You are on page 1of 1

B

CHECK ALL DIMENSIONS ON SITE PRIOR TO CONSTRUCTION. DO NOT SCALE


FROM DRAWING. REPORT ANY DISCREPANCIES. IF IN DOUBT ASK.
3000 3000 COPING BEAM COPYRIGHT AND AUTHORITY FOR ANY REPRODUCTION OF DESIGN SHOWN
R6-125 HERE IS RETAINED. DO NOT KEEP SUPERSEDED DRAWINGS ON SITE.

1. FOR GENERAL NOTES REFER DRAWING NO CEB-PKG1-M-71-ST02


2T10
200 2. FOR TYPICAL DETAILS REFER DRAWINGS NOS ST03,ST04, ST05.

200
3. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECTURAL AND ENGINEERING DRAWINGS AND
2T10 SPECIFICATIONS.

4. NO CONCRETE IS TO BE POURED UNTIL THE REINFORCEMENT


HAS BEEN INSPECTED AND APPROVED BY THE ENGINEER.
200
5. CONCRETE GRADE
BLOCK WALL
TIE BEAMS - C25
2928 2982 3000 COLUMN R/F DETAIL A-A STIFFENER COLUMNS
FIRE WALL
- C25

3074

2775
BELOW GROUND LEVEL - C35A
ABOVE GROUND LEVEL - C30
5
285

21 FOUNDATIONS - C25
63
6. WATER PROOFING AS SPECIFIED TO BE APPLIED ON ALL WATER
RETAINING AND EXCLUDING SURFACES.
2982

7. ALL DIMENSIONS ARE GIVEN IN MILLIMETERS.

334
A

4
8. IF CONTRACTOR IS PLANNING TO CARRY OUT CONCRETE
POURING EXTENDING BEYOND 12 HOURS THE SETTING TIME OF
R6-125 CONCRETE SHALL BE MORE THAN 5 HOURS.
E
-

9. UNLESS OTHERWISE INDICATED MINIMUM LAP IN


REINFORCEMENT TO BE 52 X SMALLER BAR DIAMETER AND
3000

-0.025m

303 1

150
ANCHORAGE LENGTH TO BE 52 X SMALLER BAR DIAMETER.
2T10
10. ALL MASONRY WORKS EXCEPT PLASTERING SHALL BE DONE
WITH 1:5 CEMENT/SAND MORTAR.
160
150 11. COVER TO REINFORCEMENT

2725
· TIE BEAM
3000

TOP COVER = 25mm


BOTTOM COVER = 25mm
SIDES = 25mm
B CABLE TRENCH OR AUX. TR CON. WALL COPING BEAM R/F DETAIL · RETAINING WALL
BOTTOM COVER = 50mm
SIDES = 50mm
· STIFFENER COLUMN
3000

SIDES = 25mm
TOP = 40mm
· COPING BEAM SIDES = 25mm
B1
ABBREVIATIONS
· COL. = COLUMN
3000

· R.C. = REINFORCED CONCRETE


C ·
·
TK
EL
=
=
THICKNESS
ELEVATION
COPING BEAM · Ø = DIAMETER
· ℄ = CENTER LINE
-2.350m · C/C = CENTER TO CENTER
· APS = AS PER SPECIFICATION
C1
3000

· C/C = CENTER TO CENTER


· F.G.L = FINISHED GROUND LEVEL

150
· E.G.L = EXISTING GROUND LEVEL

160
3000

· P.R.L = PROPOSED ROAD LEVEL


· SC = STIFFENER COLUMN
D
3000

150
3000

SPECIFICATION FOR LATERITICT GRAVEL TO BE


D1 150 TK WALL
USED AS BACK FILL MATERIAL.
3000

1974

SIEVE SIZE % PASSING


50mm THICK GRADE 15 SCREED CONCRETE
E 75mm 100
37.5mm 85-100
COPING DETAIL
FRONT ELEVATION (MASONRY WALL)
10mm
5mm
40-70
25-45
600μm 8-22
75μm 5-22

B
LL PI MDD CBR
COPING BEAM (%) (%) (kg/m ) (%)
<40 <15 >1600 8-20
REFER COPING
R/F DETAIL
LL - LIQUID LIMIT
PI - PLASTIC INDEX
MDD - MAXIMUM DRY DENSITY FROM PROCTOR TEST
CBR - CALIFORNIA BEARING RATIO
ANGLE OF INTERNAL FRICTION (Ø) = 25°
COHESION (C) = 10kN/m2
2775

150 TK WALL
A A

R6-150C/C
2000

125mm Tk PRECAST
CONCRETE COVER SLAB
2000

-0.025m
200
TYPE - 2C

550
03 01 REVISED AS PER SITE CONDITION 03.05.2018
3000

02 01 REVISED WALL DIMENSION 22.11.2017 LAL SM


01 01 REVISED WALL NOTATION 06.11.2017 LAL SM
00
INDEX SHEET REVISION DATE DRAWN CHECKED APPROVED
300
1525
3000

PROJECT ARCHITECT :
2325

DAMITH PERERA
CHARTERED ARCHITECT
150Ø peporated type1000 UPVC -1.550m
pipe covered with geotextile layer
(the water to be collected and
3000

CEYLON ELECTRICITY BOARD


250

discharged to stormwater drain)


SRI LANKA
600
PROJECT : GREATER COLOMBO TRANSMISSION & DISTRIBUTION
E.G.L.(-2.350m) E.G.L LOSS REDUCTION PROJECT (GCT&DLRP)
CONTRACT No. : GEB/GCTDLRP/PACKAGE-1(Lot-1)/02
2789

COMPACTED ENGINEER : JV OF   LOAN No. :


1925

BACK FILL
TOKYO ELECTRIC POWER SERVICES CO., LTD.
SL - P 107 JICA of JAPAN
ELECTRIC POWER DEVELOPMENT CO., LTD.
NIPPON KOEI CO., LTD.
1258
1591

3100

a CONTRACTOR : 

2601 2687 2827 HYOSUNG CORPORATION


a
300

SUB CONTRACTOR :

DP/CEBK/SP/126 (SIERRA CONSTRUCTION (PVT) LIMITED,NO.23 HAVELOCK ROAD,COLOMBO 05,


SRI LANKA)

KEY PLAN
2500
SUBSTATION :
132/11kV PORT/COLOMBO M GRID SUBSTATION

- SCALE- 1:200
-
-
BLOCK WALL (SECTION B-B)
TYPE - 2C (Scale: 1:20)
-
-
STIFFINER COLUMN R/F (SECTION B-B)
TYPE - 2C (Scale: 1:20)
DRAWING TITLE :

DATE : 03.05.2018

SUPPLIER / SUB CONTRACTOR : 

HYOSUNG
DRAWING No : 
BOUNDARY WALL DETAILS

CEB-PKG1-M-77-DR01
Scale :

Sheet
As Given

1
A2
of 1

You might also like