Professional Documents
Culture Documents
1.0 Introduction
2.0 Purpose of this guidance
Stairs serve many different functions in
a building e.g. a mean of escape, a The choice of stairs is crucially
means of access for ambulant disabled dependent on the designers
people or an effective and simple understanding of the function of the
means of vertical circulation, or stairs under consideration i.e.
sometimes a combination of these. approach, access, circulation, egress or
Functional requirements and guidance any combination of these. This
on compliance for stairs are given in supplementary guidance document was
various Parts of the Building developed as a tool to assist building
Regulations namely: professionals readily determine some of
the key criteria of stairs design and
Part K (Stairways, Ladders, Ramps expresses the individuality of some of
and Guards) for stairs in general, the key stairs design criteria.
Part B (Fire Safety) for escape, and The Technical Guidance Documents
give guidance on minimum standards.
Part M (Access and Use) for stairs Those involved in the design and
suitable for ambulant disabled construction of buildings should have
people. also have regard to the principles of
Universal Design and consider making
Designers should refer to the relevant additional provisions where practical
Part and accompanying TGD when and appropriate.
designing stairs.
3.0 How to use the supplementary
Technical Guidance Document K guidance
(Stairways, Ladders, Ramps and
Guards) contains the primary The guide is presented in 3 tables.
guidance document on stairs design
in an overall sense when the stairs is Table 1 deals with external stairs
located within (or immediately outside a building other than a
outside) a building. dwelling.
1
Table 1 External stairs outside buildings (other than dwellings)
Part K
Stairways, Part M Part B
Ladders, Ramps Access and Use Fire Safety
and Guards
K1 Stairways, B1 Means of escape
Building ladders and ramps M1 Adequate provision shall be in case of fire
shall be such as to made for people to access and
Regulations afford safe passage use a building, its facilities and its B5 Access and
Requirements for the users of a environs. facilities for the fire Designer decision
building. service.
Where stairs are required below on
provided:
Design for vertical
function of stairs
Application of Requirement K1
Applies to:
escape;
Make provision for
under consideration.
Building
↓
DOES NOT apply to
Regulations 1. the approach route(s) to the people with
steps or access
relating to the accessible entrance(s) (Refer to disabilities;
routes outside a
1.1.2 of TGD M 2010 for the Provision for
provision of building other than
defined approach routes);
where steps are personnel access to
external 2. the circulation routes around a buildings for
steps/ stairs immediately outside
building (Refer to 1.1.2 for the firefighting.
outside a the external door of
defined circulation routes) Refer to Section 1.2.6
a building.
building: ‘External Escape
Routes’ of TGD B for
provision of external
g
escape stairways.
2
New Existing
Above: Min Max Min Max Min Max Egress K (See across)
build building
Pitch Pitch 100 Pitch Approach/ Access/
900 1000 900 840 1000
10. Handrail line line 0 line No additional Circulation
height Interme Interme
Interm requirements
M (See across)
110 ediate
d-iate 900 1100 diate 900 840 1100 Egress + any of above
0 landin
landing landing
g
Stairs should be
guarded at the sides No additional requirements No additional Approach/ Access/
11. Guarding where the total rise is > requirements Circulation/ Egress
K (see across)
600 mm. (See 1.1.18)
No
12. Tactile Egress
requirements
hazard Top & bottom landings Approach/ Access/
No requirements No requirements
warning Circulation M (See
surfaces across)
Egress + any of above
No
Adequate artificial Egress
All step nosing to incorporate permantly requirements
lighting should be
contrasting material on the tread. Approach/ Access/
13. Visibility No requirements
Illuminance at tread level to be at least
provided to all
Circulation M (See
external escape
100 lux across)
routes (See 1.4.8) Egress + any of above
Notes:
a
Method of measurement as per Para B1.0.10 Methods of Measurement – Width “(iii) a stairway is the clear width
between walls or balustrades, (strings and handrails intruding not more than 30 mm and 100 mm respectively may be
ignored.”
b
In places of assembly to which large numbers of people have resort, there should be no more than two consecutive
flights each having a maximum of twelve risers, without a change in direction of at least 30 between flights;
c
Section 2 provides additional guidance on the minimum provisions for certain elements and features of existing buildings
where it is not practicable to achieve the provisions set out in Section 1.
d
If width between handrails > 2000 mm then divide stairs into channels not less than 1000 mm and not > 2000 mm.
e
In such a case the stairway width on each side of the handrail needs to be considered separately for the purpose of
assessing stairway capacity.
g
External escape stairways should be sufficiently protected from the weather and is adequately protected from a fire in the
building (see 1.3.9 TGD B).
h
Top and bottom landings should be level and at least as great as the smallest width of the flight determined by Criteria 1.
3
Table 2 Internal stairs in buildings (other than dwellings)
Part K
Stairways, Part B
Part M
Ladders, Fire Safety
Access and Use
Ramps and
Guards
K1 Stairways, B1 Means of escape in
ladders and ramps M1 Adequate provision shall be case of fire
Building
Regulations
shall be such as to
afford safe
made for people to access and
use a building, its facilities and its B5 Access and facilities
Designer decision
Requirements
passage for the environs. for the fire service. required below on
users of a building.
function of stairs
Where stairs are
provided: under consideration.
Design for vertical
4
>3 Provide Provide
> 3 risers handrails
Circulation/ Egress/ Both B (See across)
risers handrails
≤ 1000 one side one side
≤ 1000 only
Ambulant disabled only
9. Handrail wide only Both sides of all stairs flight
provision regardless of number of risers
d > 1000 both sides de
In additon Both sides
both
> 1000 provide a Any combination of above
sides > 1800 central
e
handrail
Above Min Max Above: Min Max Above Min Max Circulation/ Egress/ Both K (See across)
Pitch Pitch Pitch
10. Handrail line of 900 1000 line of 900 1000 line of 840 1000 No additional Ambulant disabled only
height flight flight flight requirements
M (See across)
Interme Interme Interme
diate 900 1100 diate 900 1000 diate 840 1100 Any combination of above
landing landing landing
Stairs should be
guarded at the
sides where the No additional requirements No additional Circulation/ Egress/ K (See
11. Guarding
total rise is > 600 requirements Ambulant disabled across)
mm. See 1.1.18 for
further details
12. Tactile
hazard Circulation/ Egress/ No
No requirements
warning Ambulant disabled requirements
surfaces
Adequate artificial B (See
All step nosing to incorporate Circulation/ Egress/ Both
lighting should be across)
permantly contrasting material on the M (See
13. Visibility No requirements provided Ambulant disabled only
tread. Illuminance at tread level to be across)
to all internal escape
at least 100 lux
routes (See 1.4.8) Any combination of above Both B & M
Notes:
a
Method of measurement as per Para B1.0.10(c) Methods of Measurement – Width “(iii) a stairway is the clear
width between walls or balustrades, (strings and handrails intruding not more than 30 mm and 100 mm
respectively may be ignored.”
b
In places of assembly to which large numbers of people have resort, there should be no more than two
consecutive flights each having a maximum of twelve risers, without a change in direction of at least 30
between flights;
c
Section 2 provides additional guidance on the minimum provisions for certain elements and features of existing
buildings where it is not practicable to achieve the provisions set out in Section 1.
d
If width between handrails > 2000 then divide stairs into channels not less than 1000 and not > 2000 mm.
e
In such a case the stairwaywidth on each side of the handrail needs to be considered separately for the
purpose of assessing stairway capacity.
f
Top and bottom landings should be level and at least as great as the smallest width of the flight determined by
Criteria 1.
…
5
Table 3 Dwellings