90 cm

SIZE AS SHOWN ON PLAN


PIPE EXPANSION JOINT SITE LOCATION

240
(WHERE NEEDED AT STRUCTURAL DTVC LOT-240 H
KKA
PCRC BUILDING MA
EXPANSION JOINT)
SIZE AS SHOWN ON PLAN
90 cm
PIPE EXPANSION JOINT
(WHERE NEEDED AT STRUCTURAL
EXPANSION JOINT)
FIRE EXTINGUISHER 10 LBS CO2 NOTES:
FIRE EXTINGUISHER 10 LBS DRY CHEMICAL
• FOR FIREFIGHTING LIST OF DRAWINGS, REFER TO GENERAL

30 cm
65 mm DRAWING CONTROL LOG No. GN001.
FIRE EXTINGUISHER 10 LBS CO2
FIRE EXTINGUISHER 10 LBS DRY CHEMICAL
30 cm

MOVABLE PLASTER BOARD Ø25 FROM SPRINKLER SYSTEM


TOP VIEW DOOR (AS DETAILED ON ARCH DWGS)

DOOR (AS DETAILED ON ARCH DWGS) 4 8


TOP VIEW 900 mm
Ø25 UNION
ø50 DRAIN RISER
SUPPLY PIPE 65 mm ø150 WET RISER
PRESSURE GAUGE

∅65 HOSE CONNECTION


MONITORED OS & Y GATE VALVE
WITH TAMPER SWITCH (TYP.)
SWINGING TYPE HOSE REEL
Ø25 INSPECTOR VALVE CHECK VALVE

1 40 mm FLOW SWITCH
1 1/2" X 100 FT LONG 1 UPPER COMPARTMENT CONSISTS OF 40 mm x 30 m HOSE REEL US LISTED 3 NEU

300 PSIC
ON C
OFF
SHUT-OFF VALVE
LOWER COMPARTMENT CONSISTS OF 65 mm x 30 m HOSE
120 cm

1 1/2" NOZZLE APPROVED


TO SPRINKLER
2 REEL, FIRE EXTINGUISHER AND LANDING VALVE SYSTEM
UNION CHECK VALVE
3 65 mm FIRE DEPARTMENT
3 40 mm x 30 m HOSE REEL WITH AUTOMATIC STOP VALVE
1 1/2" GATE VALVE CONNECTIONS
AND SPRAY JET SHUT OFF NOZZLE ø50 SHUT OFF VALVE

18" TO 48"
1700 mm
FIRE EXTINGUISHER 10 LBS CO2 4 40 mm ANGLE VALVE
FIRE EXTINGUISHER 10 LBS DRY CHEMICAL SIGHT
5 10 LBS ABC DRY CHEMICAL POWDER FIRE EXTINGUISHER
6 65 mm x 30 m SYNTHETIC FIRE HOSE WITH NOZZLE
FHC
7 65 mm LANDING VALVE WITH BUILT IN PRV FINISH LEVEL
DRAIN AND
10cm CONCRETE SLAB (TYPICAL) TEST VALVE
2 8 40 mm PRV AND PRESSURE GAUGES ACROSS PRV
7
9 10 LBS CO2 FIRE EXTINGUISHER
∅100 UG HDPE PIPE
LEGENDS:
SIGHT GLASS
90cm

* HOSE CONNECTIONS SHALL BE LOCATED NOT


FINISHED FLOOR LEVEL
CO 2
LESS THAN 0.9 m OR MORE THAN 1.5 m Ø25 UNION WITH CORROSION RESISTANT
A BC
ABOVE FLOOR. ORIFICE PLATE GIVING FLOW EQUIVALENT
5 6 TO THE SMALLEST SPRINKLER ORIFICE IN
9 THE SYSTEM
FRONT VIEW
FIRE HOSE CABINET DETAIL

0.4m
(HOSE REEL SYSTEM) NOTE: THE TEST VALVE SHOULD BE LOCATED AT AN ACCESSIBLE
POINT AND SHOULD NOT BE OVER 2.1M ABOVE THE FLOOR. THE
FLOOR LEVEL DISCHARGE SHOULD BE AT A POINT WHERE IT CAN BE READILY
OBSERVED.

FRONT VIEW

FIRE HOSE CABINET CLASS (II) DETAIL FIRE HOSE CABINET CLASS (III) DETAIL FIRE DEPARTMENT CONNECTION INSPECTOR TEST VALVE DETAIL ZONE CONTROL VALVE ASSEMBLY
1 NTS
2 NTS
3 NTS 4 NTS
5 NTS

STANDPIPE RISER

Ø65 LANDING VALVE

CEILING (SLAB)

MIN. 25 mm & MAX. 300 mm


ORIFICE PLATE WITH HOLE DIAMETER TO CONCRETE SLAB ø10 ANCHOR BOLT
REDUCE OPERATING PRESSURE TO 100 PSI

PIPE SUPPORT
90cm.

Nominal 'L' Bolt Size Design Load

150 mm
100 TO
Pipe Size
PIPE
Bolt Size CLAMP
in (mm) in (mm) Lbs. (KN) BRANCH LINE
1" (25) 9 9/16" (242.9) 3/8"-16x1 1/4" 255 (1.13) HORIZONTAL SIDEWALL SPRINKLER HEAD
SPRINKLER
CHROME PLATED (32) (1.13) ø10 THREADED ROD ø25
1 1/4" 10" (254.0 3/8"-16x1 1/2" 255
ESCUTCHEN ø25 25X15mm REDUCING COUPLING
1 1/2" (40) 10 5/16" (261.9) 3/8"-16x1 1/2" 255 (1.13) ESCUTCHEON
SPRINKLER HEAD ø25 x ø15 REDUCER
2" (50) 10 3/4" (273.0) 3/8"-16x1 1/2" 255 (1.13)
FFL FINISHED CEILING LINE ø25 x ø15 REDUCER
(1.73) MAIN PIPE
2 1/2" (65) 11 1/4" (285.7) 3/8"-16x1 1/2" 390
BRANCH LINE
'L'. 3" (80) 11 15/16" (303.2) 3/8"-16x1 1/2" 530 (2.35)
PENDENT SPRINKLER COVER PLATE PENDENT
3 1/2" (90) 12 3/8" (314.3) 1/2"-13x1 3/4" 670 (2.98) SPRINKLER
4" (100) 12 7/8" (327.0) 1/2"-13x1 3/4" 810 (3.60) WALL
5" (125) 14" (355.6) 1/2"-13x2" 1160 (5.16)
6" (150) 15 1/16" (382.6) 1/2"-13x2" 1570 (6.98)
8" (200) 17 1/4" (438.2) 5/8"-11x2 1/2" 2500 (11.12)
10" (250) 19 7/16" (493.7) 5/8"-11x2 1/2" 2500 (11.12)
12" (300) 20 11/16" (550.9) 5/8"-11x3" 2700 (12.01)

GS PIPE SLEEVE
FIRE RATED FILL MATERIAL
GROOVED FLEXIBLE JOINT

TYPICAL INSTALLATION HORIZONTAL TYPICAL INSTALLATION UPRIGHT SPRINKLERS


6
LANDING VALVE DETAIL
NTS
7 RISER CLAMPS DATA TYPICAL INSTALLATION PENDENT
8 RECESSED-TOP OUTLET 9 NTS
10 NTS
NTS SIDEWALL TOP OUTLET

TO SPRINKLER SYSTEM
ø150 OS & Y OR INDICATING 0C 100% DETAILED DESIGN KA NOV.2022
GATE VALVE (TYP.) 0B 90% DETAILED DESIGN KA SEPT.2022
0A 60% DETAILED DESIGN KA MAY 2022
ELECTRIC SPRINKLER ALARM No. REVISION APP'D DATE
SWITCH (TO BE CONNECTED CLIENT:
TO FIRE ALARM SYSTEM)
STRAINER
DISCHARGE NOZZLE TO MECHANICAL
FM 200 GALVANIZED PIPE SPRINKLER ALARM
Nominal Bolt Size Rod Size Hole Dia
KNURLED SWIVEL NUT Design Load
Pipe Size 'A' 'D'
CLIENT:
RETARD CHAMBER in (mm) in (mm) Lbs. (KN)
ISOLATING VALAVE 1/2" (15) 1/4" - 20X2.25 3/8" - 16 13/23" (10) 400 (1.78)
ADJUSTABLE SWIVEL
LOOP HANGER 3/4" (20) 1/4" - 20X2.25 3/8" - 16 13/23" (10) 400 (1.78)
PRESSURE GAUGE PRESSURE GAUGE (TYP.) FIRE FIGHTING PIPE (1.78)
FM200 FIRE FIGHTING CONTROL PANEL 1" (25) 1/4" - 20X2.75 3/8" - 16 13/23" (10) 400
(INSTALLED BESIDE CYLINDERS ) 1 1/4" (32) 1/4" - 20X3.00 3/8" - 16 13/23" (10) 400 (1.78)
CONSULTANT:
AUTOMATIC FM 200 1 1/2" (40) 1/4" - 20X3.25 3/8" - 16 13/23" (10) 400 (1.78)
WALL BLOCK WORK GAS RELIEF VALVE
MAIN DRAIN VALVE 2" (50) 1/4" - 20X3.50 3/8" - 16 13/23" (10) 400 (1.78)
- FIRE RATED SEALANT (FOR FIRE/SMOKE
RATED WALLS OR BARRIERS) FM200 CYLINDER 2 1/2" (65) 3/8" - 16X4.5 1/2" - 13 9/16" (14) 800 (3.56)
- SEALANT (FOR NON RATED PARTITION AND WALL BRACKETS (TYP.) 3" (80) 3/8" - 16X5.00 1/2" - 13 9/16" (14) 800 (3.56)
NORMAL BARRIERS)
3 1/2" (90) 3/8" - 16X5.50 1/2" - 13 9/16" (14) 800 (3.56)
(3.56)
DESIGNER:
4" (100) 3/8" - 16X6.5 5/8" - 11 9/16" (14) 800
ø150 OS & Y OR INDICATING 5" (125) 3/8" - 16X7.5 5/8" - 11 9/16" (14) 800 (3.56)
FIRE FIGHTING PIPE WORK GATE VALVE (TYP.)
PIPE SLEEVE 6" (150) 3/8" - 16X8.5 3/4" - 10 9/16" (14) 1000 (4.45)
8" (200) 3/8" - 16X10.50 7/8" - 9 9/16" (14) 1200 (5.34)
WALL BLOCK WORK
CONTRACTOR:
KABBANI GENERAL CONTRACTING

KABBANI ARCHITECTURAL CONCEPTS

PROJECT TITLE
PETROLEUM CONVERSION
RESEARCH CENTER- DTVC
DRAWING TITLE

FIRE FIGHTING MISCELLANOUS


DETAILS 1/2
TYPICAL DETAIL OF PIPE SLEEVE FM 200 CYLINDERS MOUNTING DETAILS ALARM CHECK VALVE DETAIL (VERTICAL TYPE) FIRE FIGHTING PIPE SUPPORT DETAIL ADJUSTABLE "J" HANGER DATA DESIGNED KA PROJECT No.
11 12 13 14 15 REVIEWED KA
NTS NTS NTS (APPLICABLE TO PIPES 2 1/2" DIA. AND BELOW) NTS NTS VERIFIED KA KH21029

FILE NAME: ENTER FILE NAME


APPROVED KA SHEET SIZE A0
DATE NOV.2022 SCALE N.T.S.
ISSUED FOR 100% DETAILED DESIGN
PROJECT ZONE BLDG. STAGE SERIAL NUMBER REVISION

KH21029 00 GN DD FG501 0C