NOTES (CONT'D)
NOTES:
OF
SUPPRESSION CONTROL PANEL (FSCP).
CONSENT
10.EXISTING POWER SOURCE OF FIRE ALARM CONTROL
PANEL SHALL BE UTILIZE TO FEED THE NEW FIRE
SUPPRESSION CONTROL PANEL.
TTEN
PANELBOARD SCHEDULE DWG. NO. DA-727734.
6. UTILIZED THE EXISTING SPARE CONDUIT SLEEVES
FOR THE NEW CABLE ENTRY TO MCC BUILDING.
WRI
2
12.NEW SET OF CABLE (3CX4MM - XLPE/CU/PVC )
INSIDE 1/2-" CONDUIT ASSOCIATED WITH COMPLETE 7. CLOUDED PORTION INDICATES THE SCOPE OF
ACCESSORIES WILL BE USE DURING INSTALLATION. JO-10-03094-0001.
THE
13.ALL WIRES SHALL BE INSTALLED AS PER
SAES-P-104. SIZES, CONDUCTOR MATERIALS AND
THOUT
INSULATION TYPE SHALL BE IN ACCORDANCE WITH
SAES-P104 AND NEC 760.49.
WI NG
DRAWI
LEGEND
S
THI
SCOPE UNDER
J.O. 10-00844-001
FROM
LOW VOLTAGE CONDUIT WIRE
NED
2
3C-4MM XLPE/CU/PVC
OBTAI
FIRE SUPPRESSION CONTROL PANEL
(FSCP)
BE
EXISTING LIGHTING PANEL
K06-LP-B
PART,SHALL
FACP FIRE ALARM CONTROL PANEL
N
I
FULL,OR
N
I ON
REPRODUCTI
SAUDIARAMCO.NO
K06-FSCP-004 DRAWING CONTROL (JO-10-03094-0001) HD-312311
SEE NOTE 9 & 10
U/G POWER DISTRIBUTION PLAN DA-700838
OF
PROPERTY
40
PC-4595
189
SOLE
600
40 188
SPARE EXISTING
THE
CONDUIT SLEEVES
F.F.
ARE N
HEREI
0 1.0 2.0 3.0 4.0 5.0
NED
SCALE: 1 : 50M
184 40
CONTAI
REVISION VALIDATION
ON
610
NFORMATI
40 72 75 DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
I
0A3 07/01/21 ISSUED FOR 100% - PP
40 204 311
THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-00844-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED
DETAIL-1
SAUDI ARABIAN OIL COMPANY
AND
STUB-UP DETAIL DRAWING TYPE
NG
4160V SWITCHGEAR BUILDING NO. 4162
DRAWI
EAST/WEST PIPELINE PUMP STATION #3
S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.
THI
K06 P DA-727739 005 0A3
Saudi Aramco 2615 ENG. (05/05)