Design of Tank
Size of Flush tank = 3.86 x 3.58 x 1.15
L/H = 3.36 B/H = 3.114
L/H and B/H are greater than 2
Hence the walls span in Vertical direction
since the tank is closed one the walls act as proped cantilevers.
Roof Slab
Slab thickness assumed is = 125 mm
clear cover taken as = 20 mm
assumed dia of bar = 8 mm
where effective depth = 101 mm
The panel size is ly = 3.86
lx = 3.58
ly/lx = 1.08
Density of concrete = 25 KN/m3
Load On slab
self weight = 3.125
Floor finish = 1.5
Live Load = 1.5
Total Load on Slab = 6.125 KN/m2 ~ 6.20 KN/m2
Considering the slab as Four edges discontinuous
As per code IS 456
Short span -ve moment -αx= 0.000 Mx = αxwlx2 = 0.000 KN-m
Short span +ve moment +αx= 0.063 Mx = αxwlx 2
= 7.537 KN-m
Long span -ve moment -αy= 0.000 My = αywl x
2
= 0.000 KN-m
Long span +ve moment +αy= 0.056 My = αywl x
2
= 6.680 KN-m
Ast required Ast provided
Ast for Short span -ve moment = 150.0 8 335 c/c 200 c/c
Ast for Short span +ve moment = 177.8 8 283 c/c 200 c/c
Ast for Long span -ve moment = 150.0 8 335 c/c 200 c/c
Ast for Long span +ve moment = 156.9 8 320 c/c 200 c/c
D = 246.00 mm
providing overall thickness = 200 mm
clear cover = 30 mm
dia of bar = 10 mm
effective depth = 165 mm
Ast for Short span -ve moment = M
σst x j x d
Ast = = 0.00 mm2
For providing dia of bar = 12 mm
spacing required = #DIV/0! ~ 100 c/c
provide # 10@ 125 c/c
Ast for Short span +ve moment = M
σst x j x d
Ast = = 983.35 mm2
For providing dia of bar = 12 mm
spacing required = 114.95 ~ 100 c/c
provide # 10@ 150 c/c
Ast for Long span -ve moment = M
σst x j x d
Ast = = 0.00 mm2
For providing dia of bar = 10 mm
spacing required = #DIV/0! ~ 100 c/c
provide # 10@ 150 c/c
Ast for Long span +ve moment = M
σst x j x d
Ast = = 871.49 mm2
For providing dia of bar = 10 mm
spacing required = 90.08 ~ 100 c/c
provide # 10@ 150 c/c
d = 318.24 mm
Provide Overall depth = 550 mm
clear cover = 30 mm
dia of bar = 20 mm
effective depth = 500 mm
Area of steel required shorter span = M
σst x j x d
Ast = = 636.51 mm2
Provide 2-#20 st + 1-#20 ext at top and 2-#20 st + 1-#20 ext at bottom
B2 span = 4.53 m
wall thickness taken as = 0.15 m
height of wall taken as = 1.95 m
thickness of beam = 0.23 m
depth of beam = 0.55 m
d = 441.58 mm
Provide Overall depth = 550 mm
clear cover = 30 mm
dia of bar = 20 mm
effective depth = 500 mm
Area of steel required shorter span = M
σst x j x d
Ast = = 1225.48 mm2
Provide 3-#20st +2-20 ext at top and 3-#20 st +2-#20 ext at bottom