Wind Load Analysis

CE 313

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Height and Exposure Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Height and Exposure Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Height and Exposure Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Height and Exposure Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Height and Exposure Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Height and Exposure Coefficeient, Cz Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Wind Speed, V Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Gust Response Coefficient, Cg Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


External Pressure Coefficient, Cpe Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


External Pressure Coefficient, Cpe Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Structural Importance Coefficient, I Wind Load Analysis

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

3 panel at 24 ft = 72 ft

Q. Determine wind load at each story level along direction A for


an internal frame. The following information are given.

Story 10
Floor Height 10 ft
Zone Dhaka
Exposure A
Structure Standard Occupancy
5 panel at 16 ft = 80 ft

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

2
pz = Cc CI Cpe Cz Cg V

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

2
pz = Cc CI Cpe Cz Cg V

Given data,
Cc = 47.2 ×10−6
CI = 1.0
Cpe = 0.80
V = 210

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

2
pz = Cc CI Cpe Cz Cg V

Given data,
Cc = 47.2 ×10−6
CI = 1.0
Cpe = 0.80
V = 210
pz = (47.2×10−6 )×1.0×0.80×Cz ×Cg ×2102
= 1.665Cz Cg

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

2
pz = Cc CI Cpe Cz Cg V

Given data,
Cc = 47.2 ×10−6
CI = 1.0
Cpe = 0.80
V = 210
pz = (47.2×10−6 )×1.0×0.80×Cz ×Cg ×2102
= 1.665Cz Cg

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

2
pz = Cc CI Cpe Cz Cg V

Given data,
Cc = 47.2 ×10−6
CI = 1.0
Cpe = 0.80
V = 210
pz = (47.2×10−6 )×1.0×0.80×Cz ×Cg ×2102
= 1.665Cz Cg

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

2
pz = Cc CI Cpe Cz Cg V

Given data,
Cc = 47.2 ×10−6
CI = 1.0
Cpe = 0.80
V = 210
pz = (47.2×10−6 )×1.0×0.80×Cz ×Cg ×2102
= 1.665Cz Cg

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

2
pz = Cc CI Cpe Cz Cg V

Given data,
Cc = 47.2 ×10−6
CI = 1.0
Cpe = 0.80
V = 210
pz = (47.2×10−6 )×1.0×0.80×Cz ×Cg ×2102
= 1.665Cz Cg

Sample calculation for Floor 10


2
pz = 1.665×0.849×1.309 = 1.85 kN/m
2 2
A = 24×16/3.28 = 22.3 m
F = 1.85×22.3 = 41.3 kN

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I


Example Wind Load Analysis

2
pz = Cc CI Cpe Cz Cg V

Given data,
Cc = 47.2 ×10−6
CI = 1.0
Cpe = 0.80
V = 210
pz = (47.2×10−6 )×1.0×0.80×Cz ×Cg ×2102
= 1.665Cz Cg

Sample calculation for Floor 10


2
pz = 1.665×0.849×1.309 = 1.85 kN/m
2 2
A = 24×16/3.28 = 22.3 m
F = 1.85×22.3 = 41.3 kN

Khondokar Al Momin Daffodil International University CE 313 Structural Analysis I