapter 24); 2.2= reciprocal of one-half theair space resistance
U, = heat transfer coefficient of roof,
Btu/h'ft2'"F,based on surface con-
r,, = [ti(AIU, +A2U,+A,U, +etc.) ductance of2.2 Btu/h.ft2.OF (upper surface,see Table 2 in Chapter
+rl,(60pc,Q,+A,U,+A,~,+AcUc+etc.)] 24); 2.2 = reciprocal of one-halfthe air space resistance
U, = heat transfer coefficient of vertical wall surface,Btulh.ft2. "F
+(Alul +A2U2+A,U3+etc. Ug = heat transfer coefficient of glass,Btu/h.ft2."F
V, = rate of introduction of outside air into the attic space by ventila-
+60pc,,Ql,+AuU,+AbU,+A,Uc+etc.) tion per square foot of ceilingarea, cfm/ft2
reduction in temperature difference affects the overall heat loss of r, = ground temperature (constant), "F
a residence with an insulated ceilingby only 1 or 2%. r, = crawl space temperature, T
Equation (3) does not consider factors such as heat exchange Ar = area of floor above, fi2
between chimney and attic or solar radiation to and from the roof. A,, = area of perimeter, exposed foundation wall plus sill box, ft2
A, = area of ground below(Ar = As), ft2
Because of these effects, attic temperatures are frequently higher
U != avenge heat transfer coefficient throughfloor, Btu/h.ft2' T
than valuescalculated using Equation (3). However,Equation (3) can Ob' = average heat transfer coefficient through ground (horizontal air
be used to calculate attic temperature because the resulting erroris film and I O ft of soil), Btuh'ft2.T
generally less than that introduced by neglecting roofthe
and assum- U,, = combined heat transfer coefficient of sill box and foundation wall
ing that the attic temperature is equal to the outdoor air temperature. (both above andbelow grade), Btu/h.ft2' T
When relatively large louvers are installed (customary in southern V, = volume of crawl space, ft3
regions of the United States), the attic temperatureis often assumed pc = volumetric heat capacity of air= 0.018 Btu/ft3. T
to be the averageof the indoor and outdoor air temperatures. 0.6$= assumed air exchange rate, volumeshour
For an approximate method of calculating heat losses through
Example 4. A crawl space of 1200 ft2 with a 140 ft perimeter is consid-
attics, the combined ceiling and roof coefficient may be used (see
ered. The construction of the perimeter wall is shown in Figure3. The
Table 5 in Chapter 24). indoor, outdoor, and the deep-down ground temperatures are 70, 10,
and 50°F. respectively. Estimate the heat loss and crawl space tempera-
CALCULATING HEAT LOSS turewithandwithoutinsulation. Theheattransmissioncoefficient
FROM CRAWL SPACES (U-factor) for each component is indicated in Table 13.
A crawl space can be considered a half basement. To prevent Table 13 Estimated U-Factors for Insulated and
groundmoisturefromevaporatingandcausingacondensation
Uninsulated Crawl Spaces
problem, sheets of vapor retarder (e.g., polyethylene film) are used
to cover the ground surface (see Chapter 23). Most codes require Uninsulated InsulatedP
crawl spacesto be adequately vented all year round. However, vent- Btuh-DFperft Btu/h."Fperft
ing the crawl space in the heating season causes substantial heat loss Comoonent of Perimeter of Perimeter
through the floor. 16 in. exposed concrete blocks 0.7 0.18
The space may be insulated in several ways: the crawl space ceil- 7.5in. sill box O.I88 0.07 I
ing (floor above the crawl space) can be insulated, or the perimeter
wall can be insulated either on the outside or on the inside. If the Ist 12 in. blockwall 0.127
below grade 0.355
floor above is insulated, the crawl space vents should be kept open 2nd 12 in. block wall below grade 0.22 0.14
because the temperatureof the crawl space is likely to be below the 3rd 12 in. block wall below grade O. I33 0.1
dew point of the indoor space.If the perimeter wall is insulated, the Total for perimeter wall 1.6 0.62
vents should be kept closed in the heating season and open the
remainder of the year. Btu/h*ft2. "F Btu/h*ft2*"F
0.077 0.077 Ground
Crawl Space Temperature space crawl
Floor above 0.25 0.076'
The crawl.space temperature depends on such factors as venting, JPerimeter walls are insulated with R-5.4; the floor is insulated with R-I 1 blanket or
heating ducts, and the heating plant. When the crawl space is well batts.
ventilated, its temperature is close to thatof the ambient air temper-
ature. When the crawl space vent is closed for the heating season, or
if the space is used as a plenum (i.e., part of the forced-air heating
system), the crawl space temperature approaches that of the indoor
conditioned space. In the former case, the floor above the crawl
space, the heating ductwork, and the utility pipes should be insu-
lated similarly to the walls and ceiling of a house.
The following steady-state equation can beused to estimate the
temperature of a crawl space.
Yf = Y/J + 4, + 4 ,
where
q, = heat loss through floor into crawl space,Btdh
q,, = heat loss from crawl space through foundation walls and sill box,
Btuh
q8 = heat loss into ground, Btuh
q, = heat loss due to ventilation of crawl space,Btuh
Latta and Boileau (1969) estimated the air exchange rate foran
uninsulated basement at0.67 ACH under winterconditions.In more
detail, the above equation canbe repeated as
where
ri = indoor air temperature (Le.,air above ceiling of crawl space),T
r , = outdoor air temperature, T Fig. 3 Uninsulated Crawl Space
Solution: Three cases are examined. Pitched roofs. Calculate the combined roof and ceiling coeffi-
Cave A. This base case is a vented and uninsulated crawl space. The cient as outlined in Chapter24.
crawl space temperature approachesthat of the outdoors, 10°F.and the
heat loss is 0.25 x 1200(70- 10) = 18,000 Btuh. 2. For pitched roofs, estimate the attic temperature (based on the
Caw B. The crawl space is vented. The floor above is insulated indoor and outdoor design temperatures) using Equation (3).
with an R- 11 blanket; no insulation on the perimeter. The temperature and substitute for t, in Equation (5), obtaining the value oft,,
of the crawl space approachesthat of the outdoors, 10°F. The heat loss together with the ceiling areaA and the ceiling U-factor. Attic
is calculated as temperatures do not need to be calculatedf o r p a t roofs, as the
ceiling-roofheat loss canbedeterminedassuggestedin
y, = 1200 X 0.076(70 - I O ) = 5470 Btu/h Method 1 above.
Cuse C. The crawl space is not vented during the heating season.
The floor above is not insulated, but the perimeterwall is insulated with
From the Basement
R-5.4 down to 3 ft below grade. The basement interior is considered conditioned space if a min-
imum temperature of 10°F below indoor design air temperature is
y, = 1200 X 0.25(70 - f c ) maintained over the heating season. In many instances, the house
4,, = 140 X 0.62(rc- 10) heating plant, water heater, and heating ductsin the are basement,so
it remains at or above 50°F.
4, = 1200 X 0.077(tC- 50)
Heat transmission from the below-grade portion of the basement
y, = 1200 X 3 X 0.67 X 0.018(tC- 10) wall to the ambient air cannot be estimatedby simple, one-dimen-
sional heat conduction. In fact, field measurement of an uninsulated
The crawlspace temperature is solvedusingEquation (4): r, =
basement by Latta and Boileau (1969) showed that the isotherms
5 1Y F . The heat loss is 5550 Btu/h.
The results show thatbasecase A canpotentiallylosethe most
near the wall arenot parallel linesbut closer to radial lines centered
heat. However,when the floor above is insulated, the crawl space must at the intersection of the grade line and the wall. Therefore, heat flow
be vented to eliminate any condensation potential, and the heating duct- paths approximately follow a concentric circular pattern (Figure 4).
work and utility pipeline in the crawl space must be adequately insu- Such heat flow paths are altered when insulation is added to the
lated. When the perimeter is insulated, the vents must be closed during wall or floor. An extreme case would be no heat loss from the base-
the heating season and opened for therest of the year; the heating duct- ment wall and floor (Le,, infinite insulation applied to the wall and
work and utility pipeline do not need insulation. floor). In this case, the isotherms would be horizontal lines parallel
to the grade line, and the heat flow would be vertical. When finite
Heat Loss Temperature insulation or partial insulation is applied to the wall and floor, the
Through
Floor of Crawl
Venting
Insulation
Case Above, B t d h Space, "F heat flow paths take shapes somewhere between the circular and
vertical lines (Figure5).
A Yes None I8.000 10 Ground Temperature. Ground temperatures assumed for esti-
B Yes R-I 1 on floor above 5,470 10 mating basement heat losses will differ for basement floors and
C No R-5.4 on perimeter wall 5,550 51.5 walls. The temperatures under floors are generally higher than those
adjacent to walls. This is discussed further in the section on Base-
ment Design Temperatures.
CALCULATING TRANSMISSION HEATLOSS
Steady-state heat loss by conduction and convection heat trans- Through Basement Walls
fer through any surface is Houghten et al. (1942) observed nonuniform heat flux across the
basement wall with respect to the depth of the wall because each
= UA([;- t,,) (5) heat flow path contains a different thermal resistance. For a base-
ment wall that has its top portion exposed to ambient air, heat may
where be conducted vertically through the concrete wall and dissipated to
y = heattransferthroughwall, glass, roof, ceiling, floor, or other the ambient from the top portion of the wall (Wang 1979, Bligh et al.
exposed surface, Btu/h 1978). Under certain conditions, this vertical heat flux becomes sig-
A = area of surface, ft2 nificant and shouldnot be ignored.
U = air-to-air heat transfer coefficient,Btu/h.ft2."F
ti = indoor air temperature nearsurface involved, "F
M
r,, = outdoor air temperature or temperature ofadjacentunheated
space, "F
Table 14 Heat Loss Below Grade in Basement Walls 160 140 120 100 BO 60
T ~ t d
Total basement heatloss below gmde ...72 + 21 = 93 Btu/h."F
Design temperature difference......................... 70 - 20 = 50°F
Maximum rateof heat loss from
below-grade basement......................... 93 x 50 = 4650 Btuh
F2 = heat loss coefficient per foot of perimeter (see Table16), PouredconcretewallUninsulated 2.732.121.84
Btulh.ft.T with duct
near R-5.4 from 0.64 0.72 0.90
P = perimeter or exposed edgeof floor, ft primete? edge to footer,
I; = indoor temperature, T (For the heated slab, r; is the weighted 3 ft under floor
average heating ductor pipe temperature.) "Weighted average temperatureof the heating duct was assumedat I IOCFduring the
r , = outdoor temperature, T heating season (outdoorair temperature less than 65°F).
and Cooling
Residential 27.13
41 = Qp(Wi-W0)hfg (9)
where
41 = heat flow required to increase moisture content of air leakage into
building from W, to W;, Btuh
Q = volumetric flow of outdoor air entering building, ft3/h
p = density of air at temperaturer;. Ib/ft3
W;= humidity ratio of indoor air,IbAb,,
W, = humidity ratio of outdoor air, Ib/lb,,
hfg = latent heat of vapor atr;, B u b
If the latent heat of vaporh,-- is 1076 Btu/lb, and the air density
is 0.075lb/ft3, Equation (7) reduces to
Crack LengthMethod
C. METAL
WALL
STUD D. CONCRETE WALL The basis of calculation for the crack method is that the amount
of crack used for computing the infiltration heat loss should not be
Fig. 8 Slab-on-Grade Foundation Insulation less than one-half the total length of crack in the outside walls of the
room. In a building without partitions, air entering through cracks
Figure 8A shows that this construction benefits from the wall on the windward side must leave through cracks on the leeward
insulationbetweenblockandbrick;theinsulationisextended side. Therefore, one-half the total crack for each side andof end the
roughly 16 in. below the slab floor. Without this wall insulation, the building is used for calculation. In a room with one exposed wall, all
heat loss coefficientF2 would be close to that of the 4 in. blockwall the crack is used. With two, three, or four exposed walls, either the
construction (FigureSB). Table 16 canbe used to estimate F2under wall with the crack that will resuIt in the greatest air leakage or at
different degree-days of heating season weather. least one-half the total crack is used, whichever is greater.
In residences, total infiltrationloss of the house is generally con-
CALCULATING INFILTRATION HEAT LOSS sidered equal to the sumof infiltration losses of the various rooms.
But, at any given time, infiltration takes place on only
the windward
Infiltration of outside air causes both sensible and latenr heat side or sides and not on the leeward. Therefore, for determining total
loss. The energy requiredto raise the temperatureof outdoor infil- heat requirements of larger buildings,it is more accurate to base total
trating air to indoor air temperature is the sensible component. The infiltration losson the wall with the most total crackonorat leasthalf
energy associated with net loss of moisture from the space is the the total crack in the building, whicheveris greater. When the crack
latent component. Infiltration is discussed in detail in Chapter 25. method ratherthan Equations (8) and (10) is used for estimating leak-
age, the heat loss in terms of the crack length may be expressed as
Sensible Heat Loss
The energy required to warm outdoor air entering
by infiltration qs = 0.018BL(ri - t(,) (1 1)
to the temperature of the roomis given by and
Air Change Method In buildings with setback-type thermostats, the furnace must be
oversized to allow for reestablishing the space temperature in an
Some designers base infiltration on an estimated number ofair
acceptable time. The amount of oversizing depends on many fac-
changes rather than the length of window cracks. The number of air
changes given in Chapter25 should be considered only as a guide.
tors, such as the amount of setback, inside-to-outside temperature
difference,buildingconstruction,andacceptablepickuptime.
Whencalculatinginfiltrationlossesbytheairchangemethod,
Figure 9 indicates this relationship for a particular residence. As a
Equations (8) and (10) can be used by substituting forQ the volume
general rulefor residences, a 10°F night setback requires 40% over-
of the room multipliedby the number ofair changes.
sizing for acceptable pickup time and minimum energy require-
Exposure Factors ments(NelsonandMacArthur1978). For smallersetback,the
oversizing can be proportionally less. If daytime as well as night set-
Some designers use empirical exposure factors to increase cal- back is practiced, oversizingof up to 60% is warranted.
culated heat loss of rooms or spaces on the side(s)of the building
exposed to prevailing winds. However, exposure factors are not REFERENCES
needed with the method of calculating heat loss described in this
chapter. Instead, they may be (1) regarded as safety factorsto allow ASHRAE. 1992. Thermal environmental conditions forhuman occupancy.
for additional capacity for rooms or spaces exposed to prevailing ANSVASHRAE Srundurd 55-1992.
ASHRAE. 1995. Addendum to ANSVASHRAE 55-1992. ANSVASHRAE
winds or (2) used to account for the effectsof radiation loss, partic- Srundurd 5%-1995.
ularly in the case of multistory buildings. Tall buildings may have Bligh, T.P., P. Shipp, and G. Meixel. 1978. Energy comparisons and where
severe infiltration heat losses induced by stack effect that require to insulate earth sheltered buildings and basements. Earth covered settle-
specialanalysis.Althougha15%exposureallowance is often ments, U.S. Department of Energy Conference, Fort Worth. TX.
assumed, the actual allowance,if any, is largely a matterof experi- Chang, J.H. 1958. Ground temperufure.Bluehill Meteorological Observa-
ence and judgment; no test data are available from which to develop tory, Harvard University, Cambridge, MA.
rules for the many conditions encountered. Harrje,D.T.,G.S.Dutt,andJ.Beyea.1979.Locatingandeliminating
obscure but major energylosses in residential housing.ASHRAE Truns-
uclions 85(2).
PICKUP LOAD Houghten, F.C.,S.1. Taimuty, C. Gutberlet. and C.J. Brown. 1942. Heat loss
through basement walls andfloors. ASHVE Trunsuctims 48369.
For intermittently heated buildings and night thermostat setback, Joy, F.A. 1958. Improving attic space insulating values. Heating, Piping und
additional heat is required to raise the temperature of air, building Air Conditioning 30(1):223.
materials, and material contents of a building to the specified tem- Joy, F.A., J.J. Zabrony,and S. Bhaduri. 1956. Insulating value of reflective
perature. The pickup load, which is the rate at which this additional elements in an attic under winter conditions. Pennsylvania State Univer-
heat must be supplied, depends on heat the capacity of the structure, sity, University Park, PA.
its material contents, and the time in which theseto be areheated. Latta, J.K. and G.G. Boileau.1969.Heatlossesfromhousebasements.
Relatively little information on pickup load exists; however, someCunudiun Building l9( 10):39.
early work by Smith (1 941, 1942) addressed pickup loads for build- McQuiston, F.C. 1984. A study and review of existing data to develop a
ings heated only occasionally, such as auditoriums and churches. standard methodology for residential heating and cooling load calcula-
Nelson and MacArthur(1978)studied the relationship between ther- tions. ASHRAE Trunsuctions90(2A): 102-36.
McQuiston, F.C. and J.D. Spitler. 1992.Cooling und heuting loud culculu-
mostat setback, furnace capacity, and recovery time. Based on this tion munuul, 2nd ed. ASHRAE, Atlanta.
limited information, the following design guidelines are offered. Nelson, L.W. and J.W. MacArthur. 1978. Energy savings through thermostat
Because design outdoor temperatures generally provide a sub- setback.ASHRAE Trunsuctions84(2):319-34.
stantial margin for outdoor temperatures typically experienced dur- Peony, B.A., F.J. Powell,and D.M. Burch. 1979. Dynamic thermal perfor-
ing operating hours, many engineers make no allowance for this mance of anexperimentalmasonrybuilding.NBS Report 10 664,
additional heat in most buildings. However, if a minimum safety National Institute of Standards and Technology, Gaithersburg,MD.
factor is to be used, the additional heat should be computed and Rowley, F.B., A.B. Algren, and C.E. Lund. 1940. Methods of moisture con-
allowedfor,asconditionsrequire. In thecase of intermittently trolandtheirapplication tobuildingconstruction. Bulletin No.17
heated buildings, an additional 10% capacity should be provided. XLII1(4):28. University of Minnesota Engineering ExperimentStation.
Smith,E.G.1941.Heatrequirement ofintermittentlyheatedbuildings.
Texas A&MEngineering Experiment Stution Series No. 62 (November).
College Station, TX.
DESIGN CONDITIONS Smith, E.G. 1942. A method of compiling tables for intermittent heating.
Heuting, Piping, und Air Conditioning 14(6):386.
// 1
INSULATION
WALLS: 35f8 in. FURNACE OUTPUT
Wang, F.S. 1979. Mathematical modeling and computer simulation of insu-
INSULATIONCEILING 6 In. CAPACITY, PERCENT
lation systems in below grade applications. ASHRAE/DOE Conference
OVER DESIGN
TEMPERATURE:
OUTDOOR DESIGN-2VF LOSS
HEAT onThermalPerformanceoftheExteriorEnvelopesof Buildings,
2D L
1 20% Orlando, FL.
BIBLIOGRAPHY
Ackridge,J.M.andJ.F.Poulos.1983.Thedecrementedaverageground
temperature method for predicting the thermal performance of under-
ground walls. ASHRAE Trunsuctions89(2A).
Burch, D.M., D.F. Krintz, and R.S. Spain. 1984. The effectof wall mass on
winterheatingloadsandindoorcomfort-Anexperimental study.
ASHRAE Trunsuctions90( I B).
Kusuda, T. and J.W. Bean. 1984. Simplified methods for determining sea-
sonal heat loss from uninsulated slab-on-grade floors. ASHRAE Truns-
I I 1 UCfi(Jn.T 90( I B).
30 40 50 70 80 90 Mitalas, G.P. 1983. Calculationof basement heat loss. ASHRAE Trunsuc-
TEMPERATURE DFFERENCE BETWEEN#DOOR AND OUTDOOFj,'F rions 89( 1B).
Yard, D.C.,M.Morton-Gibson, andJ.W. Mitchell. 1984. Simplified dimen-
Fig. 9 Furnace Operating Times Requiredto Pick Up Space sionless relations for heat loss from basements. ASHRAE Trunsuctions
Temperature Following 5 and 10°F Night Setback 90(IB).