Description of spreadsheet CO2 CALCULATIONS

REVISIONS

Date Made by Description

523296793.xls : Cover Page 1 of 21 Printed 05/10/2021 Time 01:08:52


Notes

Description Dimensions (m) Design No. of Discharge


W L H Concentration Outlet
H.V Switch room 4.5 4.5 3.7 50 2
L.V Switch room 9.0 4.5 3.7 50 4
Room A (Stesen Suis Utama) 3.0 4.6 3.2 50 2
Room B (Stesen Suis Utama) 4.6 4.6 3.2 50 2
Room C (Stesen Suis Utama) 6.1 10.6 3.2 50 6
Stesen Suis Utama (Revised-Room
A+Room B) 7.4 4.6 3.2 50 4

Page 2
Notes

Orifice Equiv S.O. Diam Equiv S.O. Area


Code No. inches mm2
1 1/32 0.49
1.5 3/64 1.11

2 1/16 1.98
2.5 5/64 3.09
3 3/32 4.45
3.5 7/64 6.06
4 1/8 7.94
4.5 9/64 10.00
5 5/32 12.39
5.5 11/64 14.97
6 3/16 17.81
6.5 13/64 20.90
7 7/32 24.26
7.5 15/64 27.81
8 1/4 31.68
8.5 17/64 35.74
9 9/32 40.06
9.5 19/64 44.65
10 5/16 49.48
11 11/32 59.87
12 3/8 71.29
13 13/32 83.61
14 7/16 96.97
15 15/32 111.29
16 1/2 126.71
18 9/16 160.32
20 5/8 197.94
22 11/16 239.48
24 3/4 285.03
32 1 506.45
48 1.5 1138.71
64 2 2025.80

Page 3
Job No. Sheet No. Rev.

Member/Location

Job Title Drg. Ref.


CO2 CALCULATIONS
Made by Date Chd.

The CO2 Total Flooding System for this project is designed based on NFPA 12 - Standard on Carbon Dioxide
Extinguishing Systems; 1989 Edition. All items in "[ ]" within these sheets are references from this standard.

AREA : H.V Switch room

a: CO2 Capacity

Volume = 4.5 m x 4.5 m x 3.66 m (H)


= 74.12 m3

Based on values from [Table 2-4.2.1] for Dry Electrical Hazards,

Design Concentration = 50 %

Flooding (Volume) Factor = 1.6 kg CO2 / m3

Material Conversion Factor = N/A

Basic Capacity of CO2 Required = 74.12 m3 x 1.6 kg CO2 / m3


= 118.58 kg

Safety Factor = 10 %

Total Capacity of CO2 = 130.44 kg

Capacity of each CO2 Cylinder = 45 kg

Quantity of CO2 Cylinders Required = 3 nos.

Total Capacity of CO2 Allowed = 135 kg


b: Pipe Sizing

Valve discharge outlet size , do = 12.7 mm dia.

Therefore;
Area of valve outlet, p x do2/4 = 127 mm2

Total area of 3 nos. of discharge outlets


= 127 mm2 x 3
= 381 mm2

Area of header , p x D2/4 = Total area of 3 nos. of discharge outlets


= 381 mm2

D = 22.03 mm

Therefore,
Diameter of header = 25 mm Sch. 80 pipe.

The CO2 gas is discharged through 2 nos. of nozzles,


thus the range pipes are estimated as follows :

Total area of gas discharge nozzle = 381 mm2


Area of each gas discharge nozzle = 381 mm2 / 2
= 190.5 mm2

Hence,
p x dn2/4 = 190.5 mm2
dn = 15.57 mm

Therefore,
Diameter of the range pi = 19 mm Sch. 40 pipe.
c: Nozzle Orifice Size

Based on values from [Table 1-9.4.4(c)], for Cylinder Pressure of 725 psia at 20oC,
Discharge Rate per square inch of Equivalent Orifice Area = 2.706 kg / min / mm2

Quantity of CO2 = 135 kg

Since the Design Concentration for Dry Electrical Hazards is always 50 % (Refer [Table 2-4.2.1]),
the Rate of Application required to achieve 30 % Design Concentration in 2 minutes is always
higher than achieving 50 % in 7 minutes - Refer Note [2-5.2.3].

Therefore,
Rate of Application = 30% x 135 kg / 2 minutes
= 20.25 kg / min

Equivalent Orifice Area = 20.25 kg/min / 2.706 kg/min/mm2


= 7.48 mm2

Since there are 2 nos. of nozzle provided,

Equivalent Single Orifice Area = 7.48 mm2 / 2


= 3.74 mm2

Closest standard equivalent single orifice area = 4.45 mm2

Hence, Discharge Nozzle information derived from [Table 1-9.4.4(a)] as follows :

No. of Discharge Nozzles = 2

Orifice Code No. = 3

Equivalent Single Orifice Diameter = 3/32 inches

Actual Time for CO2 Discharge = 5.61 minutes


Job No. Sheet No. Rev.

Member/Location

Job Title Drg. Ref.

CO2 CALCULATIONS
Made by Date Chd.

The CO2 Total Flooding System for this project is designed based on NFPA 12 - Standard on Carbon Dioxide
Extinguishing Systems; 1989 Edition. All items in "[ ]" within these sheets are references from this standard.

AREA : L.V Switch room

a: CO2 Capacity

Volume = 9 m x 4.5 m x 3.66 m (H)


= 148.23 m3

Based on values from [Table 2-4.2.1] for Dry Electrical Hazards,

Design Concentration = 50 %

Flooding (Volume) Factor = 1.6 kg CO2 / m3

Material Conversion Factor = N/A

Basic Capacity of CO2 Required = 148.23 m3 x 1.6 kg CO2 / m3


= 237.17 kg

Safety Factor = 10 %

Total Capacity of CO2 = 260.88 kg

Capacity of each CO2 Cylinder = 45 kg

Quantity of CO2 Cylinders Required = 6 nos.

Total Capacity of CO2 Allowed = 270 kg

523296793.xls : L.V Page 1 of 21 Printed 05/10/2021 Time 01:08:52


Job No. Sheet No. Rev.

Member/Location

Job Title Drg. Ref.

CO2 CALCULATIONS
Made by Date Chd.

b: Pipe Sizing

Valve discharge outlet size , do = 12.7 mm dia.

Therefore;
Area of valve outlet, p x do2/4 = 127 mm2

Total area of 6 nos. of discharge outlets


= 127 mm2 x 6
= 762 mm2

Area of header , p x D2/4 = Total area of 6 nos. of discharge outlets


= 762 mm2

D = 31.15 mm

Therefore,
Diameter of header = 32 mm Sch. 80 pipe.

The CO2 gas is discharged through 4 nos. of nozzles,


thus the range pipes are estimated as follows :

Total area of gas discharge nozzle = 762 mm2


Area of each gas discharge nozzle = 762 mm2 / 4
= 190.5 mm2

Hence,
p x dn2/4 = 190.5 mm2
dn = 15.57 mm

Therefore,
Diameter of the range = 19 mm Sch. 40 pipe.

523296793.xls : L.V Page 2 of 21 Printed 05/10/2021 Time 01:08:52


Job No. Sheet No. Rev.

Member/Location

Job Title Drg. Ref.

CO2 CALCULATIONS
Made by Date Chd.

c: Nozzle Orifice Size

Based on values from [Table 1-9.4.4(c)], for Cylinder Pressure of 725 psia at 20oC,
Discharge Rate per square inch of Equivalent Orifice Area = 2.706 kg / min / mm2

Quantity of CO2 = 270 kg

Since the Design Concentration for Dry Electrical Hazards is always 50 % (Refer [Table 2-4.2.1]),
the Rate of Application required to achieve 30 % Design Concentration in 2 minutes is always
higher than achieving 50 % in 7 minutes - Refer Note [2-5.2.3].

Therefore,
Rate of Application = 30% x 270 kg / 2 minutes
= 40.5 kg / min

Equivalent Orifice Area = 40.5 kg/min / 2.706 kg/min/mm2


= 14.97 mm2

Since there are 4 nos. of nozzle provided,

Equivalent Single Orifice Area = 14.97 mm2 / 4


= 3.74 mm2

Closest standard equivalent single orifice area = 4.45 mm2

Hence, Discharge Nozzle information derived from [Table 1-9.4.4(a)] as follows :

No. of Discharge Nozzles = 4

Orifice Code No. = 3

Equivalent Single Orifice Diameter = 3/32 inches

Actual Time for CO2 Discharge = 5.61 minutes

523296793.xls : L.V Page 3 of 21 Printed 05/10/2021 Time 01:08:52


a(SSU)

Job No. Sheet No. Rev.

Member/Location

Job Title Drg. Ref.


CO2 CALCULATIONS
Made by Date Chd.

The CO2 Total Flooding System for this project is designed based on NFPA 12 - Standard on Carbon Dioxide
Extinguishing Systems; 1989 Edition. All items in "[ ]" within these sheets are references from this standard.

AREA : Room A (Stesen Suis Utama)

a: CO2 Capacity

Volume = 3 m x 4.6 m x 3.2 m (H)


= 44.16 m3

Based on values from [Table 2-4.2.1] for Dry Electrical Hazards,

Design Concentration = 50 %

Flooding (Volume) Factor = 1.6 kg CO2 / m3

Material Conversion Factor = N/A

Basic Capacity of CO2 Required = 44.16 m3 x 1.6 kg CO2 / m3


= 70.66 kg

Safety Factor = 10 %

Total Capacity of CO2 = 77.72 kg

Capacity of each CO2 Cylinder = 45 kg

Quantity of CO2 Cylinders Required = 2 nos.

Total Capacity of CO2 Allowed = 90 kg

Page 4
a(SSU)

b: Pipe Sizing

Valve discharge outlet size , do = 12.7 mm dia.

Therefore;
Area of valve outlet, p x do2/4 = 127 mm2

Total area of 2 nos. of discharge outlets


= 127 mm2 x 2
= 254 mm2

Area of header , p x D2/4 = Total area of 2 nos. of discharge outlets


= 254 mm2
D = 17.98 mm

Therefore,
Diameter of header = 19 mm Sch. 40 pipe.

The CO2 gas is discharged through 2 nos. of nozzles,


thus the range pipes are estimated as follows :

Total area of gas discharge nozzle = 254 mm2


Area of each gas discharge nozzle = 254 mm2 / 2
= 127.0 mm2

Hence,
p x dn2/4 = 127.0 mm2
dn = 12.72 mm

Therefore,
Diameter of the range = 13 mm Sch. 40 pipe.

Page 5
a(SSU)

c: Nozzle Orifice Size

Based on values from [Table 1-9.4.4(c)], for Cylinder Pressure of 725 psia at 20oC,
Discharge Rate per square inch of Equivalent Orifice Area = 2.706 kg / min / mm2

Quantity of CO2 = 90 kg

Since the Design Concentration for Dry Electrical Hazards is always 50 % (Refer [Table 2-4.2.1]),
the Rate of Application required to achieve 30 % Design Concentration in 2 minutes is always
higher than achieving 50 % in 7 minutes - Refer Note [2-5.2.3].

Therefore,
Rate of Application = 30% x 90 kg / 2 minutes
= 13.5 kg / min

Equivalent Orifice Area = 13.5 kg/min / 2.706 kg/min/mm2


= 4.99 mm2

Since there are 2 nos. of nozzle provided,

Equivalent Single Orifice Area = 4.99 mm2 / 2


= 2.49 mm2

Closest standard equivalent single orifice area = 3.09 mm2

Hence, Discharge Nozzle information derived from [Table 1-9.4.4(a)] as follows :

No. of Discharge Nozzles = 2

Orifice Code No. = 2.5

Equivalent Single Orifice Diameter = 5/64 inches

Actual Time for CO2 Discharge = 5.38 minutes

Page 6
Job No. Sheet No. Rev.

Member/Location

Job Title Drg. Ref.


CO2 CALCULATIONS
Made by Date Chd.

The CO2 Total Flooding System for this project is designed based on NFPA 12 - Standard on Carbon Dioxide
Extinguishing Systems; 1989 Edition. All items in "[ ]" within these sheets are references from this standard.

AREA : Room B (Stesen Suis Utama)

a: CO2 Capacity

Volume = 4.6 m x 4.6 m x 3.2 m (H)


= 67.71 m3

Based on values from [Table 2-4.2.1] for Dry Electrical Hazards,

Design Concentration = 50 %

Flooding (Volume) Factor = 1.6 kg CO2 / m3

Material Conversion Factor = N/A

Basic Capacity of CO2 Required = 67.71 m3 x 1.6 kg CO2 / m3


= 108.34 kg

Safety Factor = 10 %

Total Capacity of CO2 = 119.17 kg

Capacity of each CO2 Cylinder = 45 kg

Quantity of CO2 Cylinders Required = 3 nos.

Total Capacity of CO2 Allowed = 135 kg


b: Pipe Sizing

Valve discharge outlet size , do = 12.7 mm dia.

Therefore;
Area of valve outlet, p x do2/4 = 127 mm2

Total area of 3 nos. of discharge outlets


= 127 mm2 x 3
= 381 mm2

Area of header , p x D2/4 = Total area of 3 nos. of discharge outlets


= 381 mm2
D = 22.03 mm

Therefore,
Diameter of header = 25 mm Sch. 80 pipe.

The CO2 gas is discharged through 2 nos. of nozzles,


thus the range pipes are estimated as follows :

Total area of gas discharge nozzle = 381 mm2


Area of each gas discharge nozzle = 381 mm2 / 2
= 190.5 mm2

Hence,
p x dn2/4 = 190.5 mm2
dn = 15.57 mm

Therefore,
Diameter of the range = 19 mm Sch. 40 pipe.
c: Nozzle Orifice Size

Based on values from [Table 1-9.4.4(c)], for Cylinder Pressure of 725 psia at 20oC,
Discharge Rate per square inch of Equivalent Orifice Area = 2.706 kg / min / mm2

Quantity of CO2 = 135 kg

Since the Design Concentration for Dry Electrical Hazards is always 50 % (Refer [Table 2-4.2.1]),
the Rate of Application required to achieve 30 % Design Concentration in 2 minutes is always
higher than achieving 50 % in 7 minutes - Refer Note [2-5.2.3].

Therefore,
Rate of Application = 30% x 135 kg / 2 minutes
= 20.25 kg / min

Equivalent Orifice Area = 20.25 kg/min / 2.706 kg/min/mm2


= 7.48 mm2

Since there are 2 nos. of nozzle provided,

Equivalent Single Orifice Area = 7.48 mm2 / 2


= 3.74 mm2

Closest standard equivalent single orifice area = 4.45 mm2

Hence, Discharge Nozzle information derived from [Table 1-9.4.4(a)] as follows :

No. of Discharge Nozzles = 2

Orifice Code No. = 3

Equivalent Single Orifice Diameter = 3/32 inches

Actual Time for CO2 Discharge = 5.61 minutes


Job No. Sheet No. Rev.

Member/Location

Job Title Drg. Ref.


CO2 CALCULATIONS
Made by Date Chd.

The Clean Agent Total Flooding System for this project is designed based on NFPA 2001 -Class A&C for Clean Agent

AREA : Switch Gear Room

a: Clean Agent Capacity

Volume = 4.62 m x 3.5 m x 5.72 m (H)


= 92.49 m3

Based on values from [Table 2-4.2.1] for Dry Electrical Hazards,

Design Concentration = #N/A %

Flooding (Volume) Factor = #N/A kg CO2 / m3

Material Conversion Factor = N/A

Basic Capacity of CO2 Required = 92.49 m3 x #N/A kg CO2 / m3


= #N/A kg

Safety Factor = 10 %

Total Capacity of CO2 = #N/A kg

Capacity of each CO2 Cylinder = 45 kg

Quantity of CO2 Cylinders Required = #N/A nos.

Total Capacity of CO2 Allowed = #N/A kg


b: Pipe Sizing

Valve discharge outlet size , do = 12.7 mm dia.

Therefore;
Area of valve outlet, p x do2/4 = 127 mm2

Total area of ###nos. of discharge outlets


= 127 mm2 x #N/A
= #N/A mm2

Area of header , p x D2/4 = Total area of #N/A nos. of discharge outlets


= #N/A mm2
D = #N/A mm

Therefore,
Diameter of header = #N/A mm Sch. #N/A pipe.

The CO2 gas is discharged through #N/A nos. of nozzles,


thus the range pipes are estimated as follows :

Total area of gas discharge nozzle = #N/A mm2


Area of each gas discharge nozzle = #N/A mm2 / #N/A
= #N/A mm2

Hence,
p x dn2/4 = #N/A mm2
dn = #N/A mm

Therefore,
Diameter of the range = #N/A mm Sch. #N/A pipe.
c: Nozzle Orifice Size

Based on values from [Table 1-9.4.4(c)], for Cylinder Pressure of 725 psia at 20oC,
Discharge Rate per square inch of Equivalent Orifice Area = 2.706 kg / min / mm2

Quantity of CO2 = #N/A kg

Since the Design Concentration for Dry Electrical Hazards is always 50 % (Refer [Table 2-4.2.1]),
the Rate of Application required to achieve 30 % Design Concentration in 2 minutes is always
higher than achieving 50 % in 7 minutes - Refer Note [2-5.2.3].

Therefore,
Rate of Application = 30% x #N/A kg / 2 minutes
= #N/A kg / min

Equivalent Orifice Area = #N/A kg/min / 2.706 kg/min/mm2


= #N/A mm2

Since there are 2 nos. of nozzle provided,

Equivalent Single Orifice Area = #N/A mm2 / 2


= #N/A mm2

Closest standard equivalent single orifice area = #N/A mm2

Hence, Discharge Nozzle information derived from [Table 1-9.4.4(a)] as follows :

No. of Discharge Nozzles = 2

Orifice Code No. = #N/A

Equivalent Single Orifice Diameter = #N/A inches

Actual Time for CO2 Discharge = #N/A minutes


Job No. Sheet No. Rev.

Member/Location

Job Title Drg. Ref.


CO2 CALCULATIONS
Made by Date Chd.

The CO2 Total Flooding System for this project is designed based on NFPA 12 - Standard on Carbon Dioxide
Extinguishing Systems; 1989 Edition. All items in "[ ]" within these sheets are references from this standard.

AREA : Stesen Suis Utama (Revised-Room A+Room B)

a: CO2 Capacity

Volume = 7.67 m x 5.72 m x 3 m (H)


= 131.62 m3

Based on values from [Table 2-4.2.1] for Dry Electrical Hazards,

Design Concentration = 50 %

Flooding (Volume) Factor = 1.6 kg CO2 / m3

Material Conversion Factor = N/A

Basic Capacity of CO2 Required = 131.62 m3 x 1.6 kg CO2 / m3


= 210.59 kg

Safety Factor = 10 %

Total Capacity of CO2 = 231.65 kg

Capacity of each CO2 Cylinder = 45 kg

Quantity of CO2 Cylinders Required = 6 nos.

Total Capacity of CO2 Allowed = 270 kg


b: Pipe Sizing

Valve discharge outlet size , do = 12.7 mm dia.

Therefore;
Area of valve outlet, p x do2/4 = 127 mm2

Total area of 6 nos. of discharge outlets


= 127 mm2 x 6
= 762 mm2

Area of header , p x D2/4 = Total area of 6 nos. of discharge outlets


= 762 mm2
D = 31.15 mm

Therefore,
Diameter of header = 32 mm Sch. 80 pipe.

The CO2 gas is discharged through 4 nos. of nozzles,


thus the range pipes are estimated as follows :

Total area of gas discharge nozzle = 762 mm2


Area of each gas discharge nozzle = 762 mm2 / 4
= 190.5 mm2

Hence,
p x dn2/4 = 190.5 mm2
dn = 15.57 mm

Therefore,
Diameter of the range = 19 mm Sch. 40 pipe.
c: Nozzle Orifice Size

Based on values from [Table 1-9.4.4(c)], for Cylinder Pressure of 725 psia at 20oC,
Discharge Rate per square inch of Equivalent Orifice Area = 2.706 kg / min / mm2

Quantity of CO2 = 270 kg

Since the Design Concentration for Dry Electrical Hazards is always 50 % (Refer [Table 2-4.2.1]),
the Rate of Application required to achieve 30 % Design Concentration in 2 minutes is always
higher than achieving 50 % in 7 minutes - Refer Note [2-5.2.3].

Therefore,
Rate of Application = 30% x 270 kg / 2 minutes
= 40.5 kg / min

Equivalent Orifice Area = 40.5 kg/min / 2.706 kg/min/mm2


= 14.97 mm2

Since there are 6 nos. of nozzle provided,

Equivalent Single Orifice Area = 14.97 mm2 / 6


= 2.49 mm2

Closest standard equivalent single orifice area = 3.09 mm2

Hence, Discharge Nozzle information derived from [Table 1-9.4.4(a)] as follows :

No. of Discharge Nozzles = 6

Orifice Code No. = 2.5

Equivalent Single Orifice Diameter = 5/64 inches

Actual Time for CO2 Discharge = 5.38 minutes