KEY:

SITE LOCATION

240
DTVC LOT‐240
PCRC BUILDING

NOTES:
1. FOR LEGEND AND GENERAL NOTES REFER TO DWG. No. EG001.
2. FOR FIRE ALARM SYSTEM RISERS REFER TO DWG. No. EG711, 
EG712,EG713. 
3. FOR FIRE DETECTION AND ALARM SYSTEM MISCELLANEOUS DETAILS 
REFER TO DWG. No. EG507.
4. FOR FIRE DETECTION AND ALARM SYSTEM CAUSE& EFFECT MATRIX REFER 
TO DWG. No. EG714.
5. PROVIDE FAULT ISOLATING MODULES AFTER EVERY 25 DEVICES OR AS PER 
RECOMMENDED BY THE VENDOR DEPENDING ON THE TYPE OF DEVICES 
CONNECTED TO THE LOOPS.
6. ALL POWER AND SENSING OR SIGNALING CABLES SHALL BE OF 
CONTINUOUS LENGTH.
7. ALL CONDUITS PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE 
SEALED WITH APPROVED FIRE RETARDANT SEALANT TO MAINTAIN THE 
INTEGRITY OF FIRE RATING OF THE WALL.
8. SMOKE/HEAT DETECTORS SHALL BE AT LEAST 300mm AWAY FROM ANY 
PART OF LIGHTING FIXTURES AND ATLEAST ONE METER FROM AIR 
DIFFUSERS. 
9. THE HVAC SYSTEM SHALL BE INTERFACED WITH THE FIRE ALARM 
CONTROL PANEL AND THE HVAC SYSTEM SHALL AUTOMATICALLY SHUT 
DOWN WHEN THE ALARM SYSTEM IS ACTIVATED.
10. THE AVERAGE AMBIENT SOUND LEVEL (dBA) SELECTED SETTING OF 
AUDIBLE NOTIFICATION APPLIANCES SHALL BE IN ACCORDANCE WITH 
NFPA 72.
11. THE MINIMUM REQUIRED LIGHT OUTPUT (cd) OF VISIBLE NOTIFICATION 
APPLIANCES SHALL BE IN ACCORDANCE WITH NFPA 72.
12.  ALL CEILING AND FLOOR VOIDS WHICH ARE 800MM OF GREATER SHALL 
BE PROVIDED WITH APPROPRIATE DETECTORS AS PER NFPA AND LOCAL 
CIVIL DEFENCSE REQUIREMENT.
13.  FIRE ALARM DRAWINGS SHALL BE CERTIFIED BY REGISTERED 
ROFESSIONAL ENGINEER.
14. DUCT SMOKE DETECTORS SHALL BE PROVIDED ON THE SUPPLY AND 
RETURN AIR DUCTS OF THE CENTRAL AIR HANDLING SYSTEM AS PER 
KFUPM GENERAL AND SPECIFIC REQUIREMENTS.
15. ALL FIRE ALARM CABLES SHALL BE FIRE RETARDANT CABLES TYPE AND 
SHALL BE RUN IN RIGID GALVANIZED STEEL CONDUIT IN OUTDOOR AREAS,
EMT CONDUIT IN INDOORS AREAS, FACTORY PVC COATED RIGID 
GALVANIZED STEEL CONDUIT IN CORROSIVE AREAS , PVC CONDUIT IN 
UNDERGROUND AREAS & PVC CONDUITS EMBEDDED IN CONCRETE.
16. APPROPRIATE SMOKE DETECTORS WITH REMOTE LED INDICATOR SHALL 
BE PROVIDED ABOVE FALSE CEILING AND IN ALL VOIDS THAT ONLY 
CONTAIN COMBUSTIBLE MATERIALS IN ACCORDANCE WITH LATEST 
EDITION OF NFPA‐72.
17. CONTRACTOR SHALL ENSURE THAT ALL THIRD PARTY INTERFACES  LEGENDS:
(MECHANICAL,ELECTRICAL AND LOW CURRENT)ARE PROVIDED WITH 
INTERFACE MODULE AS PER THE PROJECT REQUIREMENT.
18.  CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR ALL SYSTEMS FOR  FIRE ALARM & EVACUATION SYSTEM ‐ ELEC ROOM
APPROVAL OF ENGINEER PRIOR TO EXECUTE OF WORKS.
19. REQUIRED CIVIL DEFENCE APPROVAL AFTER FINALIZING THE DESIGN. SYMBOL DESCRIPTION
E1 2 E2 20. CONTRACTOR TO ENSURE THAT ALL FIRE ALARM DEVICES AND 
INSTALLATION MATERIALS THAT INSTALLED IN LABS SHALL MEET THE 
REQUIREMENTS OF THE LAB SPECIALIST. ADDRESSABLE SMOKE DETECTOR OPTICAL TYPE
21. ALL LOCATIONS SHALL BE COORDINATED WITH MEP AND ARCHITECT TO 
AVOID CLASHING. 

ADDRESSABLE DUCT SMOKE DETECTOR

DOUBLE ACTION ADDRESSABLE MANUAL CALL POINT

WALL MOUNTED HORN WITH INTEGRATED STROBE
TO 91/L1/FACP‐G
LIGHT,
85/L1/FACP‐G 87/L1/FACP‐G
TO 8/NAC1/FACP‐G RATING: 80dB@3m & 15Cd UNLESS OTHERWISE
INDICATED ON DRAWINGS

EA 86/L1/FACP‐G ADDRESSABLE CONTROL MODULE RELAY
90/L1/FACP‐G FROM 6/NAC1/FACP‐G
30 cd

ADDRESSABLE MONITORING MODULE RELAY
7/NAC1/FACP‐G

ISOLATION MODULE

88/L1/FACP‐G

89/L1/FACP‐G

FOR SUPPLY AIR DUCT
75/L1/FACP‐G

F FROM 74/L1/FACP‐G

EB

84/L1/FACP‐G 76/L1/FACP‐G
83/L1/FACP‐G 77/L1/FACP‐G
82/L1/FACP‐G 78/L1/FACP‐G
81/L1/FACP‐G 79/L1/FACP‐G
80/L1/FACP‐G

0C 100% DETAILED DESIGN KA NOV.2022
0B 90% DETAILED DESIGN KA SEPT. 2022
0A 60% DETAILED DESIGN KA MAY 2022
00 30% DETAILED DESIGN KA DEC 2021
No. REVISION APP'D DATE

CLIENT:

CLIENT:

CONSULTANT:

DESIGNER:

ELECTRIC ROOM BUILDING FIRE DETECTION AND ALARM SYSTEM
1 1 : 50 CONTRACTOR:
KABBANI GENERAL CONTRACTING

KABBANI ARCHITECTURAL CONCEPTS

PROJECT TITLE
PETROLEUM CONVERSION RESEARCH
CENTER‐DTVC
DRAWING TITLE
FIRE DETECTION AND ALARM SYSTEM

FILE NAME: KH21029_KAA_00_XX_M3_EL_MAIN_0021
PLAN
ELECTRIC ROOM BUILDING
DESIGNED KA PROJECT No.
REVIEWED KA
VERIFIED KA KH21029
APPROVED KA SHEET SIZE A0
DATE NOV. 2022 SCALE 1/50
ISSUED FOR 100% DETAILED DESIGN
PROJECT ZONE BLDG. STAGE SERIAL NUMBER REVISION

KH21029 00 ER DD FA1011 0C