PMC / OWNER Reply to Pre-bid Queries (SET-2)


NAME OF WORK: SUPPLY, INSTALLATION, TESTING, COMMISSIONING AND OPERATION & MAINTENANCE (O&M) OF COMPACT UNITIZED CONSTRUCTION POWER SUBSTATIONS AND
DISTRIBUTION NETWORK FOR AREA-01, AREA-02 & AREA-03 FOR CAPACITY EXPANSION (TO 9.00 MMTPA) PROJECT OF BARAUNI REFINERY OF INDIAN OIL CORPORATION LIMITED AT BARAUNI,
BIHAR.
BIDDING DOCUMENT NO.: IBCE-6373-C00-PJM-TEN-EPCM-06 Tender ID : 2018_REFHQ_83167_1

REFERENCE OF ENQUIRY DOCUMENT


SL. No BIDDER'S QUERY PMC/ OWNER REPLY
PART/VOL. PAGE NO. CLAUSE NO. SUBJECT
6.6kV Shall be SF6 insulated Compact Switchgear as
Please confirm 6.6kV Shall be SF6 insulated Compact
1 Tender Document -- -- SLD indicated in relevant documents (SLD & specification)
Switchgear or not.
attached in the tender.

Please confirm Loop in / Loop out switch shall be Load Break


Loop in / Loop out switch shall be manual operated Load
2 Tender Document -- -- SLD Switch or not. If yes, whether the same shall me manual or
Break Switch.
motorized.

Compact Switchgear shall be having copper bus bar with 100% Compact Switchgear with Aluminium busbar is available as
3 Tender Document -- -- SLD rated continuous current of 630Amp as per OEM design standard. per some vendor’s design standard. However, Compact
In your SLD, it is shown as Aluminum Bus bar. Please confirm. Switchgear with Copper busbar is also acceptable.

25kA for 1 sec for 6.6kV Switchgear is available as per


STC rating shall be 21kA for 3 Sec in place of 25kA for 1 sec for
4 Tender Document -- -- SLD some vendor's design. Bidder to check with other vendor
6.6kV Switchgear as per OEM’s standard. Please confirm.
and follow Tender requirement.

We are considering VCB module with motorized operation as per Confirmed. Same is also indicated in relevant documents
5 Tender Document -- -- SLD
OEM’s standard. Please confirm. (SLD) attached in the tender.

Bidder to note that applicable standard & loss figures for


Please confirm the IS / IEC reference for Transformer and Transformer are already indicated in clause no. 4.3 of
6 Tender Document -- -- SLD
indicate the Loss figures. “Standard Specification of Construction power Substation”
attached in the tender.

It is very difficult to accommodate 13 Nos LT outgoing Feeders 13 Nos LT outgoing Feeders inside CUS can be
7 Tender Document -- -- SLD inside CUS for most of the OEMs. Request you to consider accommodated as per some vendor's design. Bidder to
separate LT Panel for that. Please confirm. check with other vendor and follow Tender requirement.

For LT panel please confirm if CPRI approved panel builder can


8 Tender Document -- -- SLD Bidder to refer reply mentioned in sr. no.07
be considered. Please confirm.

In 415 V side, most of the OEMs do not provide any CBCT and CBCT and Kwh meter can be accommodated as per some
9 Tender Document -- -- SLD Kwh meter due to space constraint. Hence, requesting you to vendor's design in 415 V MV side. Bidder to check with
waive that requirement. Please confirm. other vendor and follow Tender requirement.

Page 3 of 4
Page 1 of 2
Attachment-1
PMC / OWNER Reply to Pre-bid Queries (SET-2)
NAME OF WORK: SUPPLY, INSTALLATION, TESTING, COMMISSIONING AND OPERATION & MAINTENANCE (O&M) OF COMPACT UNITIZED CONSTRUCTION POWER SUBSTATIONS AND
DISTRIBUTION NETWORK FOR AREA-01, AREA-02 & AREA-03 FOR CAPACITY EXPANSION (TO 9.00 MMTPA) PROJECT OF BARAUNI REFINERY OF INDIAN OIL CORPORATION LIMITED AT BARAUNI,
BIHAR.
BIDDING DOCUMENT NO.: IBCE-6373-C00-PJM-TEN-EPCM-06 Tender ID : 2018_REFHQ_83167_1

REFERENCE OF ENQUIRY DOCUMENT


SL. No BIDDER'S QUERY PMC/ OWNER REPLY
PART/VOL. PAGE NO. CLAUSE NO. SUBJECT
Bidder to note that APFC panel shall be part of CSS
Please confirm whether we need to consider APFC panel inside
compartment as indicated in relevant documents (SLD &
the CUS compartment. Because, for most of the OEMs, it is very
specification) attached in the tender. APFC panel kVAR
10 Tender Document -- -- SLD difficult to consider APFC panel inside the CUS due to space
rating is already indicated SLD. Accordingly, Bidder to
constrain. However, If yes, please confirm the rating of 5 step of
consider rating of 5 step of the capacitor bank. Bidder to
the capacitor bank.
consider step in 25kVAR & 50kVAR combination.
IBCE-6373-C00-ELE-SPC-CON- For most of the OEM, ambient temperature shall be 40deg C. But
Bidder to follow Tender requirement and consider design
11 0001, 508 2 CUS in specification, it is written as 46 deg. C. Please confirm your
temperature 46 deg. C.
Rev-0 acceptance for 40 deg C.
IBCE-6373-C00-ELE-SPC-CON-
STC rating shall be 21kA for 3 Sec instead of 25 KA for 1 sec.
12 0001, 510 4.2 CUS Bidder to refer reply mentioned in sr. no.04
Please confirm.
Rev-0
As per OEM’s standard, IP Class of IP class for transformer
IBCE-6373-C00-ELE-SPC-CON- Transformer compartment with degree of Protection IP 34 is
compartment shall be IP-23. But in your specification, it is written
13 0001, 511 4.3 CUS available as per some vendor's design. Bidder to check with
as Degree of Protection IP 34. Please amend it to IP-23 and
Rev-0 other vendor and follow Tender requirement.
confirm.
Bidder to follow Bid requirement and consider IP class IP 41
As per OEM’s standard, IP class for APFC panel shall be IP4X
IBCE-6373-C00-ELE-SPC-CON- for APFC panel.
instead of IP-41. Please confirm your acceptance for the same.
14 0001, 513 4.5 CUS Bidder to refer reply mentioned in sr. no.10 regarding rating
Also for both the APFC Panels (200 KVAR & 125 KVAR) please
Rev-0 of step.
confirm the ratings of 5 steps of capacitor bank.