1. Inspect cables for physical damage and proper connection in accordance with
single line diagram.
2. Cable connections shall be torque tested to manufacturer's recommended
values or values recommended in P-000.
3. Verify proper terminals and crimping die are used on cable and that crimping
procedure is proper.
4. Verify cable color coding or phasing.
Electrical Tests
Yes No
1. Perform Megger Test on each cable with respect to ground and adjacent
cables. For cables 250 volt and less use 500 volt megger; for cables above 250
volt to 600 volt use 1000 volt megger; for cables above 600 volts and less than
1200 volts use 2500 volt megger.
2. Perform continuity test to insure proper cable connection.