You are on page 1of 1

Pre-Bid Replies-TPDDL/ENGG/ENQ/200001287/20-21 by TATA POWER DDL

S No Queries TPDDL Reply


Please confirm if other than OEM's of relays i.e. the panel manufacturers Panel manufacturers can participate in the bid subjected to tender qualification
can participate in the tender. However, please note that we are channel criteria. However, the make of raw materials, IEDs, aux. relays, control cables, LT
partner or M/s GE T&D and we have already supplied panels in TPDDL. switchgears, Terminal Blocks, lugs & glands shall be as per TATA Power-DDL
1 approved makes.
Panel manufacturer needs to submit MAF/undertaking from IED manufacturer for
back-to-back support, services and warranty of the products.
TATA Power-DDL shall evaluate the bidder manufacturing works and offices at the
time ofrefer
The specification does not contain any bill of material. Please give desired Please tender evaluation.
Annexure-1 (Schedule of Items) of the tender document.
2 BOM to enable us to quote precisely as per your requirement.

From a few clauses of technical specifications, it appears that the Process Bus based Solution shall not be applicable for this tender. These CRPs are
protection IED's required by you should be suitable for IEC61850-edition to be considered for conventional substations.
3 2, PRP with SNTP time sync. We understand that you do not require IED's
suitable for Process Bus & precision time protocol (PTP). Also, Merging
units are not required.
Please confirm that LDR at Sr. no. 5 & 6 and ethernet switch at Sr. no. 9 & Scope of remote end LDR also includes 24-Port Ethernet Switch and all necessary
10 of "ANNEXURE-I SCHEDULE OF ITEMS" are meant for remote end for hardware for success integration with existing RTU.
4 66KV/33KV Line. Also please inform the line length for each LDR/Line
panel to enable us to decide the type & qty. of FO cable & evaluate its
cost.
Please confirm the specific requirement viz type & quantity of ports Please consider 16 Copper ports and 8 FO ports for ethernet switch and speed
required for 24 Port ethernet switch (i.e. Fibre/copper, 10/100MBPS or shall be 10/100Mbps.
5 100/1000MBPS/1GB). This is very much required because the price of an
ethernet switch varies to a large extent based on such specific
requirements.
Specification calls for IEC-61850-9-2 requirement for Transformer Process Bus based Solution shall not be applicable for this tender. These CRPs are
6 Monitoring Unit (TMU) which is not commonly used for a TMU to be considered for conventional substations.
application, please confirm what exactly is required.
List of equipment to be mounted on each type of panel viz protective Please refer tender technical specifications for the same.
7 relays, auxiliary relays, trip relays, semaphore, switches, annunciators etc.
& their quantity
Whether the FO cable connecting sending & receiving end LDR is to be Sending and receiving end LDRs shall be connected with TATA Power-DDL
supplied by us if yes then specify the length of cable required. IP/MPLS Network. Supply of FO Cable from LDR to IP/MPLS FMS Unit shall be in
8
bidder’s scope. Bidder needs to consider a max. length of 70m per LDR.
However, it may vary depending upon the site condition.