MATERIALS NOTES ON REINFORCED CONCRETE SLAB

1. CONCRETE 40
0 A. ALL SLAB REINFORCEMENT SHALL BE 18mm CLEAR FROM BOTTOM/ TOP OF SLAB.
UNLESS INDICATED OTHERWISE ON THE PLANS. THE CONCRETE CLASS AND STRENGTHEN B. LENGTH OF CUT-OFFS SHALL BE AS SPECIFIED IN FIGURE 7.
400

SHALL BE AS FOLLOWS: C. IF SLABS ARE REINFORCED ON BOTH WAYS, BARS ALONG THE SHORT SPAN SHALL BE PLACE BE PLACED BELOW THOSE ALONG
THE LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN BARS NEAR THE SUPPORT.
D. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION. SEE TABLE 3 FOR SPACING.
E. UNLESS OTHERWISE NOTED IN PLANS OR SPECIFICATIONS, CAMBER ALL R.C. SLAB ALONG THE SHORTER SPAN, 3mm PER METER
28-DAY CYLINDER STRENGTH MAX. SIZE OF SPAN.
STRUCTURAL CLASS COARSE AGGREGATE F. UNLESS OTHERWISE NOTED, ALL SLABS ON GRADE ARE TO BE REINFORCED WITH 10MM BARS AT 400MM O.C. EACH WAY AT
MEMBER PSI MPa mm (in.) CENTER OF SLAB CONSTRUCTION JOINT FOR SAME SHALL NOT BE MORE THAN 3000MM APART.
SEE NOTE C NOTES G. PROVIDE EXTRA REINFORCEMENT FOR SLAB, SEE FIGURE 8.
FOOTINGS AA 4000 27.60 20 ON CONCRETE
WALLS
COLUMNS, BEAMS AA 4000 27.60 20
SLABS AA 4000 27.60 20 L1/4+ 120 L1/4 + 120 L2/4 + 120 L2/4 + 120
400

EXTERIOR TOP BARS INTERIOR TOP BARS CONTINUOUS TOP BARS


WHERE: CANTILEVER TOP BARS
2. REINFORCING STEEL
A. REINFORCING STEEL SHALL CONFORM TO ASSHTO M31 (ASTM A615), GRADE 40 FOR BARS 16mm D=DIAMETER OF
400
REINFORCING BAR
AND SMALLER (40,000psi), fy=275.80 Mpa, GRADE 60 FOR BARS 20mm AND LARGER (60,000psi), FIGURE 3 FIGURE 4
fy=414 Mpa. USED.
CONTINUOUS BOTTOM BARS
L 1/7 EXTRA TOP BARS L 1/7 L 2/7 EXTRA TOP BARS L 2/7
3. STRUCTURAL STEEL
A. STRUCTURAL STEELS ( A36) L1 L2 L3
FY = 248 MPA TYPICAL EXTERIOR SPAN TYPICAL EXTERIOR SPAN CANTILEVER SPAN
B. ALL WELDING WORKS SHALL BE DONE BY SKILLED AND LICENSED WELDER
NOTES ON REINFORCED CONCRETE BEAMS FIGURE 7
WHERE D= DIAMETER OF REINFORCING
BARS USED
A. UNLESS OTHERWISE NOTED IN THE PLAN OR SPECIFICATIONS, CAMBER ALL REINFORCED CONCRETE BEAMS AT LEAST
6mm FOR EVERY 4500mm CLEAR SPAN EXPECT CANTILEVERS FOR WHICH THE CAMBERS SHALL BE NOTED IN THE PLANS
OR ORDERED BY THE DESIGNERS BUT IN NO CASE LESS THAN 18mm FOR EVERY 3000mm FREE SPAN
NOTES ON REINFORCED CONCRETE WALLS TABLE - 3
SCHEDULE OF MINIMUM SLAB REINFORCEMENT
A. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF WALL
REINFORCEMENT UNLESS OTHERWISE NOTED ON PLANS THICKNESS 5-10mm Ø BARS SPACED @
L1/4 + 120 L1/4 + 120 L2/4+ 120 L2/4 + 120 2/3 L3 (mm) MINIMUM TEMPERATURE BARS 200mm O.C. TOP BARS
100 10mm Ø @ 270mm O.C.
TABLE - 1
400 110 10mm Ø @ 240mm O.C.
WALL REINFORCEMENT 130 10mm Ø @ 210mm O.C.
VERTICAL 5-10mm Ø BOTTOM BARS
THICKNESS 10mm Ø @ 190mm O.C.
(mm) SECTIONS 140 SPACED @ 200mm
HORIZONTAL VERTICAL
150 10mm Ø @ 170mm O.C.
100 10mm Ø @ 300mm O.C. 10mm Ø @ 300mm O.C. VERTICAL BARS AT CENTER, HORIZONTAL BARS STAGGERED SEE FIG. 1 L1/7 L1/7 L2/7 L2/7
L3
FIGURE 8
130 10mm Ø @ 250mm O.C. 10mm Ø @ 250mm O.C. VERTICAL BARS AT CENTER, HORIZONTAL BARS STAGGERED L1 L2
SEE FIG. 1
TYPICAL EXTERIOR SPAN TYPICAL EXTERIOR SPAN CANTILEVER SPAN
12mm Ø @ 250mm O.C. 12mm Ø @ 300mm O.C. VERTICAL BARS AT CENTER, HORIZONTAL BARS STAGGERED WHERE D= DIAMETER OF REINFORCING
150 SEE FIG. 1
BARS USED
180 12mm Ø @ 250mm O.C. 12mm Ø @ 100mm O.C. VERTICAL BARS AT CENTER, HORIZONTAL BARS STAGGERED SEE FIG. 1 FIGURE 5 NOTES ON COLUMNS
200 10mm Ø @ 250mm O.C. 10mm Ø @ 300mm O.C. BOTH FACES SEE FIG. 2
A. CONFINEMENT TIES SHALL BE PROVIDED ON THE COLUMNS AT BEAM COLUMN INTERSECTION AS SHOWN IN THE FIGURE 9 AND 10
230 10mm Ø @ 200mm O.C. 10mm Ø @ 250mm O.C. BOTH FACES SEE FIG. 2 UNLESS OTHERWISE SHOWN IN STRUCTURAL PLANS
250 12mm Ø @ 300mm O.C. 12mm Ø @ 350mm O.C. BOTH FACES SEE FIG. 2 38mm B. COLUMN TIES AND SPIRAL SHALL BE PROTECTED EVERYWHERE BY COVERING OF CONCRETE CAST MONOLITHICALLY WITH CORE OF
300mm
R.C. SLAB (MIN.)
280 12mm Ø @ 250mm O.C. 12mm Ø @ 300mm O.C. CLEAR MINIMUM THICKNESS OF 38mm AND NOT LESS THAN 1 12 TIMES THE SIZE OF COURSE AGGREGATES.
BOTH FACES SEE FIG. 2
B. LENGTH OF BAR CUT-OFFS AND BAR CLEARANCES SHALL BE AS
300 12mm Ø @ 250mm O.C. 12mm Ø @ 280mm O.C. BOTH FACES SEE FIG. 2 38mm SPECIFIED IN FIGURE 5. C. WHERE COLUMN CHANGES SIZE, VERTICAL REINFORCEMENT SHALL BE OFFSET OF A SLOPE OF NOT MORE THAN 1 5 WITH EXTRA TIES AT
CLEAR 100mm O.C. SHALL BE PROVIDED THROUGHOUT THE OFFSET REGION.
350 12mm Ø @ 200mm O.C. 12mm Ø @ 250mm O.C. BOTH FACES SEE FIG. 2 25mm Ø SEPARATOR C. IF BEAM REINFORCING BARS ENDS IN A WALL THE CLEAR DISTANCE
FROM THE BAR TO THE FURTHER FACE OF THE WALL SHALL NOT BE
38mm
400 16mm Ø @ 300mm O.C. 16mm Ø @ 350mm O.C. BOTH FACES SEE FIG. 2 LESS THAN 5 BAR DIAMETERS. THE REINFORCING BARS SHALL
CLEAR TERMINATE ON A STANDARD 90° HOOK, MINIMUM EMBEDMENT SHALL
BE 40 BAR DIAMETER FOR COMPRESSION BARS.
Y= 61 STOREY HEIGHT
FIGURE 6 100mm O.C. EXTRA TIES CR MAXIMUM COLUMN
DIMENSION WHENEVER

Y
TOP OF SLAB IS GREATER
50mm 50mm
75mm TYPICAL 75mm TYPICAL
D. IF THERE ARE TWO OR MORE LAYER OF REINFORCING BARS AT 900mm O.C IN NO CASE SHALL THERE BE LESS THAN TWO
SEPARATORS BETWEEN LAYER OR BARS. 50mm 50mm 100mm O.C.
75mm TYPICAL 75mm TYPICAL EXTRA TIES

Y
REINFORCING BARS SHALL HAVE 40mm MINIMUM CLEAR DISTANCE FROM WALL FACE E. MINIMUM CONCRETE PROTECTION OF REINFORCING BARS SHALL BE AS
EXCEPT FOR WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 70mm SHALL SHOWN IN FIGURE 6.
BE PROVIDED.
F. WHEN BEAM CROSSE A GIRDER, REST REST BEAM BARS ON TOP OF THE GIRDERS. AT COLUMN INTERSECTION, GIRDER
B. CARRY VERTICAL BARS AT LEAST 800mm ABOVE FLOOR LEVEL TO PROVIDE FOR BARS SHALL BE ON TOP OF BARS.
SPLICES. ELSEWHERE STOP AT 50mm BELOW THE TOP OF THE SLAB OR SOLID BOND
WHERE THE WALLS ENDS. HORIZONTAL AND VERTICAL BARS SHALL BE SPLICED BY C. GENERALLY, NO SPLICE SHALL BE PERMITTED IN BEAMS A POINT WHERE CRITICAL BENDING STRESS OCCUR, SPLICE FIGURE 9 (EXTERIOR FIGURE 10 (INTERIOR COLUMN)
LAPPING A DISTANCE EQUAL TO 40 BAR DIAMETER AND WIRED SECURELY WITH NO. 16 G.I. WHERE SO PERMITTED SHALL BE SIXTY (60) BAR DIAMETER FOR PLAIN BARS AND FORTY (40) BAR DIAMETER FOR COLUMN)
WIRE PROVIDED AT LEAST 1530mm ON CENTER. DEFORMED BARS. NOT MORE THAN BARS AT ANY SECTION SHALL BE SPLICED THEREIN.
SCHEDULE OF CONCRETE HOLLOW BLOCKS REINFORCEMENT
GENERAL NOTES
FIGURE 1 FIGURE 2 A. IN THE INTERPRETATIONS OF THESE DRAWINGS, INDICATED DIMENSION SHALL GOVERN AND DISTANCES OF SIZES SHALL NOT BE SCALED FOR
WALL REINFORCEMENT CONSTRUCTION PURPOSES.
THICKNESS REMARKS B. BARS ON REINFORCE CONCRETE EXPOSED TO WEATHER SHALL PREFERABLY BE PROTECTED WITH AT LEAST 40mm AND IN NO CASE NO LESS
(mm) HORIZONTAL VERTICAL THAN 25mm. THIS PROVIDED MAY BE WAIVED WHEN ADEQUATE WATERPROOFING IS PROVIDED.
C. UNLESS OTHERWISE NOTED IN THE PLAN, ALL OPENING WALL 250mm THK. OR THICKNESS SHALL BE REINFORCED AROUND C. ALL CONCRETE WORKS SHALL BE DONE IN ACCORDANCE WITH THE ACI CODE FOR REINFORCED CONCRETE AND ALL STRUCTURAL STEEL
WITH 2 (TWO) - 20mm Ø BARS. FOR 230mm THICK WALL AND BELOW, USE 2-16mm Ø, FOR 76 10mm Ø @ 610mm O.C. 10mm Ø @ 610mm O.C. WORKS IN ACCORDANCE WITH THE AISC SPECIFICATIONS IN SO FAR AS THEY WILL NOT CONFLICT WITH LOCAL BUILDING CODE AND THIS
A. MINIMUM LAP AT SPLICE = 250mm
130mm 10mm THICK WALL, USE 2-12mm Ø BARS. NOTES.
10mm Ø @ 610mm O.C. 10mm Ø @ 610mm O.C. B. PROVIDE RIGHT ANGLE REINFORCEMENT AT D. FOOTINGS ARE DESIGNED AN ALLOWABLE SOIL BEARING CAPACITY OF 100 kpa AT FOUNDING DEPTH OF 1.5m FROM NATURAL GRADE LINE.THE
100
CENTERS 910mm LONG.
ALL WALL OPENING SHALL HAVE VERTICAL REINFORCEMENT BENT TO U-FORM LIKE STIRRUPS AND SPACED ACCDG. C. WHERE CHB WALLS ADJOIN R.C. COLUMNS, CONTRACTOR SHALL REPORT TO THE ENGINEER IN WRITING ACTUAL SOIL CONDITIONS UNCOVERED AND CONFIRMED ACTUAL BEARING
150 10mm Ø @ 610mm O.C. 10mm Ø @ 610mm O.C. CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE AND VERIFIED PRIOR TO CONSTRUCTION.
TO SCHEDULE (TABLE -1). ALL CONCRETE WORKS SHALL BE REINFORCED WITH BARS OF AREA AT LEAST EQUAL TO THAT R.C. BEAMS AND WALLS, DOWELS SHALL
E. NO FOOTING SHALL REST ON FILL.
SPECIFIED IN THE LATEST EDITION OF ACI CODE. 200 12mm Ø @ 610mm O.C. 10mm Ø @ 610mm O.C. PROVIDED.
F. ALL FOOTING SHALL BE PROVIDED WITH 50mm THK. LEAN CONCRETE.
1 STRUCTURAL NOTES
S 1
PROJECT & LOCATION: SHEET CONTENTS: DESIGNED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO.: SHEET NO.:
PERALTA, LAMBIE
STRUCTURAL NOTES NAVARRO, VICTOR
MACALALAG, MARRIANNE
BATAAN HEROES COLLEGE NAPURAN, JUNJUN
BUAN, JHAMAECA
CONSTRUCTION OF ONE STOREY MUNAR, SHIRLY
DEPARTMENT OF ENGINEERING AND ARCHITECTURE RESIDENTIAL
ROMAN SUPERHIGHWAY BALANGA CITY, BATAAN
DRAWN:
PERALTA, LAMBIE S 1
NAVARRO, VICTOR
MACALALAG, MARRIANNE
NAPURAN, JUNJUN
BUAN, JHAMAECA
MUNAR, SHIRLY DATE: DATE: DATE: DATE: