PROPOSED PROJECT: TWO-STOREY, THREE-UNIT RESIDENCE

LOCATION: YAKAL ST., PHASE 4, MARCELO GREEN VILLAGE, PARAÑAQUE CITY


OWNER: MS. TIA ROSE C. PERFECTO / MR. DON SANTIAGO C. PERFECTO / MR. JUNO C. PERFECTO

DESIGN OF COLUMN:
CONCRETE COLUMN (C1):
Material Strengths:
fc' = 21 Mpa DL = 139.12 KN
fy = 276 Mpa LL = 90.84 KN
Constant: *inclusive of wind and/or seismic load
Φ = 0.7
Pg = 0.01 to 0.08
Try Pg = 0.025

Axial Load:
Pu = 312.29 KN

Compute Ag:
Pu
Ag =
Φ (0.80) [0.85 fc' (1 - Pg) + fy Pg]

312.288(1000)
Ag =
0.7(0.8)[0.85(21)(1 - 0.025) + (276)(0.025)]

Ag = 22945.31267221 mm

Compute b: Check Pg:


b2= Ag As = (π/4)(d2)N
b = / Ag As = (π/4)(16)(16)(8)
b = /22945.313 As = 1608.50
b = 151 mm = say 150 mm
As
Pg =
Try: 150 mm x 350 mm Ag
1608.5
Pg =
Ag = 150mmx350mm 52500
Ag = 52500.00 mm^2 0.01 < Pg = 0.0306 < 0.08
OK!
Compute As:
As = Pg Ag Spacing of tie wires: 200mm O.C.
As = 0.025(52500)
As = 1312.50 mm2 Check Allowable Pu:
Pu = Φ (0.80) [0.85 fc' (Ag - As) + fy As]
Compute No. of bar (N):
Try: 16 mm dia. bar Pu = 0.7(0.8)[.85(21)(62500 - 1884.96) + 276(1884.96)]
No. of bars: 8 pieces
Pu = 757.32 KN > 312.29 KN
SAFE!