You are on page 1of 7

Supplementary guidance on

the design of stairs to help


achieve compliance with the
Building Regulations

Printed on recycled paper containing


a minimum of 75% post-consumer waste
Supplementary guidance on the design of stairs to help
achieve compliance with the Building Regulations

1.0 Introduction
2.0 Purpose of this guidance
Stairs serve many different functions in
a building e.g. a mean of escape, a The choice of stairs is crucially
means of access for ambulant disabled dependent on the designers
people or an effective and simple understanding of the function of the
means of vertical circulation, or stairs under consideration i.e.
sometimes a combination of these. approach, access, circulation, egress or
Functional requirements and guidance any combination of these. This
on compliance for stairs are given in supplementary guidance document was
various Parts of the Building developed as a tool to assist building
Regulations namely: professionals readily determine some of
the key criteria of stairs design and
 Part K (Stairways, Ladders, Ramps expresses the individuality of some of
and Guards) for stairs in general, the key stairs design criteria.

 Part B (Fire Safety) for escape, and The Technical Guidance Documents
give guidance on minimum standards.
 Part M (Access and Use) for stairs Those involved in the design and
suitable for ambulant disabled construction of buildings should have
people. also have regard to the principles of
Universal Design and consider making
Designers should refer to the relevant additional provisions where practical
Part and accompanying TGD when and appropriate.
designing stairs.
3.0 How to use the supplementary
 Technical Guidance Document K guidance
(Stairways, Ladders, Ramps and
Guards) contains the primary The guide is presented in 3 tables.
guidance document on stairs design
in an overall sense when the stairs is  Table 1 deals with external stairs
located within (or immediately outside a building other than a
outside) a building. dwelling.

 Technical Guidance Document B  Table 2 deals with internal stairs in a


(Fire Safety) considers, inter alia the building other than a dwelling.
stairs design criteria that need to be
addressed with respect to safe  Table 3 deals with both internal and
egress and is very much dependent external stairs in an about dwellings.
on the building purpose group,
building occupancy level, etc. Compliance with this supplementary
guidance does not confer immunity
 Technical Guidance Document M from compliance with the Building
(Access and Use) in the context of Regulations (or any other Regulations).
stairs has an objective to provide
independently accessible approach
4.0 Further reading
to the main entrance(s) of a building
and means of circulation around a C722 Safer stairs in public places -
building assessment of existing stairs - CIRIA
(2013)
Where works are carried out in
accordance with the TGDs, this will, Refurbishing stairs in dwellings to
prima facie, indicate compliance with reduce the risk of falls and injuries –
the relevant parts of the Second BRE TRUST (2013)
Schedule to the Building Regulations
(as amended).

1
Table 1 External stairs outside buildings (other than dwellings)

Part K
Stairways, Part M Part B
Ladders, Ramps Access and Use Fire Safety
and Guards
K1 Stairways, B1 Means of escape
Building ladders and ramps M1 Adequate provision shall be in case of fire
shall be such as to made for people to access and
Regulations afford safe passage use a building, its facilities and its B5 Access and
Requirements for the users of a environs. facilities for the fire Designer decision
building. service.
Where stairs are required below on
provided:
 Design for vertical
function of stairs
Application of Requirement K1
Applies to:
escape;
 Make provision for
under consideration.
Building

DOES NOT apply to
Regulations 1. the approach route(s) to the people with
steps or access
relating to the accessible entrance(s) (Refer to disabilities;
routes outside a
1.1.2 of TGD M 2010 for the  Provision for
provision of building other than
defined approach routes);
where steps are personnel access to
external 2. the circulation routes around a buildings for
steps/ stairs immediately outside
building (Refer to 1.1.2 for the firefighting.
outside a the external door of
defined circulation routes) Refer to Section 1.2.6
a building.
building: ‘External Escape
Routes’ of TGD B for
provision of external
g
escape stairways.

TGD M 2010 Reference/


TGD K 2014 Stairs designed
Criteria Existing TGD B 2006 relevant
New buildings
Section 1
buildings for: TGD
c
Section 2
1. Stairs width 1200 (min) Egress B (See across)
As wide as Refer to 1.3.4 and
(For landing between walls,
As required by TGD possible but not 1.3.5 for determining Approach/ Access/
upstands, strings M (See across)
width see B or TGD M.
and 1000 (min)
less than 1000 widths of stairways Circulation
Note h See across  mm between (but not less than 800 The wider of B
between a Egress + any of above
below) handrails. mm). and M
handrails
2. Max rise of Egress K (See across)
flight 1500 mm (max) rise or 18 rises Approach/ Access/
16 rises or 18 rises b No additional Circulation
between where going ≥ 350
b where going ≥ 350
requirements M (See across)
level Egress + any of above
landings
Opt Max Egress K (See across)
150 (min) 150 (min)
Semi No additional Approach/ Access/ 150 (min)
3. Rise (R) Public
165 190 to to
requirements Circulation to
180 (max) 180 (max)
Public 150 180 Egress + any of above 180 (max)
Opt Min Egress K (See across)
300 (min) As large as
Semi No additional Approach/ Access
4. Going (G) Public
300 250 to possible but not
requirements Circulation M (See across)
450 (max) less than 280
Public 300 280 Egress + any of above
Min Opt Max Egress
No additional requirements No additional Approach/ Access/
5. Gait (2R+G) requirements Circulation
K (See across)
550 600 700
Egress + any of above
Allowed subject to Egress Allowed
16mm (min) overlap Approach/ Access
Not allowed No additional
6. Open risers of nosing & 100mm
requirements
Circulation
Not allowed
(max) gap between
Egress + any of above
treads
Avoid Egress K (See across)
Semi
7. Tapered (unless Not allowed No additional Approach/ Access/
Public
treads necessary) requirements Circulation Not allowed
Public No allowed Egress + any of above
Egress ≥ 2000
≥ 2100 Approach/ Access/
8. Headroom ≥ 2000 ≥ 2000
Circulation ≥ 2100
Egress + any of above
>3 Provide Provide
> 3 risers Egress B (See across)
risers handrails handrails
Both one side Approach/ Access/
> 1000 ≤ 1000
sides only Circulation
Both sides of all stairs flight
9. Handrail d both
regardless of number of risers. > 1000
provision sides Both sides
de
One
≤ 1000 provide a
side Egress + any of above
wide central
only > 1800 e
handrail

2
New Existing
Above: Min Max Min Max Min Max Egress K (See across)
build building
Pitch Pitch 100 Pitch Approach/ Access/
900 1000 900 840 1000
10. Handrail line line 0 line No additional Circulation
height Interme Interme
Interm requirements
M (See across)
110 ediate
d-iate 900 1100 diate 900 840 1100 Egress + any of above
0 landin
landing landing
g
Stairs should be
guarded at the sides No additional requirements No additional Approach/ Access/
11. Guarding where the total rise is > requirements Circulation/ Egress
K (see across)
600 mm. (See 1.1.18)
No
12. Tactile Egress
requirements
hazard Top & bottom landings Approach/ Access/
No requirements No requirements
warning Circulation M (See
surfaces across)
Egress + any of above
No
Adequate artificial Egress
All step nosing to incorporate permantly requirements
lighting should be
contrasting material on the tread. Approach/ Access/
13. Visibility No requirements
Illuminance at tread level to be at least
provided to all
Circulation M (See
external escape
100 lux across)
routes (See 1.4.8) Egress + any of above

Notes:
a
Method of measurement as per Para B1.0.10 Methods of Measurement – Width “(iii) a stairway is the clear width
between walls or balustrades, (strings and handrails intruding not more than 30 mm and 100 mm respectively may be
ignored.”
b
In places of assembly to which large numbers of people have resort, there should be no more than two consecutive
flights each having a maximum of twelve risers, without a change in direction of at least 30 between flights;
c
Section 2 provides additional guidance on the minimum provisions for certain elements and features of existing buildings
where it is not practicable to achieve the provisions set out in Section 1.
d
If width between handrails > 2000 mm then divide stairs into channels not less than 1000 mm and not > 2000 mm.
e
In such a case the stairway width on each side of the handrail needs to be considered separately for the purpose of
assessing stairway capacity.
g
External escape stairways should be sufficiently protected from the weather and is adequately protected from a fire in the
building (see 1.3.9 TGD B).
h
Top and bottom landings should be level and at least as great as the smallest width of the flight determined by Criteria 1.

3
Table 2 Internal stairs in buildings (other than dwellings)
Part K
Stairways, Part B
Part M
Ladders, Fire Safety
Access and Use
Ramps and
Guards
K1 Stairways, B1 Means of escape in
ladders and ramps M1 Adequate provision shall be case of fire
Building
Regulations
shall be such as to
afford safe
made for people to access and
use a building, its facilities and its B5 Access and facilities
Designer decision
Requirements
passage for the environs. for the fire service. required below on
users of a building.
function of stairs
Where stairs are
provided: under consideration.
 Design for vertical

Application of ALL internal stairs


At least one set of stairs suitable for
escape;
 Make provision for

Building ambulant disabled people should be
(as required) must people with
Regulations provided to access all floors above
comply with Part K. disabilities;
relating to the or below entrance level.
 Make provision for
provision of personnel access to
internal stairs. buildings for
firefighting.

Technical Guidance Documents


TGD M 2010
Criteria TGD K 2014 Existing TGD B 2006 Stairs designed for:
Reference/
New buildings relevant TGD
buildings
Section 1 c
Section 2
As required by 1200 (min) As wide as Circulation/ Egress/ Both
a
B (See across)
1. Stairs width Refer to 1.3.4 and 1.3.5
TGD B or TGD M between walls, possible but not
(For landing for determining widths Ambulant disabled only M (See across)
(if stairs suitable for upstands, strings less than 1000
width see of stairways (but not
ambulant disabled and 1000 (min) mm between a The wider of B
a
Note f below) less than 800 mm ). Any combination of above
people) between handrails. handrails. and M
b
2. Max rise of Circulation/ Egress/ Both 16 rises
flight b 1800 (max) No additional Ambulant disabled only
16 risers
between level requirements 1800 (max)
b

landings Any combination of above


Opt Max Circulation/ Egress/ Both K (See across)
Semi 150 (min) to 180 (max) No additional
3. Rise (R) 165 190 Ambulant disabled only 150 (min) to 180
Public requirements
(max)
Public 150 180 Any combination of above
Opt Min Circulation/ Egress/ Both K (See across)
Semi 300 (min) As large as
300 250 No additional Ambulant disabled only
4. Going (G) Public to possible but not
requirements M (See across)
450 (max) less than 250
Public 300 280 Any combination of above

Circulation/ Egress/ Both


Min Opt Max
No additional requirements No additional
5. Gait (2R+G) Ambulant disabled only K (See across)
requirements
550 600 700 Any combination of above
Allowed subject to Circulation/ Egress/ Both K (See across)
16mm (min)
Not allowed No additional
6. Open risers overlap of nosing & Ambulant disabled only
requirements Not allowed
100mm (max) gap
between treads Any combination of above
Avoid Circulation/ Egress/ Both K (See across)
Semi
(unless
Publi
7. Tapered necessar Not allowed No additional Ambulant disabled only
c
treads y) requirements Not allowed
Publi Not
Any combination of above
c Allowed
Circulation/ Egress/ Both ≥ 2000

≥ 2100 Ambulant disabled only


8. Headroom ≥ 2000 ≥ 2000
≥ 2100
Any combination of above

4
>3 Provide Provide
> 3 risers handrails
Circulation/ Egress/ Both B (See across)
risers handrails
≤ 1000 one side one side
≤ 1000 only
Ambulant disabled only
9. Handrail wide only Both sides of all stairs flight
provision regardless of number of risers
d > 1000 both sides de
In additon Both sides
both
> 1000 provide a Any combination of above
sides > 1800 central
e
handrail

Above Min Max Above: Min Max Above Min Max Circulation/ Egress/ Both K (See across)
Pitch Pitch Pitch
10. Handrail line of 900 1000 line of 900 1000 line of 840 1000 No additional Ambulant disabled only
height flight flight flight requirements
M (See across)
Interme Interme Interme
diate 900 1100 diate 900 1000 diate 840 1100 Any combination of above
landing landing landing
Stairs should be
guarded at the
sides where the No additional requirements No additional Circulation/ Egress/ K (See
11. Guarding
total rise is > 600 requirements Ambulant disabled across)
mm. See 1.1.18 for
further details
12. Tactile
hazard Circulation/ Egress/ No
No requirements
warning Ambulant disabled requirements
surfaces
Adequate artificial B (See
All step nosing to incorporate Circulation/ Egress/ Both
lighting should be across)
permantly contrasting material on the M (See
13. Visibility No requirements provided Ambulant disabled only
tread. Illuminance at tread level to be across)
to all internal escape
at least 100 lux
routes (See 1.4.8) Any combination of above Both B & M
Notes:
a
Method of measurement as per Para B1.0.10(c) Methods of Measurement – Width “(iii) a stairway is the clear
width between walls or balustrades, (strings and handrails intruding not more than 30 mm and 100 mm
respectively may be ignored.”
b
In places of assembly to which large numbers of people have resort, there should be no more than two
consecutive flights each having a maximum of twelve risers, without a change in direction of at least 30
between flights;
c
Section 2 provides additional guidance on the minimum provisions for certain elements and features of existing
buildings where it is not practicable to achieve the provisions set out in Section 1.
d
If width between handrails > 2000 then divide stairs into channels not less than 1000 and not > 2000 mm.
e
In such a case the stairwaywidth on each side of the handrail needs to be considered separately for the
purpose of assessing stairway capacity.
f
Top and bottom landings should be level and at least as great as the smallest width of the flight determined by
Criteria 1.

5
Table 3 Dwellings

External Stairs Internal Stairs


*(See Notes 4 for Requirements of Part B Fire Safety) *(See Notes 1 to 3 for Requirements of Part B Fire Safety)
Building Part K Part K
Part M Part M
Regulations Stairways, Ladders, Stairways, Ladders,
Access and Use Access and Use
Requirements* Ramps and Guards Ramps and Guards
Where it is not practicable to
Application of Requirement K1 DOES NOT Where there is no habitable
provide the required level,
Building apply to steps or access room at entry level, the
gently sloped or ramped All internal stairs in a
routes outside a building stairway providing acess to
Regulations other than where steps are
approach to a dwelling dwelling must comply with
the storey containing the
and provision entrance from the point of Part K.
immediately outside the main living room should
of stairs. access, a stepped approach
external door of a building. comply with the following:
may be used.
Technical Guidance Document Technical Guidance Document
TGD M 2010 TGD M 2010
Criteria TGD K 2014 Section 3 TGD K 2014 Section 3
(Dwellings) (Dwellings)
1. Stairs width
(mm) 900 (min) between
(For landing 800 (min) between handrails 900 (min) between handrails 800 (min) between handrails
handrails
width see Note 5
below)
2. Max rise of
flight between 16 No. risers 1800 mm (max) 16 No. rises 1800 mm (max)
level landings
Optimum Max Optimum Max
3. Rise (R) 100 (min) to 150 (max) ≤ 175
175 220 175 220
Optimum Min Optimum Min
4. Going (G) ≥ 280 ≥ 280
250 220 250 220
5. Gait Optimum Min Max Optimum Min Max
No additional requirements No additional requirements
(2R+G) 600 550 700 600 550 700
Allowed subject to 16mm
(min) overlap of nosing &
6. Open risers 100mm (max) gap between
No additional requirements Allowed No additional requirements
treads
7. Tapered Avoid unless necessary Avoid unless necessary Avoid unless necessary Avoid unless necessary
treads (See 1.1.6) (See 3.1.2.5 (f)) (See 1.1.6) (See 3.3.2.2 (f))
6
8. Headroom 2000 (min) 2100 (min) 2000 (min) No additional requirements
Provide Provide
> 3 risers > 3 risers.
handrails Where > 3 continuous handrails
one side risers both sides one side Where 3 or more risers
9. Handrail ≤ 1000 ≤ 1000
only only; provide continuous
provision handrails handrail both sides
Where going
> 1000 both sides need not be > 1000 both sides
≥ 750
provided.
Above: Min Max Above: Min Max Above: Min Max Above: Min Max
Pitch line of Pitch line of Pitch line of Pitch line of
10. Handrail 900 1000 900 1000 900 1000 900 1000
flight flight flight flight
height Intermediate Intermediate Intermediate Intermediate
900 1100 900 1100 900 1100 900 1100
landing landing landing landing
Stairs should be guarded at Stairs should be guarded at
the sides where the total rise the sides where the total
11. Guarding is > 600 mm. See 1.1.18 for
No additional requirements
rise is > 600 mm. See
No additional requirements
further details 1.1.18 for further details
Notes:
1. For dwelling houses with no floors more than 4.5m above ground level (Purpose Group 1(a)) refer to 1.5.2 of TGD
B for additional considerations on stairway design.
2. For dwelling houses with one floor more than 4.5m above ground level (Purpose Group 1(b)) refer to 1.5.3 of
TGD B for additional considerations on stairway design.
3. For dwelling houses with more than one floor more than 4.5m above ground level (Purpose Group 1(b)) refer to
1.5.4 of TGD B for additional considerations on stairway design.
4. For Duplex dwellings, Purpose Group 1(c) refer to 1.3.9 of TGD B for specific requirements for external escape
stairs.
5. Top and bottom landings should be level and at least as great as the smallest width of the flight determined by
Criteria 1.
6. In the conversion of a loft where space is limited, headroom measured at the centre of the stairs should be not
less than 1.9 m but may reduce to not less than 1.8 m at the side of the stairs.

You might also like