You are on page 1of 1

1.

UNLESS OTHERWISE SHOWN IN PLANS ALL CONCRETE HOLLOW BLOCKS AND CERAMIC BLOCKS

GENERAL CONSTRUCTION NOTES:


1. IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL GOVERN AND
DISTANCES OF SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. 1. UNLESS OTHERWISE NOTED IN PLANS, THE YIELD STRENGTH OF REINFORCING BARS SHALL BE: SHALL BE REINFORCED AS SHOWN IN THE SCHEDULE OF CONCRETE HOLLOW BLOCKS AND CERAMIC
A. FOOTINGS, FOOTING BEAMS AND GIRDERS ------ fy = 275 MPa ( 40,000 psi ) BLOCK REINFORCEMENT.
2. IN REFERENCE TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR DEPRESSIONS
B. COLUMNS AND SHEAR WALLS -------------- fy = 275 MPa ( 40,000 psi )
IN FLOOR SLABS, OPENINGS IN THE WALLS AND SLABS, INTERIOR PARTIONS, LOCATION 2. PROVIDE 150mm x 300mm STIFFENER COLUMN REIFORCED WITH 4-12mm WITH 6mmØ TIES AT
OF DRAINS ETC. C. BEAMS AND GIRDER ------------------- fy = 275 MPa ( 40,000 psi ) 150mm ON CENTER WHERE CONCRETE HOLLOW BLOCK TERMINATES AND AT EVERY 3.0M LENGTH
3. IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS, AND ELEVATIONS BETWEEN D. NON-LOAD BEARING WALL PARTITIONS, BEDDED SLABS, FLOOR & ROOF SLABS, OF CONCRETE HOLLOW BLOCK WALLS UNLESS NOTED IN STRUCTURAL PLANS.
PARAPETS, CATCH BASIN, SIDE WALK. --------- fy = 227 MPa ( 33,000 psi ) 1. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF WALL 1. UNLESS , OTHERWISE NOTED IN PLANS, CAMBER ALL
THE STRUCTURAL PLANS, AND ARCHITECTURAL DRAWINGS, THE COTRACTOR SHALL NOTIFY 1. PROVIDE EXTRA SETS OF TIES AT 100mm O.C. FOR TIED COLUMN REINFORCEMENT
REINFORCEMENT UNLESS OTHERWISE INDICATED IN THE PLANS. BEAMS AND GIDER AT LEAST 6mm.S
BOTH THE STRUCTURAL ENGINEERS AND THE ARCHITECT. 2. ALL REINFORCING BARS SIZE 10mm OR BIGGER SHALL BE DEFORMED IN ACCORDANCE WITH SCHEDULE OF CONCRETE HOLLOW BLOCK AND CERAMIC BLOCK REINFORCEMENT ABOVE AND BELOW BEAM-COLUMN CONNECTIONS FOR A DISTANCE FROM FACE FOR EVERY 4.50M OF SPAN , EXCEPT CANTILEVERS
ASTM A 706. BARS. BLOCK OF CONNECTION EQUAL TO THE GREATER OF THE OVERALL THICKNESS OF COLUMN,
4. ALL CONCRETE WORKS SHALL BE DONE IN ACCORDANCE WITH THE ACI.318 95 BUILDING THICKNESS REINFORCEMENT NOTES FOR WHICH THE CAMBER SHALL BE
3. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE 1/6 THE CLEAR HEIGHT OF COLUMN OR 450mm. WALL VERTICAL AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER
CODE REQUIREMENTS FOR REINFORCED CONCRETE AND ALL STRUCTURAL STEEL WORK HORIZONTAL VERTICAL A. MINIMUM LAPS AT SPLICE = 0.25M
THICKNESS
W/ TABLE A & TABLE B (TABLE OF LAP SPLICE & ANCHORAGE LENGTH) UNLESS OTHERWISE 2. COLUMN TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST SECTION BUT IN NO CASE LESS THAN
ACCORDING WITH ASCI SPECIFICATION (9th EDITION) IN SO FAR AS THEY DO NOT CONFLICT B. PROVIdE RIGHT ANGLED REINFORCEMENT HORIZONTAL VERTICAL REMARKS
SHOWN ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE. 75 mm 10mmØ @ 600mm O.C. 10mmØ @ 600mm O.C. 20mm FOR EVERY 3.0M OF FREE SPAN.
WITH THE LOCAL BUILDING CODE REQUIREMENT. AT CORNERS 0.92M LONG MONOLITHICALLY WITH THE CORE WITH THE MINIMUM THICKNESS OF 40mm AND NOT
100mm Ø10mm @ 250mm O.C. Ø10mm @ 300mm O.C. HORIZONTAL BARS VERT.
C. WHERE CHB OR CER. BLK. WALL DOWELS LESS THAN 40 TIMES THE MAXIMUM SIZE OF COARSE AGGREGATE IN MILLIMETERS. 20 BAR DIA.
5. ACI REFERS TO AMERICAN CONCRETE INSTITUTE, ASCI TO AMERICAN INSTITUTE OF STEEL 125 mm 10mmØ @ 600mm O.C. 10mmØ @ 600mm O.C. 125mm Ø10mm @ 200mm O.C. Ø10mm @ 250mm O.C. AT CENTERS VERTICAL BARS
JOIN COL. R.C. BEAMS AND WALL DOWELS
LAPPED SPLICE
3. WHERE COLUMNS CHANGE IN SIZE , VERTICAL REINFORCEMENTS SHALL SHALL BE OFFSET HORIZ. 2. TYPICAL BARS BENDING AND CUTTING DETAILS FOR ON COMPRESSION
CONSTRUCTION AND ASTM TO AMERICAN SOCIETY FOR TESTING MATERIALS. 150 mm 10mmØ @ 600mm O.C. 10mmØ @ 600mm O.C. 150mm Ø12mm @ 250mm O.C. Ø12mm @ 300mm O.C. BARS STAGGERED OUT
WITH THE SAME SIZE AS VERT. OR HOR. BARS SHALL BE AS SHOWN IN FIG. B-1. BARS
AT A SLOPE OF NOT MORE THAN 1 IN 6 AND EXTRA 10mm TIES AT 100mm SHALL THREE-FOURTH
6. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE 1. ALL SLAB REINFORCEMENTS SHALL BE 20mm CLEAR MINIMUM FROM BOTTOM AND FROM REINFORCEMENTS SHALL BE PROVIDED THE ENBEDMENT
200 mm 12mmØ @ 600mm O.C. 12mmØ @ 600mm O.C. BE PROVIDED THRU OUT THE OFFSET REGION. REINFORCING BARS SHALL HAVE 25mm CLEAR CONCRETE COVER FROM FACE OF WALL EXCEPT L1 L2 L1

SHOWN OR NOTED MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. THE TOP OF SLAB. LENGTHS IN
FOR WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 60mm SHALL BE PROVIDED,
4. UNLESS OTHERWISE INDICATED IN THE PLANS, LAP SPLICES FOR COLUMN REINFORCE- SEE TABLE "A" TABLE 'A'
7. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, 2. UNLESS OTHERWISE DETAILED IN CONTINUOUS SLAB HAVING SAME REINFORCEMENT RUNNING AND FOR EXPOSED FACES OF FORMED WALLS WHERE THE MINIMUM SHALL BE 50mm CLEAR. L1/5 L1/3 L1/4 L1/4 L1/3 L1/5

MENT SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND THE SPLICE FOR LENGTH OF
MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC. SHALL BE SUBMITTED FOR ENGINEERS IN ONE DIRECTION, REINFORCING BARS SHALL BE BENT UP, OR CUT AS FOLLOWS 2. CARRY VERTICAL BARS AT LEAST 60mm ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES WHEN EMBEDMENT
APPROVAL BEFORE FABRICATION. LENGTH SHALL NOT BE LESS THAN 40 BAR DIAMETERS. WELDING OR APPROVED NECESSARY STOP AT 50mm BELOW TOP SLAB OR SOLID BAND WHERE THE WALL ENDS VERTICAL
MECHANICAL DEVICES MAY BE USED PROVIDED THAT NOT MORE THAN ALTERNATE BARS AND HORIZONTAL BARS SHALL BE SPLICED BY LAPPING A DISTANCE EQUAL TO 30 DIAMETERS
8. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, STOOLS, ARE WELDED OR MECHANICALLY SPLICED AT ANY LEVEL AND THE VERTICAL DISTANCES AND WIRED SECURELY WITH 16 G.I. WIRE PROVIDED THAT SPLICES IN ADJACENT BARS ARE
EQUIPMENT'S AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL, BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT LESS THAN 600mm. STAGGERED AT LEAST 1.50M.O.C.
CLEAR TOTAL MIN. HEIGHT OF REINFORCEMENT
ELECTRICAL, AND MECHANICAL DRAWINGS. L /3 L2 /4 L2 /4
L /4 2 L3 2 2L/3 SPAN LENGTH fc' LINTEL 3. UNLESS OTHERWISE NOTED IN THE PLANS, ALL OPENINGS IN WALLS 250mm OR THICKER SHALL SEE TABLE "A"
H SEE TABLE "A" 15 MIN. (WHENE COUNTED
9. ALL RESULTS OF MATERIAL TESTING FOR CONCRETE, REINFORCING BARS, & STRUCTURAL ("L") (L+0.40M) (MPa) (MM) BOTTOM TOP STIRRUPS BE REINFORCED AROUND WITH 2-20mmØ BARS FOR 225mm, 200mm, 175mm, 150mm, USE FOR LENGTH OF FOR COMPRESSION
FOR LENGTH OF
2-16mmØ. FOR 125mm AND 100mm WALLS, USE 2-12mmØ BARS. ALL WALLS SPANNING EMBEDMENT EXTEND 20 DIA. 15 MIN.

STEEL MUST BE NOTED & APPROVED BY THE STRUCTURAL DESIGNER. CROSS-TIE LAPPED SPLICE
1.20M 1.60M 200 1-Ø10 1-Ø10 Ø6mm @ 200mm SHALL HAVE VERTICAL REINFORCEMENT BENT TO A U-FORM LIKE STIRRUPS AND SPACED BEYONG OPPOSITE FACE
0.20 MIN. 0.15M MIN. 0.15M MIN. EDGE BARS 150M 1.90M 14.0 200 1-Ø10 1-Ø10 Ø6mm @ 200mm SUPPORT

350mm. MAX.
ACCORDING TO THE SCHEDULE UNLESS OTHERWISE NOTED (SEE FIG.1)
2 BARS 1.80M 2.20M 200 1-Ø12 1-Ø10 Ø6mm @ 200mm
10 EXTERIOR COLUMN INTERIOR COLUMN INTERIOR COLUMN EXTERIOR COLUMN
1. ALL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY 2.10M 2.50M 250 1-Ø12 1-Ø10 Ø6mm @ 200mm d 4-Ø16 VERT. BARS SUPPORT SUPPORT SUPPORT SUPPORT
L2 /5 L2 /5 L3 /5 L3 /3 m

H
EIGHT (28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMPS AS FOLLOWS. L1/3 L /5
2.40M 2.90M 17.0 250 1-Ø12 1-Ø10 Ø6mm @ 200mm in
2.70M 3.10M 250 1-Ø16 1-Ø12 Ø10mm @ 200mm . 4-Ø16 VERT. BARS

550
L
1 L
2 L
3 L
3

LOCATION 28 DAYS STRENGTH MAX. SIZE OF MAX. SLUMP TABLE 'A' TABLE 'B'

550
AGGREGATE EXTERIOR SPAN INTERIOR SPAN CANTILEVER SPAN 3.00 3.40M 300 1-Ø16 1-Ø12 Ø10mm @ 200mm
TENSION BARS COMPRESSION BARS
3.30 3.70M 20.0 300 1-Ø16 1-Ø12 Ø10mm @ 200mm
ALL OTHERS, INCLUDING 3.60 4.00 300 1-Ø20 1-Ø12 Ø10mm @ 200mm EMBEDMENT LENGTHS AND EMBEDMENT LENGTHS AND
3,000 PSI (20.70 MPa) 20mm 100mm JOINT HOOP SPACE @ "2Sh" WHEN
SUSPENDED SLABS, LAPPED SPLICED IN MILLIMETERS LAPPED SPLICED IN MILLIMETERS

CONF. REINF.
THERE ARE BEAMS HAVING WIDTH OF
COLUMNS 3.000 PSI (20.70 MPa) 20mm 100mm 12 THK. EXPANSION JOINT
AT LEAST ONE-HALF THE COLUMN BAR SIZE fc'= 20.7MPa(3000psi) fc'= 27.6MPa(4000psi) BAR SIZE fc'= 20.7MPa(3000psi) fc'= 27.6MPa(4000psi)
WITH MASTIC FILLER 1-Ø16 VERT. BARS
WIDTH & DEPTHS NOT LESS THAN 550 550 (DEFORMED) (DEFORMED)
BEAMS, SLABS 3,000 PSI (20.70 MPa) 20mm 100mm EMBEDMENT LAPPED EMBEDMENT LAPPED EMBEDMENT LAPPED EMBEDMENT LAPPED
3. IF SLABS ARE REINFORCED BOTHWAYS BARS ALONG THE SHORTER SPAN SHALL BE PLACED CHB WALL THREE QUARTERS OF THE DEEPEST
10mm Ø 300 300 300 300 10mm Ø 225 300 200 300
SLAB ON GRADE 2,500 PSI (17.24 MPa) 20mm 100mm BELOW THOSE ALONG THE LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN BEAM THAT FRAME INTO FOUR TYPICAL CONNECTION DETAIL

(DOWEL)
FOR SIZE AND SPACING 12mm Ø 300 300 300 300 12mm Ø 275 300 250 300
FOR REINFOCING BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS AT THE COLUMN SIDES OF THE COLUMN. ALL OTHER
OF R.C. WALL AT CORNERS

400
OF HOR. & VERT. BARS
2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS. STRIPS SHALL BE APPOXIMATELY ONE AND A HALF (1 1/2) SLAB THICKNESS 1-Ø16 VERT. BARS CONDITIONS USE HOOPS @ "Sh" CENTERS. 16mm Ø 300 400 300 400 16mm Ø 350 400 325 400
OR 45 CENTIMETERS CHB WALL SEE CONSTRUCTION NOTES.

CONF. REINF.
SUSPENDED SLABS -------------------------------------- 20mm FLR. SLAB OR BEAM DOWEL BARS TO 20mm Ø 400 550 350 500 20mm Ø 450 500 475 500
SLAB ON GRADE ---------------------------------------- 40mm 4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION FOR SIZE AND SPACING MATCH VERT. BARS

Sh
SEE CONSTRUCTION NOTES 25mm Ø 600 800 550 750 25mm Ø 550 625 550 625
WALLS ABOVE GRADE ------------------------------------- 25mm AND SHALL NOT BE LESS THAN 0.0025 BT. (SEE SCHEDULE BELOW) OF HOR. & VERT. BARS

(DOWEL)
SEE CONSTRUCTION NOTES. FOR MASONRY WALL REIN- 28mm Ø 750 1000 650 850 28mm Ø 625 675 625 675
BEAM STIRRUPS AND COLUMN TIES ---------------------------- 40mm
SCHEDULE OF MINIMUM SLAB REINFORCEMENT FORCEMENTS (TYPICAL)

400
WHERE CONCRETE IS EXPOSED TO CORNER WALL OPENING OR END WALL FIN. FLR. LVL.

PER SCHEDULE
32mm Ø 950 1300 850 1100 32mm Ø 700 775 700 775
FOR COL. BAR SPLICES SEE TABLE 1. ALL JOINTS AND CELLS
EARTH BUT POURED AGAINST FORMS --------------------------- 50mm THICKNESS MINIMUM TEMPERATURE BARS
OF MIN. LAP SPLICE LENGTH OF CONTAINING REINFORCING NOTE : TOP PLAIN BARS , MULTIPLY VALUE BY 2 NOTE : TOP PLAIN BARS , MULTIPLY VALUE BY 2
WHERE CONCRETE IS DEPOSITED
100 mm 10 mm Ø @ 400mm EACH WAY 1-Ø16 VERT. BARS R.C. COLUMN OR WALL COLUMN REINFORCEMENT BARS SHALL BE FILLED NAT. GRD. LVL. VALUES GIVEN ABOVE CAN ALSO BE USED
DIRECTLY AGAINST EARTH ---------------------------------- 75mm
(SPACING OF TIES ALONG THIS REGION DOWEL BARS TO MATCH FOR COLUMNS.
125 mm 10 mm Ø @ 400mm EACH WAY DOWEL BARS TO MATCH WITH CONCRETE GROUT.
3. CONCTRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION. RE-HAND 12 THK. EXPANSION JOINT SHALL NOT BE LESS THAN 100mm) CHB VERTICAL BARS 3. IF THE BEAM REINFORCING BARS END IN A WALL THE CLEAR DISTANCE FROM THE BAR TO
CHB HOR. BARS 2. FOR REINFORCEMENTS SEE
LING OR FLOWING PLACING SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKETS OR 150 mm 10 mm Ø @ 250mm EACH WAY WITH MASTIC FILLER THE FARTHER FACE OF THE WALL NOT BE LESS THAN 25mm. EMBEDMENT LENGTH SHALL
Ø10 BOTT. BARS

CONF. REINF.
CONSTRUCTION NOTES.
WHEELBARROWS, NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM CHB WALL 12 THK. EXPANSION JOINT @ 300 O.C. BE AS SHOWN IN A TABLE 'A' FOR TENSION BARS AND TABLE 'B' FOR COMPRESSION BARS

Sh
175 mm 10 mm Ø @ 225mm EACH WAY

(DOWEL)
HOPPERS TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT WITH MASTIC FILLER UNLESS SPECIFIED IN PLAN S. TOP BAR SHALL NOT BE SPLICED WITHIN THE COLUMN OR
3-Ø10 BOTT. BARS

400
WITHIN A DISTANCE TWICE THE MEMBER DEPTH FROM THE FACE OF THE COLUMN. AT LEAST
EXCEED SIX (6) METERS IN AGGREGATE LENGTH. 200 mm 10 mm Ø @ 150mm EACH WAY NOTE: 1-Ø16 CONT. HOR. BARS TWO STIRRUPS SHALL BE PROVIDED AT ALL SPLICES.

(DOWEL)
4. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS ALL CONCRETE REINF. DETAIL SHOULD FOR FLOOR SLAB ONLY
4. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USE 25mmØ BAR SEPARATORS

400
UNLESS AUTORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR UNUSUAL CONDITIONS 5. UNLESS OTHERWISE NOTED IN THE PLANS ALL BEDDED SLABS SHALL BE REINFORCED BE DONE IN ACCORDANCE WITH ACI
WITH 10mm Ø AT 250mm O.C EACH WAY TO CENTER OF SLAB AND CONSTRUCTION FOR SIZE AND SPACING SPACED AT 1.0M ON CENTER. IN NO CASE SHALL THERE BE LESS THAN TWO (2) SEPARATORS
WHERE VIBRATIONS IS EXTREMELY DIFFICULT TO ACCOMPLISH. DETAILING MANUAL LATEST EDITION
JOINTS FOR SAME SHALL NOT BE LESS THAN 3.65 METER APART OF HOR. & VERT. BARS DOWEL TO MATCH BETWEEN TWO LAYERS OF BARS.
5. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS, SHALL BE PROPERLY POSITIONED & SEE CONSTRUCTION NOTES. 400

CONF. REINF.
CHB VERT. BARS 5. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS OR STEEL SHAPES SHALL BE AS
SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. 6. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB (TWO ADJACENT DISCONTINUOUS (DOWEL) TYP. SECTION OF MASONRY
EDGES) AS SHOWN BELOW. WHERE DEPRESSED SHOWN IN FIG. B-2 UNLESS SPECIFIED ELSEWHERE.
6. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN CONSECUTIVE DAYS INTERSECTION WALL INTERSECTING R.C. COL. OR WALL
PARTITION REINFORCEMENTS SLAB OCCURS
b

7. CONCRETE SLAB REINFORCEMENTS SHALL BE PROPERLY SUPPORTED WITH 10mmØ STEEL MAIN REINFORCEMENT
IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP FOG SPRAYING, CURING
CHAIR OR APPROVED EQUIVALENT SPACED AT 1.0 METER ON CENTER BOTHWAYS DOWEL TO MATCH
COMPOUNDS OR OTHER APPROVED METHODS.

t
TYPICAL CONNECTION DETAIL OF MASONRY WALL TYPICAL COLUMN ELEV. SHOWING CHB VERT. BARS

t OR 1/4 D
7. STRIPPING OF FORMS AND SHORES:
FOUNDATION -----------------------------------------
DOWELS AND TIES SPACING WEB BARS

t
24 HRS. SLEEVES FOR UTILITY

ht
SEE NOTE
SUSPENDED SLAB EXCEPT WHEN PIPES MAX. 1/5 D
200 (MIN) 200 (MIN)

D
LAP SPLICE LENGTH: SEE NOTE
ADDITIONAL LOADS ARE IMPOSED ----------------------------- 8 DAYS Ø12x1000 LONG AT
DOWN INTO EDGE BEAM. EXTENDED AT ANY LEVEL NO MORE THAN
WALLS --------------------------------------------- 21 DAYS MID-DEPTH OF SLAB 3-Ø10 BARS (AS SHOWN)
4-Ø 12@ 1800 LONG TOP BARS BEND FOR SIZE AND SPACING ALTERNATE BARS SHOULD BE FIN. FLR. LVL.
BEAMS --------------------------------------------- 14 DAYS BARS MIN. OF 1,200 (4'-0") INTO BARS. AT EACH CORNER Ø10 STIRRUPS OF HOR. & VERT. BARS Ø10 BOTT. BARS @ 300 O.C. PROVIDE 3-Ø10 EXTRA STIRR.
SPLICED. MIN. DISTANCE BET. 0.025M Ø
COLUMNS -------------------------------------------- 21 DAYS @ 150 O.C. SEE CONSTRUCTION NOTES EACH SIDE OF SLEEVES
1-Ø12 TOP & TWO ADJACENT BARS SPLICES SEE NOTE SEPARATOR
4-Ø12 BOTT. BARS

WITHIN CENTER
BOTT. BARS

(DOWEL)
SHALL BE 600mm.
8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE 20 mm CLEAR FOR JOIST TYP. DET. FOR SLEEVES
DOWEL BARS TO MATCH 3-Ø10 BARS (AS SHOWN) TYPICAL CHB FOOTING DETAILS

HALF OF "H"
400
CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST (4) DAYS PRIOR TO THE NOTE 1 40 mm CLEAR FOR BEAMS
CHB WALL L/4 THRU CONCRETE BEAM
400

CHB VERT. BARS Ø10 BOTT. BARS @ 300 O.C. AND GIRDERS
POURING FOR APPROVAL. 2 BARS
( WHERE APPLICABLE )
9. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS SHORINGS UNTIL THE 2-Ø12 TOP BARS TOP BARS @ SUPPORT (CONT.) FIG. B-2 FIG. B-3
0
60

OPENING 6. WHEN A BEAM CROSSES A GIRDER, REST BEAM ON TOP OF GIRDER BARS, BEAM REINF-

200
CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH. 1-Ø16 VERT. REQ'D. BOTT. BARS @ SUPPORT (min.) (min.)
SLAB 38mm
CLEAR BARS TYPICAL 2-Ø12 BOTT. BARS FORCING BAR SHALL BE SYMMETRICAL ABOUT CENTER LINE WHENEVER POSSIBLE.
0

OPENING
60

t=FOR SLAB
7. GENERALLY NO SPLICES SHALL BE PERMITTED AT POINTS WHERE CRITICAL BENDING STRESSES

JT. REINF.
OCCUR, SPLICES WHERE SO PERMITTED SHALL BE INDICATED IN THE TABLE 'A' AND 'B'.
1. FOOTINGS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 112.00 WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125 % OF THE SPECIFIED YIELD
2 BARS
SECTION
400

STRENGTH OF THE BAR. NOT MORE THAN 50% OF THE BARS AT ANY ONE SECTION IS
FIN. FLR. LVL.
ALLOWED TO BE SPLICED THEREIN.
CONDITIONS, UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE
DEPOSITING CONCRETE. IN TWO WAY SLAB EXTEND BOTTOM BARS
BARS UP TO BEAM SUPPORT ELEVATION 20 SPLICE
AT MID SPAN 2t=FOR SLAB
60

2. FOOTING SHALL REST AT LEAST 1500mm BELOW NATURAL GRADE LINE UNLESS OTHERWISE
0

OMIT TRIMMER BARS WHERE 1. USE E70xx ELECTRODES FOR ALL MEMBERS WELDED.
INDICATED IN PLANS. NO FOOTING SHALL REST ON FILL. EXTRA TOP BARS
OPENING IS FRAMED BY BEAM
3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENTS SHALL BE 75mm CLEAR
TYP. DET. OF LINTEL BEAM AT CHB WALL OPENING @ SUPPORT (min.) 2. WELDS SHALL DEVELOP THE FULL STRENGTH OF MEMBERS JOINED UNLESS OTHERWISE

FOR CONCRETE DEPOSITED THE GROUND AND 50mm FOR CONCRETE TYPICAL CORNER SLAB DETAIL TYPICAL SLAB TYP. DETAIL OF COL. LAP SPLICE TYPICAL DETAIL FOR BEAM SHOWN OR DETAILED IN THE DRAWINGS.
DEPOSITED AGAINST A FORMWORK. OPENING DET. OR SLAB CHANGE SOFFIT
& EXT. GIRDER TO COL. CONNECT.
1. STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION OF THIS STRUCTURE SHALL
COMPLY WITH ALL THE PERTINENT PROVISION OF AISC SPECIFICATION FOR THE DESIGN,
1. ALL REINFORCEMENT SHALL BE BENT COLD UNLESS OTHERWISE PERMITTED BY THE FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDING LATEST EDITION.
db
STRUCTURAL ENGINEER. MAIN BAR END HOOKS STIRRUP AND TIE HOOKS 2. ALL STRUCTURAL STEEL SHAPES SHALL BE ASTM A 36 STRUCTURAL STEEL UNLESS
1. WHERE A CONSTRUCTION JOINT IS TO BE MADE, MAIN REINFORCEMENTS
NOTE: 2. REINFORCEMENT PARCIALLY EMBEDED IN CONCRETE SHALL NOT BE FILLED BENT, EXCEPT (ALL GRADES) (ALL GRADES) OTHERWISE INDICATED.
TO BE CONTINUOUS PROVIDE THESE ADDITIONAL BARS FOR
AS SHOWN IN THE DESIGN DRAWINGS OR PERMITTED BY THE STRUCTURAL ENGINEER. 3. ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE MEMBERS CONNECTED.

L
THE SURFACE OF CONCRETE SHALL BE 38mm
ALL OPENINGS PLUS BARS (NOT BAR SIZE DIAMETER BAR SIZE DIAMETER
CLEANED AND ALL LAITANCE AND CLEAR WINDOW 3. TIES & CLOSE STIRRUPS MUST BE BENT AT 135°. 180° HOOK 90° HOOK 180° HOOK 90° HOOK 4. ALL BOLTS USED UNLESS OTHERWISE SPECIFIED SHALL BE ASTM A 307 BOLTS.
Ø10x1000 LONG SHOWN) PARALLEL TO SIDE OF OPENING
STANDING WATER REMOVED. @ 300 O.C. OPENING (DEFORMED) (mm) (DEFORMED) (mm)
EQUAL TO THE NUMBER OF TERMINATED L D+2db L L D+2db L L
MAIN REINFORCEMENTS TO BE

D db

D+2db
CONTINUOUS (TOP & BOTT. BARS) 40 BARS AT OPENING A. ALL EMBEDED PIPES FOR UTILITIES, ETC. THAT PASS THRU BEAMS SHALL BE MAXIMUM 100mm

D
10mm Ø 60 75 125 150 10mm Ø 40 125 85 100

6d
DOOR

b
OR D/3 WHICHEVER IS LESS DIAMETER SINGLE RIGID GALVANIZED IRON PIPE UNLESS OTHERWISE
t/3

SEE ARCHITECTURAL & MECHANICAL


OPENING 4db or 65mm 12mm Ø 75 100 150 200 12mm Ø 50 165 115 115
WHERE JOINTS IS AT POINT OF OR APPROVED IN WRITING BY THE STRUCTURAL ENGINEER.
t/3

PLANS FOR SLAB OPENING LOCATION.


t

STRESS, PROVIDE SHEAR RODS


t/3

WITH ENGINEERS APPROVAL 16mm Ø 95 125 175 250 16mm Ø 65 200 140 150 B. NO PIPES SHALL BE ALLOWED TO PASS THRU BEAMS VERTICALLY.
SLAB C. NO PIPES SHALL BE EMBEDED TO COLUMNS.
30 BAR DIA. 30 BAR DIA.

db
50
(MIN.) (MIN.)
TYPICAL SLAB & BEAM CONSTRUCTION JOINT DET. 1. PROVIDE TEMPORARY REMOVAL OF WATER FROM ANY SOURCE DURING CONSTRUCTION. DEWATERING
D/3

12db
L
L SHALL BE CAREFULLY AND PROPERLY PERFORMED TO AVOID DISTURBING THE FOUNDATIONS AND
TYP. EXTERIOR WINDOW & DOOR OPENING
D/3

L1 SLAB BEARING SURFACES.


D

D
D/3

2. CONTRACTOR SHALL DESIGN, INSTALL AND MONITOR EXCAVATIONS RETENTION SYSTEMS, AS REQUIRED FOR
PROTECTION OF ADJACENT PROPERTIES AND PROVIDE ALL MEASURES AND PRECAUTIONS NECESSARY TO
BEAM MINIMIZE SETTLEMENT AND PREVENT DAMAGE TO ADJACENT EXISTING OR NEW CONSTRUCTION.

PROJECT TITLE: CERTIFIED BY : PRC NO. : PREPARED BY : CHECKED & REVIEWED BY : RECOMMENDING APPROVAL : APPROVED BY : SHEET CONTENTS : SHEET NO. :
REPUBLIC OF THE PHILIPPINES VALIDITY : GENERAL NOTES

REPUBLIC OF THE PHILIPPINES


DEPARTMENT OF AGRICULTURE
REGION VI-WESTERN VISAYAS
PROVINCE OF ILOILO
BONIFACIO DRIVE , ILOILO CITY 5000
REHABILITATION AND EXPANSION
OF PUNTALES FEEDER PORT
P T R NO. :

DATE ISSUED :
GENERAL CONSTRUCTION NOTES
S-01
PHILIPPINE RURAL DEVELOPMENT PROJECT PROJECT SP ID NP.:
EVA MAE V. PARRENAS ROMEO ANDIG RAUL N. BANIAS M.D.,MPA ATTY. SUZETTE A. MAMON ARTHUR R. DEFENSOR JR.
PRDP-IB-R006-ILO-010-000-000-2019-AF
PROJECT LOCATION: BRGY. NIPA , CONCEPCION , ILOILO
PLACE ISSUED :

T I N:
M U N I C I P A L E N G I N E E R ACTING PROVINCIAL ENGINEER MUNICIPAL MAYOR , MUNICIPALITY OF CONCEPCION PROVINCIAL ADMINISTRATOR P R O V I N C I A L G O V E R N O R 44-84

You might also like