CHECK DESIGN AND CALCULATIONS REPORT FOR

EXISTING ARGON TANK FOUNDATION DUE TO NEW


LOAD APPLIED ,REV.01

AHG Abdullah Hashim Industrial Gases &


Equipment Co. Ltd. Dammam 2nd Industrial City
,DAMMAM, SAUDI ARABIA

Perpared by:
Eng'r / Hany Mohammed
Senior structural engineer
17.02.2021
STRUCTURAL DESIGN ANALYSIS REFERANCE
A. DESIGN CRITERIA

1.0 INTRODUCTION

This specifications list the design criteria used while performing calculations for the design check of
ARGON Tank Foundation.
Briefly described herein are the design approach adopted, various codes used,
materials properties, loads and soil properties. This criterion complies with all relevant Intenational
Code and Standards.

1.1 DESIGN APPROACH

Check if the new applied load (New tank = 85 ton) due to increase tank capacity could be suppored
safely with existing raft foundation.

1.2 APPLICABLE CODE AND STANDARDS

ACI 318M-14 American Concrete Institute, Building Code Requirements


for Structural Concrete.
ACI 315 American Concrete Institute, Details and Detailing of
Concrete Reinforcement.
ASCE 7 Minimum Design Loads for Buildings and other Related
Structures.

1.3 MATERIALS

1.3.1 Concrete:
Concrete cylinder compressive strength at 28 days shall be, f'c = 28 Mpa.
for concrete pavement and f'c = 17 Mpa for blinding concrete.
1.3.2 Cement:
Portland cement shall conform to ASTM C150. Sulphate resistant cement Type V shall
be used for concrete pavement.
1.3.3 Reinforcing Steel Bars:
All reinforcing steel bars shall conform to ASTM A615M grade 60 deformed bars
with fy = 414 Mpa.

1.4 DESIGN LOADS


1.4.1 Dead Load

a) Concrete = 24.00 KN/M3


b) Weight of soil = 18.00 KN/M3
c) Weight of old Tank (Full) = 61.00 tons, Po = 610.00 KN By Client
d) Weight of new Tank (Full) = 85.00 tons, PN = 850.00 KN By Client
e) Weight of new Tank (Empty) = 21.00 tons, We = 210.00 KN By Client
STRUCTURAL DESIGN ANALYSIS REFERANCE

1.4.2 Wind Load


qz = 0.613 Kz Kzt Kd V2 ASCE 7-10
Where:
qz = Velocity pressure evaluated at height z as defined in Section 29.3.2
Kz = Velocity pressure exposure coefficient defined in Section 29.3.1 Table 23.3-1
Exposure C
= 0.85 (0 - 4.60) meters high
= 0.94 Upto 7.60 meters high
= 0.98 Upto 9.10 meters high
= 1.04 Upto 12.20 meters high
Kzt = 1.00 - Topographic factor defined in Section 26.8.2 Table 26.6-1
Kd = 0.95 - Wind directional factor defined in Section 26.6
V = Wind velocity = 155 Km/hour (43 M/sec) By Client

1.5 SOIL BEARING CAPACITY


The Net Allowable Soil Bearing Capacity (SBC) as per KAABI Geotechnical Soil
Investigation Report is equal 60 KN/M2 Soil Report
STRUCTURAL DESIGN ANALYSIS REFERANCE
B. CHECK FOUNDATION DIMENSION

DATA: (Povided by Client)


Diameter of Tank, D = 3.00 M
Tank Height, H = 9.00 M
Weight of NEW Tank Full (85 tons) (WF)= 850.00 KN

Existing Footing Size: Width, B = 3.10 M


Length, L = 3.10 M
Thickness, T = 0.60 M

Actual Area, AF = B x L = 9.61 M2

Weight of Footing, W = B x L x T x 24 = 138.40 KN

Calculate Required Area of Footing

A(Approx.) = WF x 1.10 / SBC = 850*1.10/60 = 15.58 m2 < 9.61 m2 Unsafe

Plan
STRUCTURAL DESIGN ANALYSIS REFERANCE
Calculate Wind Load:

LOAD DIAGRAM

Wind Load:
qz = 0.613 Kz Kzt Kd V2
F = qz G Cf Af
Where:
F = Design wind pressure
G = 0.85 - Gust effect factor from Section 26.9
Cf = Force coefficient from Fig. 29.5-1
Af = Projected area normal to wind

Therefore, qz= 0.613 x 1.04 x 1.00 x 0.95 x 432 / 1000 = 1.12 KN/M2

H / D = 4.06
D√qz = 103.92
Cf = 0.90 Figure 29.5-1

Af = 11.58*2.85 = 33 M2

Fx = 1.12 x 0.85 x 0.90 x 11.58*2.85 = 28.28 KN


STRUCTURAL DESIGN ANALYSIS REFERANCE
Check Footing Stability:

Factor of Safety Against Overturning (F.S.O.)

Tank is critical when empty

Righting Moment (R.M)


F.S.O. = ≥ 1.50
Overturning Moment ( O.M)

Calculate Righting Moment, (R.M.): Take Σ of Moment at point A


= WE x L / 2 = 102*3.10/2= 158.00 KN-M
= W x L / 2 = 138.40*3.10/2= 214.52 KN-M
Total R.M. = 372.62 KN-M

Calculate Overturning Moment, (O.M.):


O.M. = Fx (H / 2 + T) = 28.28*6.39 = 180.71 KN-M

F.S.O. = R.M. / O.M. = 2.01 > 1.50 Safe


STRUCTURAL DESIGN ANALYSIS REFERANCE
E. Check Actual Soil Pressure

E.1 Case (1) : Tank Empty


Calculate Eccentricity, e

R.M. - O.M.
X= = 1.21 m
ΣP

L
e= -X = 0.34 m
2
e < L / 6, Therefore the Resultant Force is within the middle third

p(max.)/p(min.) = (ΣP / AF) ± Mc / I


Where:
AF = Area of Footing = L x B = 9.61 M2
M = O.M. = 118.00 KN-M
c = L / 2 = 1.55 M
I = B x L3 / 12 = 7.70 M4

p(max.) = 60.00 KN/M2 = S.B.C. = 60 KN/M2 Safe


STRUCTURAL DESIGN ANALYSIS REFERANCE
E.2 Case (2) : Tank Full
Calculate Eccentricity, e

R.M. = WF x L / 2 = 1317.50 KN-M


W x L / 2 = 214.52 KN-M
Total R.M. = 1532.20 KN-M

R.M. - O.M.
X= = 1.43 m
ΣP

L
e= - X = 0.12 m
2
e < L / 6, Therefore the Resultant Force is within the middle third

p(max.)/p(min.) = ΣP / AF ± Mc / I
Where:
AF = Area of Footing = L x B = 9.61 M2
M = O.M. = 118.00 KN-M
c = L / 2 = 1.55 M
I = B x L3 / 12 = 7.70 M4

p(max.) = 118.17 KN/M2 > S.B.C. = 60 KN/M2 Unsafe

p(max.) is greater than the allowable and even, as per code: If the Vertical Load is
combined with Wind Load, the Allowable Soil Bearing Capacity could be increased by
33 %, Therefore 60 x 1.33 = 79.80 KN/M2 < p(max.). Unsafe

F. 1. Summary Report

No. Test Result


1 CHECK FOUNDATION DIMENSION Unsafe
2 Check Footing Stability: Safe
3 Check Actual Soil Pressure Unsafe

2. Conclusion
1. The existing tank foundation is not capable of carrying extra loads due
to Unsafe soil pressure that could lead to differtial settlement and structure failure.

2.To accept extra load , Soil bearing capacity must be improved by replacing the poor soil with
A-1-a Material and apply compaction Test or increase foundation dimensions .