Fire Main Loop Test with Fire
Hydrant
Why..?
To determine if the condition of the system is adequate to support a
Worst Case Credible Event(WCCE) need for firewater.
SP1
RP1
Q1
Shut Valve -1
1 2
Source
Isolate the Legs : Test -2
SP2
RP2
Q2
Shut Valve -2
1 2
Source
Isolate the Legs : Test -3
SP3
RP3
Q3
Both valve opened
1 2
Source
Result
The static pressure should be identical in each of the three tests. A
drop in static pressure in test 1 or 2 is indicative of a restriction and a
leak.
In the event of a 100% restriction, no water will come out of the
hydrant
In the event of a partial restriction, the residual pressure and/or the
flow is significantly diminished.
Further flow testing on different hydrants can usually narrow down
the location of the restriction