-Internal DT-'N'
FIRE & GAS SYSTEM
LOGIC DIAGRAM
EXECUTED BY
SCALE REPLACE / DERIVED FROM 1st ISSUE ORIGINAL JOB SIZE LANGUAGE
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
REVISION INDEX
SHEET TITLE 0 1 2 3 4 5 6 7
1 COVER SHEET X ACRONYMS LEGEND
2 INDEX X
F&G = CUSTOMER PLANT F&G SYSTEM
3 SYMBOL LEGEND X
LD = FIRE FIGHTING LOCAL DISPLAY
4 XooY VOTING LOGIC X
HMI = UCS HUMAN MACHINE INTERFACE
5 FIRE 2oo2 VOTING LOGIC WITH FAULT DETECTION SIGNAL X
TCP = TURBINE CONTROLLER
6 FIRE 2oo3 VOTING LOGIC WITH FAULT DETECTION SIGNAL X
UCS = UNIT CONTROL SYSTEM
7 FIRE 2oo4 VOTING LOGIC WITH FAULT DETECTION SIGNAL X
FGS = CUSTOMER PLANT FIRE & GAS SYSTEM
8 UV/IR FIRE 2oo2 VOTING LOGIC BLOCK X
SIS = MARK VIeS
9 GAS 2oo3 VOTING LOGIC BLOCK X
24 FAULT LOGIC X
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
SYMBOLS LEGEND
DI
DELAY ON
OR OR PORT . FRONT PANEL MOUNTED T ENERGIZING
HARDWARE INTERLOCK
PUSH BUTTON/SELECTOR
.
A AND PORT
AUX. RELAY LOCAL INSTRUMENT
DO
DROP-OUT
T
T
GREATER THAN S
ALARM HORN SET PREVALENT FLIP-FLOP
R PULSE
PULSE
NOT
T
FLASHING LAMPS INPUT/OUTPUT DESCRIPTION
REFERENCE FOR OTHER PAGE:
X X: TO/FROM
Y Y: REFERECE NO.
FUNCTIONAL BLOCK
LAMPS
. INDICATION/ALARM ON
OPERATOR INTERFACE
. SV SOLENOID VALVE
I FUNCTIONAL INTERLOCK
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
XooY voting logic
SYMBOL LOGIC
A
B
C A
D B
Out C
XooY
X A
Y
X
OR Out
Xi All AND
logics
X outputs
inputs
A
Xj
Xk
X
A
inputs
Y
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
Fire Sensor 1 X1 Y1
FIRE ALARM
OR Y3 LOOP FAULT
AND SHUTDOWN
Fire Sensor 2 X3
AND
Fire Sensor 2 Fault X4
1oo2
Logic Y4 FIRE TRIP
OR
2oo2
Logic
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
Fire Sensor 1 X1 Y1
FIRE ALARM
OR Y3 LOOP FAULT
AND
SHUTDOWN
Fire Sensor 2 X3
AND
Fire Sensor 2 Fault X4
2oo3
Logic Y4
OR FIRE TRIP
2oo3
Fire Sensor 3 X5 Logic
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
Y1
Fire Sensor 1 X1 FIRE ALARM
AND
Fire Sensor 3 X5
Fire Sensor 3 Fault X6
2oo4
Logic Y4
OR FIRE TRIP
Fire Sensor 4 X7
Fire Sensor 4 Fault X8
2oo4
Logic
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
Fire Sensor 1 X1
Y1
OR FIRE ALARM
Y3 LOOP FAULT
Fire Sensor 2 X3 AND
SHUTDOWN
Fire Sensor 2 Fault X4
2oo2
Logic
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
AND
GAS DETECTOR 1 X1 TRIP = 1
OR
GAS DETECTOR 1 FAULT X2 FAULT = 1
Y1
GAS DETECTOR 2 AND OR GAS TRIP
X3 TRIP = 1
OR
GAS DETECTOR 2 FAULT X4 FAULT = 1
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FIELD FROM SH. FIRE CONTROL LOGIC TO SHEET TURBINE CONTROLLER
1
COMPARTMENT
X1 FIRE DETECTOR
(LC) FIRE = 1
(CLOSED=FIRE)
2
OR 12 FIRE TRIP (1= TRIP)
Note 2
FAULT
COMPARTMENT 1
Xn FIRE DETECTOR (LC) FIRE = 1
(CLOSED=FIRE)
Note 1 2
OR 24 FAULT ALARM (1= FAULT)
FAULT
Instrument and Signals I/O summary LD LD
1 TAHH TA
Accessory Comp. Turbine Comp. Coupling Comp. Other 2
REF. TAG X1 X2 X3 X4 X5 X6 X1 X2 X3 X4 X5 X6 X1 X2 X3 X4 X5 X6 X1 X2 X3 X4 X5 X6 . .
GE TAG 45FT-1 45FT-2 45FT-3 45FT-4 45FT-5 45FT-6
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FIELD FROM SH. FIRE CONTROL LOGIC TO SHEET TURBINE CONTROLLER
Y1
LOOP (N.O. CONTACT) UV/IR DETECTOR FIRE ALARM
UV/IR 3 HMI
TCP Y1D
2oo2
(LC) .
X1 UV/IR DETECTOR X1
FAULT Y1 Note 1
Note 1 X2
2 Y2 Y2
X2
(LC) (N.O. CONTACT)
UV/IR DETECTOR X3
Y3
3 Y2D
HMI
FAULT TCP
Note 1 X4 Y4
.
2
Note 1
Note:
FIRE FAULT SHUTDOWN
1. Instrument Customer Tag and GE Tag will be
23
follow “Instrument and Signals I/O summary” table. (1= SHUTDOWN)
LD LD LD
BAHH BA Y
. . . 12 UV DETECTOR FIRE TRIP
(1=TRIP)
1 2 3
Instrument and Signals I/O summary
Loop1 Loop2 Loop3 Loop4 Loop5
REF. TAG X1 X2 Y1D Y2D X1 X2 Y1D Y2D X1 X2 Y1D Y2D X1 X2 Y1D Y2D X1 X2 Y1D Y2D
GE TAG IR3-1 IR3-2 45FTA
RE RE
CUST. TAG 702/ A 702/ B
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FROM SH. FIRE CONTROL LOGIC TO SHEET TURBINE CONTROLLER
FIRE MONITOR
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FROM SH. FIRE CONTROL LOGIC TO SHEET TURBINE CONTROLLER
15 FIRE TRIP
ENCLOSURE FIRE TRIP (1=TRIP) 12 1 (1=TRIP)
DI
FIRE TRIP
OR 16
T 1 (1=DISCH)
FIELD FIRE TRIP
T=1 sec 18
(1=DISCH)
1
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
F&G PANEL FROM SH. FIRE CONTROL LOGIC TO SHEET FIELD
1 FAULT
(LC)
SV CO2 DISCHARGE
SOLENOID VALVE
FV-741 (45CR-1)
1 FAULT
DI
DISCHARGE COMMAND LATCHED 13 (LC) CO2 DISCHARGE
A SV SOLENOID VALVE
(1=DISCH) T
FV-742 (45CR-2)
T=30 sec
DISCHARGE OK 19
(1=OK)
1 FA
LD
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FROM SH. FIRE CONTROL LOGIC TO SHEET SIS
XS-370
(45FTT_S)
FIRE TRIP FROM F&G OR RELEASE IN
(N.O. CONTACT) PROGRESS
CO2 DISCHARGED 20 SIS
(1=DISCHARGED)
OR S
R
1
FIRE TRIP 13
(1=TRIP) 1
XS-112
(45FTT_C)
(N.O. CONTACT) Plant F&G System
RESET 13 FGS
(1=RESET) 2
1
ENCLOSURE FIRE DETECTED TRIP
1 Y
LD
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FROM SH. FIRE CONTROL LOGIC TO SHEET UCS TO MCC
XS-380
(4BA2_C)
(N.O. CONTACT)
FILTER HOUSE GAS DETECTED 22
TRIP (1=TRIP)
FIRE TRIP 13
(1=TRIP) 1
ENCLOSURE
RESET 13 VENTILATION
(1=RESET) 2 FAN #n CUT
OUT
1
1 Y
LD XS-381
(4BA2_C)
(N.O. CONTACT)
.
Instrument and Signals I/O summary
Fan Cut‐Out 1 Fan Cut‐Out 2 Fan Cut‐Out 3 Fan Cut‐Out 4 Fan Cut‐Out 5 Fan Cut‐Out 6 Fan Cut‐Out 7 Fan Cut‐Out 8
GE TAG 4BA1_C 4BA2_C
CUST. TAG XS‐380 XS‐381
TITLE DOCUMENT CODE REVISION
OPTION 1.A - UCS NO SIL CONFIGURATION
VENTILATION CUT OUT LOGIC
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
F&G HMI FROM SH. FIRE CONTROL LOGIC TO SHEET TURBINE CONTROLLER
XS-163 (43CP_I)
(CONTACT NO )
SYSTEM INHIBITED
(1=INHIBITED)
XS 1 TCP HMI
457
ELECTRICAL DISCHARGE XA
AUTO/INHIBIT SELECTOR
(CLOSED=INHIBIT) 163
(43AUTO) 2
INHIBIT TO
START
ELECTRICAL DISCHARGE
19 SYSTEM INHIBITED
(1=INHIBITED)
1 2 Y
LD
XA
. .
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
F&G HMI FROM SH. FIRE CONTROL LOGIC TO SHEET F&G PANEL
LAMP TEST 19
OR
FIELD
FIRE TRIP 13 XL (XL-n)
(LC)
(1=TRIP) 1 OR S FIRE ALARM RED
FLASHING LIGHT DURING
R DISCHARGE, FIXED AFTER
CO2 DISCHARGED 1 FAULT DISCHARGE)
20
(1=DISCH) Note 1
(LC) XA (XA-n)
RESET FIRE ALARM HORN
(1=RESET) 13
2
Note: 1 FAULT
1. Lamps and Horns to be added according to q.ty
defined in the Ordering sheet
2. Alert and signalization status is active on all inputs or
internal diagnostics change status
Instrument and Signals I/O summary
1 XA
Red Lamps Horns
REF.TAG XL‐1 XL‐2 XL‐3 XL‐4 XL‐5 XL‐6 XA‐1 XA‐2 XA‐3 XA‐4 XA‐5 XA‐6 .
GE TAG XL‐1 XL‐2 XA‐1 XA‐2
XL XL XA XA
CUST. TAG 702/ A 702/ B 703/ A 703/ B
TITLE DOCUMENT CODE REVISION
ALARM AND SIGNALIZATION
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FIELD FROM SH. FIRE CONTROL LOGIC TO SHEET TURBINE CONTROLLER
ZAL
SLOW DISCHARGE ISOLATION (LC) 1
744/A
VALVE CLOSE CLOSED = 1
(33CP-1A) (CLOSED =CLOSE) TCP
XA
HMI
FAULT 2 AND
-
INHIBIT TO
ZAL
QUICK DISCHARGE ISOLATION (LC) CLOSED = 1 START
744/B
VALVE CLOSE XS-164 (33CP-1)
(33CP-1B) (CLOSED =CLOSE) (N.O. CONTACT ) FIRE FIGHTING CO2 ISOLATION VALVES CLOSED
FAULT 2 1
DISCHARGE OK
14 (1=OK)
OR
1 ZI 2 ZA
. . 18 LAMP TEST
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FIELD FROM SH. FIRE CONTROL LOGIC TO SHEET TURBINE CONTROLLER
13 CO2 DISCHARGED
(1=DISCHARGED)
15 CO2 DISCHARGED
(1=DISCHARGED)
XS-113
(63CPD-C) CO2 RELEASE IN PROGRESS
(N.O. CONTACT)
0=RELEASE IN PROGRESS
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FIELD FROM SH. GAS CONTROL LOGIC TO SHEET TURBINE CONTROLLER
1 Note 3 Y1
VENTILATION OUTLET GAS GAS DETECTED ALARM
X1 2 (N.O CONTACT) Note 1
DETECTOR PRE-ALARM = 1
>= TCP HMI
LELxH
PRE-ALARM = 1
Y1
Note 1 2 OR
1 PRE-ALARM = 1 .
>=
VENTILATION OUTLET GAS LELxH
X2 I
DETECTOR 2 PERMISSIVE
TO START
>= Y2
Note 1 1 LELxH
(N.O CONTACT)
GAS DETECTED TRIP
3 GAS 2oo3 Note 1
VENTILATION OUTLET GAS
X3 >=
with Fault TCP
Y2
HMI
DETECTOR LELxHH
TRIP = 1
X1
4 .
Note 1 FAULT Y1D
FAULT = 1 (N.O CONTACT)
X2
3 I TRIP
>= TRIP = 1
X3 S
LELxHH
4 Plant F&G System
FAULT = 1
Y1 R
FAULT X4
FGS
3
TRIP = 1
>= X5 GAS DETECTED TRIP
LELxHH
Note: 4
FAULT = 1
1. Instrument Customer Tag and GE Tag will be follow
“Instrument and Signals I/O summary” table. FAULT X6 SIS
2. HW outputs to be evaluated according to SIL Y2D SIS
requirements (1=RESET) (N.O CONTACT)
3. LEL H=5% and LEL HH=10% 15
GAS DETECTED TRIP
Instrument and Signals I/O summary
LD
Loop1 Loop2 LD
AH
LD
AHH
LD
AA
1
AI
2 3 4
REF. TAG X1 X2 X3 Y1 Y2 Y1D Y2D . . . .
GE TAG 45HD-1A 45HD-1B 45HD-1C 45HTA 45HTT 45HTT-C 45HTT_S
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FIELD FROM SH. GAS CONTROL LOGIC TO SHEET TURBINE CONTROLLER
1 Note 3 Y1
FILTER HOUSE 2 GAS DETECTED ALARM
X1 (N.O CONTACT)
GAS DETECTOR PRE-ALARM = 1
>= TCP HMI
LELxH
PRE-ALARM = 1
Y1
Note 1 2 OR
1 PRE-ALARM = 1 .
>=
FILTER HOUSE LELxH
X2 I PERMISSIVE
GAS DETECTOR 2 TO START
>= Y2
Note 1 1 LELxH
(N.O CONTACT) FILTER HOUSE GAS DETECTED
16 TRIP (1=TRIP)
3 GAS 2oo3
FILTER HOUSE
X3 >=
with Fault GAS DETECTED TRIP
GAS DETECTOR LELxHH
TRIP = 1
TCP HMI
X1
4 Y2
Note 1 FAULT Y1D
FAULT = 1 (N.O CONTACT) .
X2
3
LELxHH
>= TRIP = 1
X3 S I TRIP
3
TRIP = 1
>= X5 GAS DETECTED TRIP
LELxHH
4
Note: FAULT = 1
1. Instrument Customer Tag and GE Tag will be follow FAULT X6 SIS
“Instrument and Signals I/O summary” table. Y2D SIS
2. HW outputs to be evaluated according to SIL
(1=RESET) (N.O CONTACT)
requirements 15
3. LEL H=10% and LEL HH=20% GAS DETECTED TRIP
Instrument and Signals I/O summary
LD LD
Loop1 Loop2 LD
AH
LD
AHH AA
1
AI 2 3 4
REF. TAG X1 X2 X3 Y1 Y2 Y1D Y2D . . . .
GE TAG 45HF-1 45HF-2 45HF-3 45HFA 45HFT 45HFT-C 45HTT_S
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FIELD FROM SH. GAS CONTROL LOGIC TO SHEET TURBINE CONTROLLER
1
GAS DETECTOR
X1 FLOW SWITCH
(LC) ALARM = 1 XS-160
(33IDA)
(N.O. CONTACT) GAS DETECTOR FLOW
(CLOSED=ALARM) SWITCH ALARM
TCP TCP
2 XS-160
OR
Note 2 33IDA
FAULT
GAS DETECTOR 1
Xn FLOW SWITCH (LC) ALARM = 1
(CLOSED=ALARM)
Note 1 2
FAULT
XS-161
(33IDT)
(N.O. CONTACT) GAS DETECTOR FLOW
SWITCH TRIP
TCP TCP
XS-161
2ooN
33IDT
Note: Note 3
1. Instrument Customer Tag and GE Tag will be
follow “Instrument and Signals I/O summary”
table.
2. These instruments are part of the same loop.
3. N represents the maximun qty of instruments
in the loop
Instrument and Signals I/O summary TAHH
LD
TA
LD
1 2
REF. TAG X1 X2 X3 X4 X5 X6 X1 X2 X3 X4 X5 X6 X1 X2 X3 X4 X5
. .
GE TAG 33ID‐5A 33ID‐5B 33ID‐5C
CUST. TAG FSL‐262A FSL‐262B FSL‐262C
TITLE DOCUMENT CODE REVISION
GAS FLOW SWITCH VOTING LOGIC
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.
FIELD FROM SH. FIRE CONTROL LOGIC TO SHEET TURBINE CONTROLLER
Note 1 XA
S
.
R
I NORMAL STOP
FIRE FAULT SHUTDOWN
(1= SHUTDOWN) 11
Note 1
XS-115
(86FG-SD-C)
Plant F&G System
(N.O CONTACT) FGS
Note:
1. Instrument Customer Tag and GE Tag will be XS-114
change according to Personalization sheet. (86FF-C) FIRE & GAS SYSTEM FAULT
2. internal FF CPU fault, not included Sensors fault (N.O CONTACT)
3. fault from line monitoring checks.
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE SHEET
WRITTEN PERMISSION OF UNPUBLISHED WORK ©2013 ALL RIGHTS RESERVED.