You are on page 1of 6

APPENDIX - X

TECHNICAL SPECIFICATION FOR


3D CAD MODELING
MIRFA INDEPENDENT WATER AND POWER PLANT
Technical Specification for 3D CAD MODELING Rev. A

Table of Contents

Section Page

1. 3D MODELING........................................................................................................................1

1.1 PURPOSE ................................................................................................................................1

1.2 3D MODELING SCOPE ...........................................................................................................1

1.3 3D MODELING SOFTWARE ...................................................................................................2

1.4 SUBMISSION FORMAT AND METHODS ...............................................................................2

1.5 3D MODEL SUBMITTAL TIME ..............................................................................................4

RO PLNAT i Rev. A
MIRFA INDEPENDENT WATER AND POWER PLANT
Technical Specification for 3D CAD MODELING Rev. A

1. 3D MODELING

1.1 PURPOSE
The purpose of 3D Modeling is to review the engineering documents and drawings and prevent
problems which may arise during construction. The 3D models shall be developed to a level of
detail that is consistent with the submitted drawings as deliverables.

1.2 3D MODELING SCOPE


The equipment vendors shall provide 3D models of both equipment and structures. The contents of
3D modeling details are as follows. Item not in the scope of supply by vendors is excluded.
1) Civil
- Concrete foundation
- Steel structure
- Handrail, Ladders & Stairs Etc.
2) Architecture
- Building foundation
- Steel structure foundation
- Equipment foundation
- Wall (Opening, Window, Door)
- Ladders, Hand rails, Gratings, Etc.
3) Equipment
- Mechanical equipment & nozzles
- Platforms and ladders for maintenance
- Cranes and hoists
- Maintenance area for pumps
- Maintenance area for heat exchangers
- Equipment insulation envelopes
4) Piping
- Piping
- Piping Supports
- Valve Hand wheels and actuators Etc.
5) Fire Fighting and HVAC
- Fire Fighting Pipes
- Hydrants
- Sprinkler System
- HVAC DUCT in the building
- Drain pipes in building
6) Electrical and Instruments

RO PLNAT 1/4 Rev. A


MIRFA INDEPENDENT WATER AND POWER PLANT
Technical Specification for 3D CAD MODELING Rev. A

- Cable Tray & Cable tray support


- Panel
- Junction box
- In-line instrument

1.3 3D MODELING SOFTWARE


- Plant Design System (V 7.3)
- Microstation J

1.4 SUBMISSION FORMAT AND METHODS

1.4.1 3D Model to submit shall be created as one of the following formats.(included 3D model List)
Order S/W File Format Remark
Model & Data
1 PDS SmartPlant Review dri, drv, dgn, prp
(property are required)
Model
2 Microstation 3D dgn
(property are not required)

1.4.2 Graphic Core is Microstaion J or equivalent and please use the following working unit.
*(): alternative unit
Master Unit Sub Unit Positional Unit
Unit Name M (MM) MM (MM) -
Resolution 1 (1) 1000 (1) 80

1.4.3 The location of all 3D model files should be placed at the coordinates shown on Plot Plan.
3D Model should be located in actual position from the origin point.

1.4.4 If 3D model file naming rule is required, the equipment supplier should follow.

1.4.5 Model files of equipment, plumbing, electricity, steel, etc. shall be separated in each file as per the
discipline. Each file size shall be less than 2MB.

1.4.6 The model list shall be submitted with the 3D model files.

1.4.7 For the main equipment, the inside items shall be modeled. (If there is no interference inside
equipment, only the external shape of equipment could be modeled by agreement.)

RO PLNAT 2/4 Rev. A


MIRFA INDEPENDENT WATER AND POWER PLANT
Technical Specification for 3D CAD MODELING Rev. A

1.4.8 Model file should show the properties for each element on review program. The minimum property
is as follows.
□ Pipe
- Line numbers
- Design conditions (design temperature, design pressure, operation temperature, operation
pressure, test pressure etc.)
- Etc.
□ Steel structure
- Member size
□ Cable tray
- Cable tray size
□ Panel
- Panel tag no.
- Panel description
- Panel door open space
□ Equipment
- Equipment tag no.
- Equipment Nozzle data
- Equipment description
- Equipment Removal space

1.4.9 3D model should be checked as follows before providing.


□ Work scope specified by contract
□ Working unit in 3D model
□ Consistency between 3D Model and drawing
□ Location and direction of 3D Model
□ Consistency between nozzle location and drawings
□ Piping and Cable Terminal Point
□ Consistency between 3D Model and list, etc.

RO PLNAT 3/4 Rev. A


MIRFA INDE EPENDENT WATER W AND POWER
P PLAN
NT
Technical Specification forr 3D CAD MO
ODELING Rev. A

1.4.10 If ccontractors do
d not use PDS for 3D C
CAD modeling, 3D CAD model
m shall bbe converted
d properly so
o
tha
at it can be re
endered in th
he 3D modell review prog
gram (SmartP
Plant Review
w). (When the
e 3D modelss
are
e developed not in PDS but using an
nother solutio
on and they are converteed to MICRO
OSTATION J
forrmat, sometim
mes the 3D CAD
C model sshapes are looked only WIRE
W FRAM
ME. Please be
e cautious)
-Exxample of not acceptable 3D
D model-

1.5 3D
D MODEL SUBMITTAL
S L TIME
- when afterr the contractt within 1 mo
onth (in appro
oximate shap
pe)
- when subm
mit related drrawings
- when an ow
wner require
es
- when subm
mit final docu
uments

RO PLNAT 4/4 Rev. A