PROCESS STORAGE TANK LAH & LAHH LEVEL CALCULATION

Parameter Value Unit

Tank Diameter [D] 14 feet

Tank Height [H] 18 feet 18.00 ft Overfill


Normal Liquid Level [NLL] 6 feet
𝝅𝑫𝟐 𝑯
Pump in Flow [QPump In] 250 USGPM 𝟒× 𝟕. 𝟒𝟖𝟎𝟓𝟐 × 𝟒 − 𝑸𝑷𝒖𝒎𝒑 𝑰𝒏 × 𝑻𝟏𝟓 𝒎𝒊𝒏 𝑰𝒏𝒍𝒆𝒕 𝑭𝒊𝒍𝒍 × 𝟎. 𝟏𝟑𝟑𝟔𝟖𝟏
𝟒 × 𝑽𝑶𝒗𝒆𝒓𝒇𝒊𝒍𝒍 𝒕𝒐 𝑳𝑨𝑯𝑯 𝑻𝒂𝒏𝒌 𝟒 × 𝟐𝟐𝟕𝟎
2,771 ft3 𝑳𝑨𝑯𝑯 𝑯𝒆𝒊𝒈𝒉𝒕 = = = = 14.74 ft LAHH
Total Volume of Tank [Vtotal] 𝝅 × 𝑫𝟐 𝝅× 𝑫𝟐 𝝅 × 𝟏𝟒𝟐
20,728 U.S Gallons

Time to fill from Overfill to LAHH 15 min

Tank flow in 15 minutes 3,750 U.S Gallons


𝝅𝑫𝟐 𝑯
16,978 U.S Gallons 𝟒× 𝟕. 𝟒𝟖𝟎𝟓𝟐 × 𝟒 − 𝑸𝑷𝒖𝒎𝒑 𝑰𝒏 × 𝑻𝟒𝟓 𝒎𝒊𝒏 𝑰𝒏𝒍𝒆𝒕 𝑭𝒊𝒍𝒍 × 𝟎. 𝟏𝟑𝟑𝟔𝟖𝟏
LAHH to Overfill Volume 𝟒 × 𝑽𝑶𝒗𝒆𝒓𝒇𝒊𝒍𝒍 𝒕𝒐 𝑳𝑨𝑯 𝑻𝒂𝒏𝒌 𝟒 × 𝟏𝟐𝟔𝟕
3
2,270 ft 𝑳𝑨𝑯 𝑯𝒆𝒊𝒈𝒉𝒕 = = = = 8.23 ft LAH
𝝅 × 𝑫𝟐 𝝅 × 𝑫𝟐 𝝅 × 𝟏𝟒𝟐
Liquid Alarm HH [LAHH] 14.74 ft

Time to fill from Overfill to LAH 45 min

Tank flow in 45 minutes 11250 U.S Gallons

9,478 U.S Gallons 6.00 ft NLL


LAH to Overfill
3
1267 ft

Liquid Alarm H [LAH] 8.23 ft Pump In Flow 250 USGPM

Summary 0.00 ft Tank Bottom


Liquid Alarm HH [LAHH] 14.74 ft

Liquid Alarm H [LAH] 8.23 ft 14 ft


LAH to NLL 2.23 ft

Legend Input Data

Output Data

Terminology Description Remarks

LAHH Liquid Alarm High-High Initiates Tank Inlet Flow Shutdown

LAH Liquid Alarm High Alerts The Operator

NLL Normal Liquid Level Intended Operating Liquid Level