NOTES - FIRE FIGHTING

FIRE SUPPRESSION SYSTEM 1. COMPLETE PIPE WORK FOR FIRE PROTECTION SYSTEMS WITHIN THE BUILDING
ERW GI HEAVY DUTY PIPES & FITTINGS.
2. PIPE JOINTS AS FOLLOWS
NOZZLE a) 65 MM TO 150 MM PIPES - WELDED / GROOVED
b) 15 MM TO 50 MM PIPES - THREADED
3. ALL PIPES PAINTING AS PER ASIC APPROVED PAINTING PROCEDURES.
4. THE SUPPORTING & ANCHORING FOR SPRINKLER PIPE WORK AS PER NFPA-13.
WET CHEMICAL CYLINDER 5. SIZING OF ON - FLOOR DISTRIBUTION AND RANGE PIPES IN THE SPRINKLER
INSTALLATION ACCORDANCE WITH NFPA 13 UPRIGHT SPRINKLER ALONG WITH
CAPACITY PENDENT SPRINKLER PROVIDING IN AREA WHERE CEILING VOID EXCEED 800MM
(TYP).
6. ZONE CONTROL VALVE PROVIDING AS INDICATED IN DRAWINGS WITH TAMPER
MANUAL FULL STATION SWITCH AND A FLOW SWITCH. THE SAME WILL BE LINK TO THE FIRE ALARM
SYSTEM.
7. TEST VALVE PROVIDING AT EACH FLOOR AS PER DRAWING AND SHALL BE
DEFENDER DM KITCHEN CONNECTED TO THE DRAIN LINE.

13 14 15 16 18 19 20
EXTINGUISHING SYSTEM
HANWEI KB6000III GAS
8. FIRE EXTINGUISHERS OF CO2 5Kg. WITH HOSE AND HORN (1No.) AND WATER
10Lit. WITH HOSE (1No.) PROVIDING WITH EACH CABINET.
9. THE OPERATING INSTRUCTIONS FOR THE EXTINGUISHER IN ARABIC AND
ENGLISH LANGUAGE WILL BE PASTING INSIDE THE CABINET.
10. THE FIRE FIGHTING EQUIPMENTS AND ACCESSORIES AS GDCD APPROVED
CONTROL PANEL 11. FIRE ALARM INTERFACING WILL PROVIDE.

FIRE ALARM CABLE


LEGENDS:
DEFENDER DM12 KITCHEN HOOD FIRE SUPPRESSION SYSTEM-12 POINTS
SEAMLESS PIPE

PENDANT SPRINKLER
STANDARD RESPONSE EXTENDED
COVERAGE SPRINKLER

BUTTERFLY VALVE

M
HOT KITCHEN

C 23.10.2023 ISSUED FOR APPROVAL- REVISED AS PER COMMENTS ALI


HOT + COLD PICK-UP
PASS STATION
B 22.07.2023 ISSUED FOR APPROVAL- REVISED AS PER COMMENTS ALI
PREPARATION
AREA
STAIR
WELL A 16.07.2023 ISSUED FOR APPROVAL ALI

Revisions Date Description Checked


1000.0000

PROJECT:

RAAW COURTYARD
DUMB
WAITER
Riffa - Bahrain
CLEAN UTENSIL
AREA

STAFF CLIENT:
ENTRY

GOODS
ENTRY

DISHWASH
AREA
RAAW CAFE

POTWASH RECEIVING + ICE


AREA PROD AREA
CONSULTANT:

JANITORIAL
AREA Rayan Bldg. 1098, Flat 21
Road 3622 Block 436,
Al Seef, Kingdom of Bahrain
Tel. No. : +973 1362 5552
Email: g.karam@gkinterior.com

DRY STORE MEP CONSULTANT:


WALK-IN AREA
CHILLER

CONTRACTOR:

MEP CONTRACTOR:

Po Box 32651, BAHRAIN info@shringaelectric.com

DRAWING TITLE:

FIRE SUPPRESSION SYSTEMS


-
-
MEZZANINE FLOOR

ALI -- -- 1:50@A1

AHMED AMAR EP/001 M-405 C