The wind load\ presure on projected area of cylinderical surfaces = 0.86 KN/m = 18.0 psf
This presure is for wind velocity of 120 mph (190 Km/hr) For all other wind velocities
2
the presure shall be adjusted in proportion of ratio (V/190)
O.D of tank = D 0 = 4.512 m
D = 4.506 m
H = 6.3 m
D/H = 0.71524
Site Class = D
Corroded thickness of bottom plate = 7.00 mm
Corroded thickness of first shell course = 3.00 mm
2 2
Mrw = sqrt[Ai(WiXi+WsXs+WrXr)] + [Ac(WcXc)]
Ai = 2.5 x Q x Fa x So ( I / Rwi )
Wi = (1-0.218x(D/H)) x Wp Eq E-14
Xi = Height from the bottom of the shell to the center of action of the lateral Siesmic force related to impulsive liquid force
Xi = 0.5-0.094(D/H)*H E- 17
Xi = 2.726436 m
Xr = Height from the top of the shell to the roof and roof appurtenances center of gravity
= 0.167 m
Tc = Natural peroid of the convective (sloshing ) mode of behaviour of the liquid, seconds As per E 4.8.2
Tc = 1.8 Ks sqrt (D)
Ks = 0.578
Therefore
Tc = 2.209 ( As per E.4.8.2)
TL = 4 ( As per E.4.9.1)
Therefore
Ac = 0.09508 < Ai
Wc = 161.68607 KN = 161686.1 N
Xc = Height from the bottom of the tank shell to the center of action of lateral siemic force related to convective liquid force
Xc = 5.788 E-18
Wt = 3.74 KN/m
Therefore
J = 0.603
2
ơc = [wt(1+0.4Av)+1.273Mrw/D )1/1000ts]
2 2
= 0.0087 KN/mm = 8.73 N/mm
10.2) Allowable Longitudinal Membrane Compression Stress in Tank Shell As per E.6.2.2.3
2
Calculating value of GHD
2
t
= 3.6
2 2
When GHD / t is less than 44,
Than
Fc = 83ts/(2.5*D)+7.5 sqrt(G*H < Fty)
2
Fc = 40.93 N/mm
= 110 N/mm 2