You are on page 1of 1

GENERAL STRUCTURAL SPECIFICATIONS

1.0 NOTES ON CONCRETE MIXES AND PLACING I. ALL TRUSSES MUST BE PROVIDED WITH A CAMBER AT THE RATE OF 3MM FOR EVERY 3000MM (UNLESS OTHERWISE SPECIFIED) 6.0 NOTES ON CONCRETE SLABS
EFFECTED BY MEANS OF A PARABOLIC LAYOUT.
A. UNLESS OTHERWIS INDICATED IN THE PLANS OR NOTED IN THE SPECIFICATIONS, THE MINIMUM 28-DAY CYLINDER COMPRESSIVE A. ALL SLAB REINFORCEMENTS SHALL HAVE A MINIMUM CONCRETE COVER OF 20MM FROM BOTTOM AND FROM THE TOP OF SLAB.
STRENGTH OF CONCRETE SHALL BE AS FOLLOWS: 4.0 NOTES ON BEAMS AND GIRDERS
B. UNLESS OTHERWISE DETAILED IN CONTINUOUS SLAB HAVING SAME REINFORCEMENT RUNNING IN ONE DIRECTION, REINFORCING
1. FOOTINGS, FOOTING BEAMS AND GIRDERS, AND BASEMENT WALLS. 20.7 MPA (3000 PSI) A. UNLESS OTHERWISE NOTED IN PLANS OR SPECIFICATIONS, CAMBER ALL BEAMS AND GIRDERS AT LEAST 6MM FOR EVERY 4.50M BARS SHALL BE BENT UP, EXTENDED OR CUT AS FOLLOWS:
2. COLUMNS AND SHEAR WALL. 20.7 MPA (3000 PSI) OF SPAN, EXCEPT CANTILEVERS FOR WHICH THE CAMBER SHALL BE AS ORDERED BY THE DESIGNER BUT IN NO CASE LESS THAN
L* L* L* L* L* 2L 4/3 EDGE BARS
3. FLOOR AND ROOF SLABS, BEAMS AND GIRDERS (OTHERWISE SPECIFIED) 20.7 MPA (3000 PSI) 20MM FOR EVERY 3.0M OF FREE SPAN. 2 BARS
4. NON-LOAD BEARING WALLS, PARTITIONS, BEDDED SLABS, PARAPETS,

0.26M MIN. HT.


CATCH BASINS, SIDEWALKS 20.7 MPA (3000 PSI) B. TYPICAL BAR BENDING AND CUTTING DETAILS FOR BEAMS AND GIRDERS SHALL BE AS SHOWN IN FIG. 4. EXTRA BARS

B. 1. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION, REHANDLING, OR FLOWING PLACING SHALL 20MMØ
BE DONE, PREFERABLY WITH BUGGIES, BUCKETS, WHEELBARROWS OR BUCKETS, IN WHICH CASE THEY SHALL NOT EXCEED LAPPED SPLICE ON
SIX (6) METERS IN AGGREGATE LENGTH. COMPRESSION BARS
SEE TABLE "B"
FOR LENGTH OF L/1 L/2 L/2
2. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS AUTHORIZED IN WRITING BY EMBEDMENT 0.15 MIN.
THE DESIGNERS AND ONLY FOR UNUSUAL CONDITION IS EXTREMELY DIFFICULT TO ACCOMPLISH. SEE TABLE "A" L 1/5 L* L* L* L* L 3/5
0.20 MIN. 0.15 MIN.
FOR LENGTH OF
EMBEDMENT THREE-FOURTH L 1/6 L* L* L* L* L 3/3
2.0 NOTES ON CONCRETE WALLS
THE EMBEDMENT L1 L2 L3 L4
LENGTHS IN
A. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF WALL UNLESS TABLE "A" EXTERIOR INTERIOR CANTILEVER
OTHERWISE INDICATED IN THE PLANS. REINFORCING BARS SHALL HAVE 25MM CLEAR CONCRETE COVER FROM FACE OF WALL SPAN SPAN SPAN
EXCEPT FOR WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 63MM SHALL BE PROVIDED, AND FOR EXPOSED FACES FIG. 4
OF FORMED WALLS WHERE THE MINIMUM SHALL BE 50M CLEAR. 20 MIN (WHEN COUNTED L* THE GREATER C. IF SLABS ARE REINFORCED BOTHWAYS BARS ALONG THE SHORTER SPAN SHALL BE PLACED BELOW THOSE ALONG THE LONG
FOR COMPRESSION OF THE ADJACENT SPAN AT THE CENTER AND OVER THE LONGER SPAN FOR REINFORCING BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS
SEE TABLE "B" EXTENDED 20Ø BEYOND 20MM SPAN
AT THE COLUMN STRIPS SHALL BE APPROXIMATELY ONE AND ONE-HALF (1-1/2) THAT IN THE MIDDLE STRIPS BUT IN NO CASE
FOR LENGTH OF OPPOSITE SUPPORT)
REINFORCEMENTS GREATER THAN TWO AND ONE-HALF (2-1/2) THAT IN THE MIDDLE STRIPS BUT IN NO CASE GREATER THAN TWO AND ONE-HALF
WALL VERTICAL LAPPED SPLICE
THICKNESS
REMARKS
SECTION
(2-1/2) SLAB THICKNESS OR 45CM UNLESS OTHERWISE INDICATED IN THE PLANS.
HORIZONTAL VERTICAL EXTERIOR COLUMN INTERIOR COLUMN INTERIOR GIRDER EXTERIOR GIRDER 6
SUPPORT SUPPORT SUPPORT SUPPORT 6 D. TEMPERATURE BARS FOR SLABS SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION AND SHALL NOT BE LESS THAN
100 MM 10MMØ AT 250MM O.C. 10MMØ AT 300MM O.C.
HORIZONTAL BARS VERT. BARS 0.0025 BT. (SEE SCHEDULE BELOW).
AT CENTERS EXTRA TIES FOR UNLEVELED BEAM 10MM ADDT'L. TIES
125 MM 10MMØ AT 200MM O.C. 10MMØ AT 250MM O.C. (TYP. TO 150MM @ LOWER DROP ONLY)
VERTICAL BARS @ 150MM O.C.
HOR. BARS C. IF BEAM REINFORCING BARS END IN A WALL, THE CLEAR DISTANCE FROM THE BAR TO THE FARTHER FACE OF THE WALL SHALL
STAGGERED OUTSIDE
150 MM 12MMØ AT 225MM O.C. 12MMØ AT 250MM O.C. NOT BE LESS THAN 50MM. EMBEDMENT LENGTH SHALL BE AS SHOWN IN TABLE "B" FOR COMPRESSION BARS UNLESS SPECIFIED IN 150 4-10MM DROP
PLANS. TOP BARS SHALL NOT BE SPLICED WITHIN THE COLUMN OR WITHIN A DISTANCE OF TWICE THE MEMBER DEPTH FROM THE MIN. OF SLAB
SCHEDULE OF CONCRETE MIN. SLAB REINFORCEMENT
175 MM 12MMØ AT 250MM O.C.E.F. 12MMØ AT 300MM O.C.E.F. FACE OF THE COLUMN AT LEAST TWO (2) STIRRUPS SHALL BE PROVIDED AT ALL SPLICES.
THICKNESS MINIMUM TEMPERATURE BARS

T
200 MM 10MMØ AT 225MM O.C.E.F. 10MMØ AT 250MM O.C.E.F. BOTH FACES VERT. BARS
D. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USE 25MMØ BAR SEPARATORS SPACED AT 1.00M O.C. IN NO CASE 100MM 10MMØ AT 300MM EACH WAY
HORIZONTAL BARS
HOR. BARS SHALL THERE BE LESS THAN TWO (2) SEPARATORS BETWEEN LAYERS OF BARS. 125MM 10MMØ AT 250MM EACH WAY
225 MM 10MMØ AT 200MM O.C.E.F. 10MMØ AT 225MM O.C.E.F. SHALL BE OUTSIDE
150MM 10MMØ AT 200MM EACH WAY
T 300
250 MM 12MMØ AT 225MM O.C.E.F. 12MMØ AT 300MM O.C.E.F. E. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS OR STEEL SHAPES SHALL BE AS SHOWN IN FIG. 5, UNLESS SPECIFIED. 175MM 10MMØ AT 175MM EACH WAY
200MM 10MMØ AT 150MM EACH WAY
L/5 L/5
FIG. 1 L
WEB BARS FULL 2.0MM LINTEL BEAM AT
b SQUARE SQUARE 30MM O.C. TYP. TO DROP SLAB
B. CARRY VERTICAL BARS AT LEAST 600MM ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES WHEN NECESSARY. STOP AT 50MM 25MMØ PENETRATION
BUTT WELDS CUT END CUT END CONCRETE HOLLOW
BELOW TO SLAB OR SOLID BAND WHERE THE WALL ENDS VERTICAL AND HORIZONTAL BARS SHALL BE SPLICED BY LAPPING A SEPARATOR 2-16MM
BLOCKS WALL STR. BARS
DISTANCE EQUAL TO 40Ø AND WIRED SECURELY WITH NO. 16 G.I. WIRE PROVIDED THAT SPLICES IN ADJACENT BARS ARE STAGG E. UNLESS OTHERWISE NOTED IN THE PLANS, ALL BEDDED SLABS SHALL BE REINFORCED WITH 10MMØ AT 250MM O.C. EACH WAY AT
AT LEAST 1.52M (SEE FIG. 2). WELDING OF 10MM TIES CENTER OF SLAB AND CONSTRUCTION JOINTS FOR SAME SHALL NOT BE LESS THAN 3.00M APART.
REINFORCING TO @ 300MM O.C.
BE IN ACCORDANCE 2-12MMØ
C. UNLESS OTHERWISE NOTED IN THE PLANS, ALL OPENINGS IN WALLS 250MM OR THICKER SHALL BE REINFORCED AROUND WITH F. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB (TWO ADJACENT DISCONTINUOUS EDGES) AS SHOWN BELOW.

HT.
SEE NOTE W/ SPECIFICATION HOR. STR. BARS

400
2 - 20MMØ BARS. FOR 225MM, 200MM, 175MM, 150MM, USE 2 - 16MMØ. FOR 125MM AND 100MM WALLS, USE 2 - 12MMØ BARS AWS - D 12 W/ 6MM TIES
(SEE FIG. 3). ALL WALLS SPANNING SHALL HAVE VERTICAL REINFORCEMENT BENT TO A U - FORM LIKE STIRRUPS AND SPACED 1 - 16 @ 300MM O.C. G. CONCRETE SLAB REINFORCEMENTS SHALL BE PROPERLY SUPPORTED WITH 10MMØ STEEL CHAIR OR APPROVED EQUIVALENT
ACCORDING TO THE SCHEDULE UNLESS OTHERWISE NOTED (SEE FIG. 3). ALL CONCRETE WORK SHALL BE REINFORCED WITH SPACED AT 1.00M ON CENTER BOTHWAYS.
BARS OF AREA AT LEAST EQUAL TO THAT SPECIFIED IN ACI 318 - 89 BUILDING CODE.
3.18 MIN
SEE NOTE MAX BEAM BLOCK BEAM
NOTE 1 AT 800MM O.C.
VERTICAL BARS 12MM
20MM CLEAR FOR JOIST
1520MM BENT IN A U-FORM
40MM CLEAR FOR BEAMS THRU 28MM
LIKE STIRRUPS
MIN. AND GIRDERS
SEE SCHED. 5-10MM BARS
40d TYP. WELDED SPLICE DET.
UNDER NOTE C CHB WALL AT@ 200MM O.C.
2 BARS EACH FIG. 5 FOR BARS 12MM & 28MM
TOP & BOTTOM BARS
40d

DETAIL OF BLOCK
F. WHEN A BEAM CROSSES A GIRDER, REST BEAM BARS, BEAM REINFORCING BARS SHALL BE SYMMETRICAL ABOUT CENTER LIN AND LINTEL BEAM CORNER SLAB
SEE SCHED. WHENEVER POSSIBLE. 7.0 NOTES ON COLUMNS
1520MM

UNDER NOTE C
MIN.

G. GENERALLY, NO SPLICE SHALL BE PERMITTED ON BEAMS AT POINTS WHERE CRITICAL BENDING STRESSES OCCUR, SPLICES
A. PROVIDE EXTRA SETS OF TIES AT 100MM O.C. FOR TIED COLUMN REINFORCEMENT ABOVE AND BELOW BEAM-COLUMN
SPLICE

WHERE SO PERMITTED SHALL BE AS INDICATED IN TABLES "A" AND "B". WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST
40 CONNECTIONS FOR A DISTANCE FROM FACE OF CONNECTION EQUAL TO THE GREATER OF ALL OVERALL THICKNESS, 61THE CLEAR
40d

VERT. BARS 6-12MMØ


d 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR NOT MORE THAN 50% OF THE BARS AT ANY ONE SECTION SHALL BE
40d VERT. BARS HEIGHT OF COLUMN OR 450MM.
A ALLOWED TO BE SPLICED THEREIN.
MIN.

40
600

W/ 10MM TIES
FLOOR LEVEL d @ 400MM O.C. CHB WALL B. COLUMN TIES AND SPIRALS SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST MONOLITHICALLY WITH
FIG. 2 OPENINGS IN R.C. WALL SECTION "A" 5.0 NOTES ON FOUNDATION 400
THE CORE WITH THE MINIMUM THICKNESS OF 40MM AND NOT LESS THAN 1-1/2 TIMES MAXIMUM SIZE OF COARSE AGGREGATE IN
FIG. 3 MILLIMETER.
3.0 NOTES ON STRUCTURAL STEEL A. FOOTINGS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 240 KPa (ASSUMED). THE CONTRACTOR SHALL
REPORT IN WRITING TO THE ENGINEER THE ACTUAL SOIL CONDITIONS UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF C. WHERE COLUMNS CHANGE IN SIZE, VERTICAL REINFORCEMENTS SHALL BE OFFSET AT A SLOPE OF NOT MORE THAN 1 IN 6 AND
A. STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION OF THIS STRUCTURE SHALL COMPLY WITH ALL THE SOIL BEFORE DEPOSITING CONCRETE. EXTRA 10MM TIES AT 100MM O.C. SHALL BE PROVIDED THROUGHOUT THE OFFSET REGION.
DETAIL OF POST
PERTINENT PROVISION OF AISC SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR
BUILDING 1980, 8TH EDITION. B. FOOTING SHALL REST AT LEAST 600MM BELOW NATURAL GRADE LINE UNLESS OTHERWISE INDICATED IN PLANS. NO FOOTING D. UNLESS OTHERWISE INDICATED IN PLANS, LAP SPLICES FOR COLUMN REINFORCEMENT SHALL BE MADE WITHIN THE CENTER HALF
SHALL REST ON UNCOMPACTED FILL. OF COLUMN HEIGHT, AND THE SPLICES LENGTH SHALL NOT BE LESS THAN 30 BAR DIAMETER. WELDING OR APPROVED MECH'L.
B. ALL STRUCTURAL STEEL MEMBERS SHALL CONFORM TO ASTM SPECIFICATIONS FOR A - 36 STEEL. DEVICES MAY BE USED PROVIDED THAT NOT MORE THAN ALTERNATE BARS ARE WELDED OR MECHANICALLY SPLICED AT ANY
C. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENTS SHALL BE 75MM CLEAR FOR CONCRETE DEPOSITED AGAINST THE LEVEL AND VERTICAL DISTANCES BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT LESS THAN 600MM.
C. ALL WELDED AND BOLTED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE MEMBERS. USE A325 BOLTS AND E70XX GROUND AND 50MM FOR CONCRETE DEPOSITED AGAINST A FORM WORK.
ELECTRODES FOR WELDING. E. IN REFERENCE TO OTHER DRAWINGS, SEE ARCHT'L. DRAWINGS FOR DEPRESSIONS IN FLOOR SLABS, OPENINGS IN WALLS AND
SLABS, INTERIOR PARTITIONS, LOCATION OF DRAINS, ETC.
D. FABRICATION AND WELDING SHALL BE GOVERNED BY APPLICABLE PROVISIONS OF THE LATEST AISC AND AWS STANDARDS. SCHEDULE OF CONCRETE HOLLOW BLOCK REINFORCEMENT
F. IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS, AND ELEVATIONS BETWEEN THE STRUCTURAL PLANS AND ARCHT'L.
E. THE CONTRACTOR SHALL PREPARE FABRICATION (SHOP) DRAWING OF ALL STRUCTURAL STEEL MEMBERS BASED ON DESIGNS REINFORCEMENTS
BLOCK DRAWINGS, THE CONTRACTOR SHALL NOTIFY BOTH THE STRUCTURAL ENGINEERS AND THE ARCHITECT.
REMARKS
FOR THE APPROVAL OF THE STRUCTURAL ENGINEER PRIOR TO FABRICATION. THICKNESS
HORIZONTAL VERTICAL
G. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND LOCATIONS OF CONSTRUCTION JOINTS TO THE STRUCTURAL
F. ALL DOUBLE ANGLE STRUCTURAL MEMBERS MUST BE PROVIDED WITH FILLER PLATES AT 300MM ON CENTERS MAXIMUM SPACING. A. MINIMUM LAP AT SPLICES = 250MM
75 MM 10MMØ AT 600MM O.C. 10MMØ AT 600MM O.C. ENGINEER AT LEAST FOUR (4) DAYS PRIOR TO THE POURING FOR APPROVAL. CURING OF CONCRETE SHALL BE CONTINUOUS FOR
B. PROVIDE RIGHT ANGLED REINFORCEMENT AT
CORNERS 900MM LONG. A MINIMUM PERIOD OF SEVEN (7)DAYS IMMEDIATELY AFTER POURING.
G. ALL STRUCTURAL STEEL WORKS SHALL BE IN ACCORDANCE WITH THE NATIONAL STRUCTURAL CODE OF THE PHILIPPINES VOL. 1 100 MM 10MMØ AT 600MM O.C. 10MMØ AT 600MM O.C. C. WHERE CHB WALLS ADJOIN COLUMNS R.C.
1992, 4TH EDITION. UNLESS OTHERWISE DETAILED IN THE PLANS, ALL STEEL SHAPES AND SECTIONS SHALL CONFORM TO ASEP BEAMS & WALLS DOWELS W/ THE SAME SIZE AS H. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS AND SHORINGS UNTIL THE CONCRETE MEMBERS HAVE
HANDBOOK OF STRUCTURAL STEEL SHAPES AND SECTION, 1987 FIRST EDITION. 150 MM 12MMØ AT 400MM O.C. 12MMØ AT 600MM O.C. VERTICAL OR HORIZONTAL REINFORCEMENT
SHALL BE PROVIDED. ATTAINED THEIR WORKING CONDITION AND STRENGTH.
D. PROVIDE BEAM BLOCKS AT EVERY FOURTH
H. ALL EXPOSED STRUCTURAL MEMBERS SHALL RECEIVE AT LEAST TWO (2) COATS OF RED LEAD OR ZINC CHROMATE PRIMER PAINT. 200 MM 12MMØ AT 400MM O.C. 12MMØ AT 600MM O.C.
COARSE AND POST AT 3000MM O.C. (SEE DET.) I. ACI REFERS TO AMERICAN CONCRETE INSTITUTE, AISC TO AMERICAN INSTITUTE OF STEEL CONSTRUCTION, AND ASTM TO
AMERICAN SOCIETY FOR TESTING MATERIALS.

CERTIFIED BY: NAME OF PROJECT: APPROVED BY: SHEET CONTENT:


NOTE
THIS DRAWING IS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE
INTELLECTUAL PROPERTY AND DOCUMENT OF THE ENGINEER. ITS SHALL
BE UNLAWFUL FOR ANY PERSON TO DUPLICATE OR TO MAKE COPIES OF SPS. MITCHELLE & FRANCIS GREGG FUNCLARA
ALFREDO T. INFANTE III
CIVIL ENGINEER
THE SAID DOCUMENT FOR USE IN THE REPITITION OF AND FOR OTHER S-1
PROJECTS OR BUILDINGS WITHOUT THE CONSENT OF THE ENGINEER, LOCATION: ADDRESS: BLK. 6 LOT 12, ST. PAUL VILLAGE AS SHOWN
BLK. 6 LOT 12, ST. PAUL VILLAGE MANDURRIAO, ILOILO CITY
PRC NO.: 116475 VALIDITY: 5-10-2024 WHETHER EXECUTED PARTLY OR IN WHOLE. MANDURRIAO, ILOILO CITY
PTR NO.: 7729246 DATE: 1-19-2022 RA 9266, ART 3, SEC 20 (4) LOT OWNER: DATE: PLACE:
SPS. MITCHELLE & FRANCIS GREGG FUNCLARA 7 / 14
TIN: PLACE: ILOILO CITY

You might also like