Panel Board Schedule for /3/ CHILLERS


PANEL TAG : MDB 1 MAINS:4000 AT / 4000 AF, 380 / 220 V, 4W NEUTRAL: YES
LOCATION : MAIN ELEC. ROOM MOUNTING: FREE STANDING GROUND : YES
ENCLOSURE: IP54
VA VA VA P P VA VA VA
CABLE C O CT.
R Y B CT. O C CABLE
L L
LOAD [mm²] B NO NO B [mm²] LOAD
R Y B E E
R Y B
155000 1 2 102000

CH (01/CKT01) 155000 2*(3Cx300)+300 E 1000 3P 3 4 3P 800 2*(3Cx185)+185 E 102000 CH (01/CKT02)

155000 5 6 102000

155000 7 8 102000

CH (02/CKT01) 155000 2*(3Cx300)+300 E 1000 3P 9 10 3P 800 2*(3Cx185)+185 E 102000 CH (02/CKT02)

155000 11 12 102000

155000 13 14 102000

CH (03/CKT01) 155000 2*(3Cx300)+300 E 1000 3P 15 16 3P 800 2*(3Cx185)+185 E 102000 CH (03/CKT02)

155000 17 18 102000

19 20

SPARE 1000 3P 21 22 3P SPACE

23 24

TOTAL LOAD KVA TOTAL LOAD KVA


TOTAL CONNECTED LOAD KVA
465,000 465,000 465,000 771,000 771,000 771,000 0 306,000 306,000 306,000

C.LOAD 2,313.00 KVA


BUS BAR RATE : 4000A
REQUIRED AMPERE 4217 A D.FACTOR 1 %
MAIN MCCB : 4000A
STANDARD TRANSFERMOR 2500 KVA D.LOAD 2313.00 KVA 40 KA
SHORT CIRCUIT LEVEL :
TRANSFERMOR LOAD RATE 0.93 % D.AMPS. 3514.34 AMP.
Client :

Panel Board Schedule for /3/ CHILLERS


PANEL TAG : MDB 2 MAINS:4000 AT / 4000 AF, 380 / 220 V, 4W NEUTRAL: YES
LOCATION : MAIN ELEC. ROOM MOUNTING: FREE STANDING GROUND : YES
ENCLOSURE: IP54
VA VA VA P P VA VA VA
CABLE C O CT. CT. O C CABLE
[mm²] B L NO R Y B NO L
B [mm²]
LOAD LOAD
R Y B E E
R Y B
155000 1 2 102000

CH (04/CKT01) 155000 2*(3Cx300)+300 E 1000 3P 3 4 3P 800 2*(3Cx185)+185 E 102000 CH (04/CKT02)

155000 5 6 102000

155000 7 8 102000

CH (05/CKT01) 155000 2*(3Cx300)+300 E 1000 3P 9 10 3P 800 2*(3Cx185)+185 E 102000 CH (05/CKT02)

155000 11 12 102000

155000 13 14 102000

CH (06/CKT01) 155000 2*(3Cx300)+300 E 1000 3P 15 16 3P 800 2*(3Cx185)+185 E 102000 CH (06/CKT02)

155000 17 18 102000

19 20

SPARE 1000 3P 21 22 3P SPACE

23 24

TOTAL LOAD KVA TOTAL LOAD KVA


TOTAL CONNECTED LOAD KVA
465,000 465,000 465,000 771,000 771,000 771,000 0 306,000 306,000 306,000

C.LOAD 2,313.00 KVA


BUS BAR RATE : 4000A
REQUIRED AMPERE 4217 A D.FACTOR 1 % 4000A
MAIN MCCB :
STANDARD TRANSFERMOR 2500 KVA D.LOAD 2313.00 KVA
SHORT CIRCUIT LEVEL : 40 KA
TRANSFERMOR LOAD RATE 0.93 % D.AMPS. 3514.34 AMP.
Client :

Panel Board Schedule for /2/ CHILLERS & Service Panels


PANEL TAG : MDB 3 MAINS: 3200 AT / 3200 AF, 380 / 220 V, 4W NEUTRAL: YES
LOCATION : MAIN ELEC. ROOM MOUNTING: FREE STANDING GROUND : YES
ENCLOSURE: IP54
VA VA VA P P VA VA VA
CABLE C O CT. CT. O C CABLE
[mm²] B L NO R Y B NO L
B [mm²]
LOAD LOAD
R Y B E E
R Y B
155000 1 2 102000

CH (07/CKT01) 155000 2*(3Cx300)+300 E 1000 3P 3 4 3P 800 2*(3Cx185)+185 E 102000 CH (07/CKT02)

155000 5 6 102000

155000 7 8 102000

CH (08/CKT01) 155000 2*(3Cx300)+300 E 1000 3P 9 10 3P 800 2*(3Cx185)+185 E 102000 CH (08/CKT02)

155000 11 12 102000

23000 13 14 16000
Lighting & Power Panel Lighting & Power Panel
LPP1 23000 (4Cx50)+25 E 160 3P 15 16 3P 100 (4Cx35)+16 E 16000 LPP2
23000 17 18 16000

21000 19 20 25000
A/C Panel for Pumps
Work Shops Power Panel 21000 (4Cx95)+50 E 200 3P 21 22 3P 200 (4Cx95)+50 E 25000
Room
21000 23 24 25000

25 26

Spare 160 3P 27 28 3P Space

29 30

TOTAL LOAD KVA TOTAL LOAD KVA


TOTAL CONNECTED LOAD KVA
354,000 354,000 354,000 599,000 599,000 599,000 0 245,000 245,000 245,000

C.LOAD 1,797.00 KVA


BUS BAR RATE : 3200A
REQUIRED AMPERE 3276 A D.FACTOR 1 % 3200A
MAIN MCCB :
STANDARD TRANSFERMOR 2000 KVA D.LOAD 1797.00 KVA 33 KA
SHORT CIRCUIT LEVEL :
TRANSFERMOR LOAD RATE 0.90 % D.AMPS. 2730.34 AMP.
Client :

Panel Board Schedule for /2/ Sets of Pumps


PANEL TAG : Pumps Panel MAINS: 3200 AT / 3200 AF, 380 / 220 V, 4W NEUTRAL: YES
LOCATION : MAIN ELEC. ROOM MOUNTING: FREE STANDING GROUND : YES
ENCLOSURE: IP54
VA VA VA P P VA VA VA
CABLE C O CT. CT. O C CABLE
[mm²] B L NO R Y B NO L
B [mm²]
LOAD LOAD
R Y B E E
R Y B
58800 1 2 58800

SCHWP 01 58800 (4Cx240)+120 E 400 3P 3 4 3P 400 (4Cx240)+120 E 58800 SCHWP 02

58800 5 6 58800

58800 7 8 58800

SCHWP 03 58800 (4Cx240)+120 E 400 3P 9 10 3P 400 (4Cx240)+120 E 58800 SCHWP 04

58800 11 12 58800

58800 13 14 58800

SCHWP 05 58800 (4Cx240)+120 E 400 3P 15 16 3P 400 (4Cx240)+120 E 58800 SCHWP 06

58800 17 18 58800

58800 19 20 58800

SCHWP 07 58800 (4Cx240)+120 E 400 3P 21 22 3P 400 (4Cx240)+120 E 58800 SCHWP 08

58800 23 24 58800

128000 25 26
Primary Pumps Main
Circuit Breaker 128000 2*(4Cx185)+185 E 800 3P 27 28 3P 400 Spare

128000 29 30

TOTAL LOAD KVA TOTAL LOAD KVA


TOTAL CONNECTED LOAD KVA
363,200 363,200 363,200 598,400 598,400 598,400 0 235,200 235,200 235,200

C.LOAD 1,795.20 KVA


BUS BAR RATE : 3200A
REQUIRED AMPERE 3273 A D.FACTOR 1 % 3200A
MAIN MCCB :
STANDARD TRANSFERMOR 2000 KVA D.LOAD 1795.20 KVA 40 KA
SHORT CIRCUIT LEVEL :
TRANSFERMOR LOAD RATE 0.90 % D.AMPS. 2727.60 AMP.