SHELL APPURTENANCES :
1. ONE (1) 24 IN. MANWAY FOR TANKS UP TO AND
INCLUDING 6m (20 FT.) DIAMETER.
TWO (2) 24 IN. MANWAYS FOR TANKS OVER 6m
(20 FT.) TO 30m (100 FT.) DIAMETER.

24 IN. MANWAY ONE (1) 30 IN. AND TWO (2) 24 IN. MANWAYS FOR
30 IN. MANWAY OR LOCATION WHEN 2 OR TANKS OVER 30m (100 FT.) TO 60m (200 FT.)
915 mm x 1220 mm MORE SPECIFIED DIAMETER.
(3 FT. x 4 FT.)
ONE (1) 30 IN. MANWAY AND A SUFFICIENT NUMBER
CLEANOUT DOOR
OF 24 IN. MANWAYS SPACED AT NO MORE THAN
46m (150 FT.) APART AROUND THE TANK
CIRCUMFERENCE FOR TANKS OVER 60m (200 FT.)
DIAMETER.
2. FLUSH TYPE CLEAN-OUT DOOR, WHEN SPECIFIED IN
THE TANK DATA SHEET, SHALL BE 900mm x
1200mm (36 IN. x 48 IN.) MINIMUM, AND IT MAY BE
SUBSTITUTED FOR ONE MANWAY.

3. APPURTENANCE ORIENTATION TO BE SPECIFIED BY


THE DESIGN ENGINEER. CLEANOUT DOOR SHALL BE
LOCATED TRANSVERSE TO THE PREVAILING WIND
90^ AND EASILY ACCESSIBLE FROM THE ROADWAY.

CONE ROOF:
1. ONE (1) 24 IN. MANWAY FOR TANKS UP TO AND
INCLUDING 6m (20 FT.) DIAMETER.

TWO (2) 24 IN. MANWAYS FOR TANKS OVER


24 IN. MANWAY 6m (20 FT.) TO 30m (100 FT.) DIAMETER.

THREE (3) 24 IN. MANWAYS FOR TANKS OVER


30m (100 FT.) DIAMETER.
24 IN. MANWAY LOCATION 2. VENTS TO BE SIZED IN ACCORDANCE WITH API
WHEN ONE OR MORE EMERGENCY VENT
(WHEN 2 OR MORE STANDARD 2000.
SPECIFIED WATER DRAWOFF MANWAY REQUIRED)
3. TANKS IN SOUR SERVICE SHALL HAVE VENTS
LOCATED DOWNWIND FROM GAGE HATCH.
5^
(MI 4. IF VENTS IN ADDITION TO THE CENTER VENT ARE
N.)
PRODUCT NOZZLES REQUIRED, LOCATE AS SHOWN.
24" ROOF MANWAY
EXTERNAL FLOATING ROOF:
FIGURE-1 TO API 650
1. MANWAYS FOR ACCESS :

TYPICAL PLAN FOR SHELL APPURTENANCES ONE (1) 30 IN. DECK MANWAY FOR TANKS UP TO
AND INCLUDING 91m (300 FT.) DIAMETER.
ONE (1) 40 IN. DECK MANWAY FOR TANKS OVER
91m (300 FT.) DIAMETER.
VENT
(DWG. AD-036061) 2. MANWAYS FOR VENTILLATION :
24" ROOF MANWAY
TO API 650 ONE (1) 24 IN. DECK MANWAY FOR TANKS UP TO
AND INCLUDING 60m (200 FT.) DIAMETER.

TWO (2) 24 IN. DECK MANWAY FOR TANKS OVER


60m (200 FT.) TO 90m (300 FT.) DIAMETER.

THREE (3) 24 IN. DECK MANWAYS FOR TANKS OVER


VENTS 90m (300 FT.) DIAMETER.
6" RIM VENT 3. PONTOON MANWAYS SHALL BE 20 IN. NOMINAL
GAGE HATCH
20" PONTOON MANWAY 2 DIAMETER.
’-
ONE PONTOON MANWAY TO BE 6
"
SUPPLIED FOR EACH PONTOON 4. MINIMUM OF ONE (1) 6 IN. RIM VENT IS REQUIRED.
OF THE ROOF. 5’ ADDITIONAL VENTS SHALL BE PROVIDED AS
-0 REQUIRED PER DESIGN.
" 5
’-0
" 5’-0
" 5’-0" 5. BLEEDER VENT SHALL BE SIZED IN ACCORDANCE
24" ROOF MANWAY
WITH THE MAXIMUM FILLING AND EMPTYING RATES
(EMERGENCY VENT
WHEN ONE MANWAY SPECIFIED ON THE TANK DATA SHEET.
SPIRAL STAIRWAY REQUIRED)
PLATFORM & RAILING INTERNAL FLOATING ROOF:
1. REQUIREMENT OF VENT AND MANWAYS SHALL BE IN
ACCORDANCE WITH 32-SAMSS-005, APPENDIX H.

MANWAY FIGURE-2
DRAWING RESPONSIBILITY :

DRAIN
TYPICAL PLAN FOR CONE ROOFS VESSEL STANDARDS COMMITTEE

ESSD REVISED NOTES & CHANGED "DWG.


01 MAY96 MANDATORY NOTE" TO "DWG.
RLO RESPONSIBILITY NOTE".
REV.
DATE BY JO/EWO DESCRIPTION CHKD. CERT. APPD.
NO.

SAUDI ARABIAN OIL COMPANY


DRAWN BY ESSD/BSC CHECKED BY NONE
SCALE
GAGE WELL & GUIDEPOLE DATE STARTED DATE COMPLETED 02-05-92
DWG. AA-036504 OR AA-036256,
OPR’G. DEPT. ENG. DEPT.
AS APPLICABLE
APP’D FOR CONSTR.

THIS DRAWING IS NOT TO BE USED FOR CERTIFIED


CONSTRUCTION OR FOR ORDERING
SPIRAL STAIR GAGER’S PLATFORM MATERIAL UNTIL CERTIFIED AND DATED BY DATE

& INTERMEDIATE PLATFORM DWG. AE-036129


TO API 650 MANWAYS AND VENTS FOR TANKS
FIGURE-3
TYPICAL PLAN FOR EXTERNAL FLOATING ROOFS STD. DWG.
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

990 D AB-036003 001 01


Saudi Aramco 2634 ENG. (3/91)