REV 1
PREPARED BY: PKS
Design department
DATE: 16-Jan-24
1.Wind Analysis
Directionality Factor (Table 6-4, ASCE 7-05) for solid sign),kd = 0.85
ASCE 7-16
Fig30.11-1 Wind on roof
Wind acting upward
Net wind pressure coefficient,GCp = -0.70
Wind Pressure acting upward ,F=qh*G*Cp = -0.70kN/m2
Secondary beam Tributory width = 1.33m
Wind load = -0.928kN/m
Secondary beam Tributory width = 2.64m
Wind load = -1.851kN/m
Secondary beam Tributory width = 2.09m
Wind load = -1.466kN/m
Secondary beam Tributory width = 0.78m
Wind load = -0.544kN/m
Secondary beam Tributory width = 1.80m
Wind load = -1.259kN/m
Secondary beam Tributory width = 1.80m
Wind load = -1.260kN/m
Secondary beam Tributory width = 1.79m
Wind load = -1.250kN/m
Secondary beam Tributory width = 0.89m
Wind load = -0.619kN/m
Wind acting downward
Net wind pressure coefficient,GCp = 0.60
Wind Pressure acting downward ,F=qh*G*Cp = 0.60kN/m2
Secondary beam Tributory width = 1.33m
Wind load = 0.796kN/m
Secondary beam Tributory width = 2.64m
Wind load = 1.586kN/m
Secondary beam Tributory width = 2.09m
Wind load = 1.257kN/m
Secondary beam Tributory width = 0.78m
Wind load = 0.466kN/m
Secondary beam Tributory width = 1.80m
Wind load = 1.079kN/m
Secondary beam Tributory width = 1.80m
Wind load = 1.080kN/m
Secondary beam Tributory width = 1.79m
Wind load = 1.071kN/m
Secondary beam Tributory width = 0.89m
Wind load = 0.531kN/m