Perpared by:
Eng'r / Hany Mohammed
Senior structural engineer
17.02.2021
STRUCTURAL DESIGN ANALYSIS REFERANCE
A. DESIGN CRITERIA
1.0 INTRODUCTION
This specifications list the design criteria used while performing calculations for the design check of
ARGON Tank Foundation.
Briefly described herein are the design approach adopted, various codes used,
materials properties, loads and soil properties. This criterion complies with all relevant Intenational
Code and Standards.
Check if the new applied load (New tank = 85 ton) due to increase tank capacity could be suppored
safely with existing raft foundation.
1.3 MATERIALS
1.3.1 Concrete:
Concrete cylinder compressive strength at 28 days shall be, f'c = 28 Mpa.
for concrete pavement and f'c = 17 Mpa for blinding concrete.
1.3.2 Cement:
Portland cement shall conform to ASTM C150. Sulphate resistant cement Type V shall
be used for concrete pavement.
1.3.3 Reinforcing Steel Bars:
All reinforcing steel bars shall conform to ASTM A615M grade 60 deformed bars
with fy = 414 Mpa.
Plan
STRUCTURAL DESIGN ANALYSIS REFERANCE
Calculate Wind Load:
LOAD DIAGRAM
Wind Load:
qz = 0.613 Kz Kzt Kd V2
F = qz G Cf Af
Where:
F = Design wind pressure
G = 0.85 - Gust effect factor from Section 26.9
Cf = Force coefficient from Fig. 29.5-1
Af = Projected area normal to wind
Therefore, qz= 0.613 x 1.04 x 1.00 x 0.95 x 432 / 1000 = 1.12 KN/M2
H / D = 4.06
D√qz = 103.92
Cf = 0.90 Figure 29.5-1
Af = 11.58*2.85 = 33 M2
R.M. - O.M.
X= = 1.21 m
ΣP
L
e= -X = 0.34 m
2
e < L / 6, Therefore the Resultant Force is within the middle third
R.M. - O.M.
X= = 1.43 m
ΣP
L
e= - X = 0.12 m
2
e < L / 6, Therefore the Resultant Force is within the middle third
p(max.)/p(min.) = ΣP / AF ± Mc / I
Where:
AF = Area of Footing = L x B = 9.61 M2
M = O.M. = 118.00 KN-M
c = L / 2 = 1.55 M
I = B x L3 / 12 = 7.70 M4
p(max.) is greater than the allowable and even, as per code: If the Vertical Load is
combined with Wind Load, the Allowable Soil Bearing Capacity could be increased by
33 %, Therefore 60 x 1.33 = 79.80 KN/M2 < p(max.). Unsafe
F. 1. Summary Report
2. Conclusion
1. The existing tank foundation is not capable of carrying extra loads due
to Unsafe soil pressure that could lead to differtial settlement and structure failure.
2.To accept extra load , Soil bearing capacity must be improved by replacing the poor soil with
A-1-a Material and apply compaction Test or increase foundation dimensions .