Safety Technique

SAFEMASTER S
Standstill Monitor
LH 5946

Your Advantages
• Without sensor and safe
• Fast reaction time
• Easy to retrofit
0255161

• Combined with Interlock SAFEMASTER STS

Features
• According to
- Performance Level (PL) e und category 4 to EN ISO 13849-1: 2008
- SIL-Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• Safe standstill detection on 3- and single-phase motors
• No external sensors necessary
• Independent of direction
• Broken wire detection
• Forcibly guided safety contacts:
Function Diagramm 3 NO contacts, 1 NC contact for AC 250 V
• 2 semiconductor monitoring outputs
• 1 monitoring output (NO contact)
• Adjustable voltage setting
auxiliary voltage on

• Adjustable standstill time delay


standstill detected

motor runs down


motor runs down

• LED indicators for standstill, event of line breakage and


line breakage

line breakage

reset X3-X2
reset X3-X2

operation voltage
Motor Ein
motor on

• Suitable for operation with inverters


stop

• Width 45 mm
UH

A1/A2 t Approval and Markings


motor speed /
voltage voltage level
L1/L2/L3 Uan

Canada / USA A025518


line breakage
L1/L2/L3 Applications

23-24 Safe standstill detection on 3- and single-phase motors, e.g. to enable gate
33-34 interlocks on machine tools or to activate hold in brakes.
43-44
53-54
A3-ON Function

The Standstill monitor LH5946 is suitable to monitor the standstill of all


11-12
electric motors that generate a remanence voltage while coasting to stop.
The LH 5946 is connected to the motor terminals and measures the induced
back emf voltage. 2 redundant measuring channels are used (L2-L1 and
tE tE
A3-ERR L3 L1). If the back emf voltage drops to 0 simultaneously in both channels
standstill delay time ts this indicates standstill and the output relay is energized.
M9647_b
tE=2...2,5s To adopt the unit to all different types of motors and applications the
start up delay time UH
voltage threshold indicating standstill on LH 5946 is adjustable. Also the
time delay between detection and energisation of the relay is adjustable
(standstill time ts).
In addition the unit detects broken wire on the measuring inputs
Flashing Codes L1 / L2 / L3. If broken wire is detected the output relays goes into safe state
(as with running motor). This state is stored and can be reset by bridging
terminals X3-X2.
undervoltage
at UH The input signals of both channels are permanently compared. If the signals
are different for more then 2.5 sec a simultaneity failure is detected. This
wire-break/offset failure resets when both input channels receive simultaneous signals with
on L2
a level, above the voltage threshold and hysteresis.
wire-break/offset To the terminals X1-X2 the feedback circuit of external contactors (used
on L3 for contact reinforcement) is connected (NC contact). If no feedback circuit
is required, these terminals must be linked. Open terminals will cause a
failure in feedback failure message.
circuit X1-X2

simultaneity failure Notes


signal L2/L3
The terminals X1 - X2 - X3 has no galvanic separation to the measuring
potentiometer error ciruit L1 - L2 - L3. They must be controlled with volt free contacts.
Uan

potentiometer error
ts

t M9648_c

Flashing codes of the LED „ERR“ in sequence of priority


All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time. 1 09.12.15 en / 619
Circuit Diagram Technical Data

Input (L1 - L2 - L3)


53 54 L1 L2 L3

X1 X2 X3 11 23 33 43
Measuring-/Motor voltage: max. AC 690 V
Input resistance: 500 kΩ
11 23 33 43 53 A3+ Response value Uan: 20 mV ... 400 mV, adjustable or
K1 0.2 ... 4 V, adjustable

K2 Response value dependent on frequency


Input frequency (Hz): 50 100 200 400 600 1k 1,5 k 2k
12 24 34 44 54 A4 ON ERR
Multiplication factor for Uan: 1,0 1,1 1,2 1,5 2,0 2,8 5 8
12 24 34 44

A3 A4 ON ERR Hysteresis (for detection


A1 A2
+ of running motor): 100 %
M9163_d Release delay for detection
of running motor: < 100 ms
Standstill time delay ts: 0.2 ... 6 s adjustable
Connection terminals
Auxiliary voltage UH
Terminal designation Signal designation (A1 - A2): AC 115 V, AC 230 V, AC 400 V, DC 24 V
L1 - L2 - L3 Connection to monitored motor Recommended fusing: 2A
11 - 12 Safety contacts (NC) Voltage range
AC: 0.8 ... 1.1 UN
23 - 24, 33 - 34, 43 - 44
Safety contacts (NO)
DC: 0.9 ... 1.2 UN
53 - 54 Monitoring contact (NO) Nominal consumption: 5 VA, 3W
Connection of feedback circuit Nominal frequency (AC): 50 / 60 Hz
X1 - X2
(for external contactors) Frequency range (AC): 45 ... 65 Hz
X2 - X3 Manual reset for external faults max. residual ripple (DC): 10 %
Start up delay when
A1 - A2 Auxiliary supply (UH)
connecting UH at standstill: 0,4 ... 0,8 s + adjustable ts
A3(+) - A4 Supply for semiconductor outputs
ON: Semiconductor output indicates state Output
of safety contacts
ERR: Semiconductor output indicates failures Contacts
(saftey contacts)
Attention: The outputs 53-54, ON and ERR are only monitoring out-
LH 5946.48: 3 NO contacts, 1 NC contact
puts and must not be used in safety circuits!
Contact type: relay, positive guide
Nominal output voltage: AC 250 V
Thermal current Ith: 5 A (bis 40°C)
Indicators Quadratic total current: see derating curve
Switching capacity
green-red LED „UH“: green on, when operation to AC 15
red on, with internal error
NO contact: 3 A / AC 230 V IEC/EN 60 947-5-1
yellow-green LED „OUT“: yellow on, at EMK > Uan NC contact 2 A / AC 230 V IEC/EN 60 947-5-1

flashes green at time progression of ts to DC 13

permanent on, when output contacts NO contact: 1 A / DC 24 V IEC/EN 60 947-5-1
are enable NC contact 1 A / DC 24 V IEC/EN 60 947-5-1
red LED „ERR“: flashes at error in measuring and to DC 13
feedback circuit and low auxiliary NO contact: 4 A / 24 V at 0.1 Hz IEC/EN 60 947-5-1
voltage UH (see flashing codes) NC contact 4 A / 24 V at 0.1 Hz IEC/EN 60 947-5-1
Fusing of the
safety contacts: max. fuse rating 4AgL
line circuit breaker C6A
Max. operating frequency: 1200 / h
Contact service life
at AC 230 V / 5 A cosϕ = 0.5: ≥ 2 x 105 switching cycles
Mechanical life: ≥ 50 x 106 switching cycles

Semiconductor monitoring
output: 100 mA DC 24 V, plus switching,
galvanic separation; supply via
A3+ / A4 for output; „ON“ and „ERR“
NO monitoring contact: 3 A AC 250 V (closed when enabled)

2 09.12.15 en / 619
Technical Data Technical Data
General Data Safety Related Data

Nominal operating mode: continuous operation Values according to EN ISO 13849-1:


Temperature range Category: 4
operation: - 25 ... + 60°C PL: e
(+ 40°C with max. contact current, MTTFd: 93 a
see Derating) DCavg: 99.0 %
dop: 365 d/a (days/year)
storage: - 40 ... + 75°C
hop: 24 h/d (hours/day)
Altitude: < 2.000 m
tZyklus: 28.8E+03 s/Zyklus
Clearance and creepage distance = 1 /8 h (hours)
rated impulse voltage / pollution degree: IEC 60 664-1
Contacts 11/12, 23/24, Values according to IEC/EN 62061 / IEC/EN 61508 / IEC/EN 61511:
33/34, 43/44 against all others: 6 kV / 2 SIL CL: 3 IEC/EN 62061
Contacts 11/12, 23/24, SIL 3 IEC/EN 61508 /
33/34, 43/44 against each others: 4 kV / 2 IEC/EN 61511
Indicator contact 53/54 HFT*): 1
against all others: 4 kV / 2 DCavg: 99.0 %
SFF 99.7 %
Semiconductor outputs A3+/
PFHD: 4.10E-10 h-1
ON / ERR / A4 against all others: 6 kV / 2
PFD: 1,42E-04
Auxiliary voltage A1 / A2 T1: 20 a (year)
against all others
at auxiliary voltage AC: 6 kV / 2 *)
HFT = Hardware-Failure Tolerance
at auxiliary voltage DC: 4 kV / 2
Control terminal X1 / X2 / X3: no galvanic separation to L1 / L2 / L3 The values stated above are valid for the standard type.
EMC IEC/EN 62 061 Safety data for other variants are available on request.
Interference suppression: limit value class B EN 55 011 nfo The safety relevant data of the complete system has to be
Degree of protection
determined by the manufacturer of the system.
Housing: IP 40 IEC/EN 60 529
Terminals: IP 20 IEC/EN 60 529
Enclosure: thermoplastic with VO behaviour
according to UL subject 94
Vibration resistance: amplitude 0.35 mm
frequency 10 ... 55 Hz, IEC/EN 60 068-2-6 UL-Data
Climate resistance: 25 / 060 / 04 IEC/EN 60 068-1
The safety functions were not evaluated by UL. Listing is accom-
Terminal designation: EN 50 005
plished according to requirements of Standard UL 508, “general use
Wire connection DIN 46 228-1/-2/-3/-4 applications”
UL detail: 60°C Copper conductors only
Screw terminals Auxiliary voltage UH
(integrated): 1 x 4 mm2 solid or for DC 24 V: Device must be supplied with a Class 2 or
1 x 2.5 mm2 stranded ferruled or a voltage / current limited power supply
2 x 1.5 mm2 stranded ferruled or (max. 4 A).
2 x 2.5 mm2 solid Measuring-/Motor voltage: max. AC 600 V
Insulation of wires
or sleeve length: 8 mm Ambient temperature: - 25 ... + 60°C, (+ 40°C with max. contact
Plugin with screw terminals current, see Derating)
max. cross section Switching capacity
for connection: 1 x 2.5 mm2 solid or safety contacts
1 x 2.5 mm2 stranded ferruled (11/12, 23/24, 33/34, 43/44)
Insulation of wires Ambient temperature 40°C: Pilot duty B300
or sleeve length: 8 mm 5A 250Vac G.P.
Plugin with cage 5A 24Vdc G.P.
clamp terminals
Ambient temperature 60°C: Pilot duty B300
max. cross section
2A 250Vac G.P.
for connection: 1 x 4 mm2 solid or 2A 24Vdc G.P.
1 x 2.5 mm2 stranded ferruled
min. cross section Switching capacity
for connection: 0.5 mm2 indicator contact (53/54) 3A 250Vac G.P.
Insulation of wires Wire connection: 60°C / 75°C copper conductors only
or sleeve length: 12 ±0.5 mm Fixed screw terminal: 1 x AWG 20 - 12 Sol/Str Torque 0.8 Nm or
Wire fixing: Plus-minus terminal screws M 3.5 2 x AWG 20 - 14 Sol/Str Torque 0.8 Nm
box terminals with wire protection or
Plugin screw terminal: AWG 20 - 14 Sol Torque 0.8 Nm or
cage clamp terminals
AWG 20 - 18 Str Torque 0.8 Nm
Mounting: DIN-rail IEC/EN 60 715

Weight: approx. 400 g Plugin cage clamp terminal: AWG 20 - 12 Sol/Str
Dimensions Technical data that is not stated in the UL-Data, can be found
in the technical data section.
Width x height x depth: 45 x 90 x 121 mm nfo

EAC-Data

Auxiliary voltage UH: DC 24V



Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo

3 09.12.15 en / 619
Standard Type Characteristic

LH 5946.48/61 20 ... 400 mV UH DC 24 V 0.2 ... 6 s 2


 I (A )
2

Article number: 0059266


80
• Safety output: 3 NO contacts, 1 NC contact
• Response value Uan: 20 ... 400 mV 70
• Auxiliary voltage UH: DC 24 V 60
• Standstill time ts: 0.2 ... 6 s 50
• 1 semiconductor and 1 NO contact for indicator output
40
• 1 semiconductor for fault indicator output
• Width: 45 mm 30

20
Ordering Example 10

LH 5946.48 _ _ 61 20 ... 400 mV UH DC 24 V 0.2 ... 6 s T (° C)


0 10 20 30 40 50 60

Standstill time ts Quadratic total current M9658


2 2 2
 = I1 + I2 + I3
Auxiliary voltage UH
I1 , I2 , I 3 - current in contact paths
Response value Uan
max. permitted current up to 40°C on 3 contact paths = 5A
UL-approval
(5 +5 +5 = 75A )
2 2 2 2

Type of terminals max. permitted current up to 60°C on 3 contact paths = 2A


without indication:
(2 +2 +2 = 12A )
2 2 2 2

terminal blocks fixed,


with screw terminals Derating curve for contact currents of safety contacts

PC (plugin cage clamp)


pluggable terminal blocks
with cage clamp terminals
PS (plugin screw)
pluggable terminal blocks
with screw terminals
Type

Options with Pluggable Terminal Blocks


M4313_a

M4314_a

Screw terminal Cage clamp terminal


(PS/plugin screw) (PC/plugin cage clamp)

Notes

Removing the plugin terminal blocks

1. The unit has to be disconnected.


2. Insert a screwdriver in the side recess of the front plate.
3. Turn the screwdriver to the right and left.
4. Please note that the terminal blocks have to be mounted on the
belonging plug in terminations.
M4105_a

4 09.12.15 en / 619
Application Examples

PE L1 L2 L3 PE N L

motor contactor motor contactor

L L

A1 11 23 33 43 53 A3+ A4 A1 11 23 33 43 53 A3+ A4
L1 X1 K4 L1 X1 K4
L2 X2 L2 X2
LH5946 LH5946
L3 K5 L3 K5
X3 X3

A2 12 24 34 44 54 ON ERR A2 12 24 34 44 54 ON ERR

K4 K5 K4 K5

N N
M M
3~ M9649_b 1~ M9650_b

With 3-phase motor; suitable up to SIL3, Performance Level e, Cat. 4 With single-phase motor; suitable up to SIL3, Performance Level e, Cat. 4

L1
L2
L3

F2 F1

Entriegelung
Unlock K4
Déverrouillage

Auf
Open On
Ouvert K4

Not-Aus Off
E-Stop
Arrêt d'urgence

A1 S11 S12 S22 13 23 33 41 A1 11 23 33 43 L1 L2 L3

53 M
Not-Aus-Modul K4 Stillstandswächter 3
E-Stop-Modul Stand-Still-Monitor
Module d'arrêt d'urgence Détecteur de vitesse zéro X1
LG5925 54 LH5946
X2

S21 S33 S34 14 24 34 42 A2 A3 ON ERR A4 12 24 34 44 A2


+

*
+24V E0 E1 ... Meldung an * optional
* übergeordnete
SPS / PLC / API Steuerung
Signal to SPS
N
Signalisation à la
Meldelampe M9165_f
commande supérieure
Signal lamp
Lampe de signalisation

Typical connection combination with E-Stop; suitable up to SIL3, Performance Level e, Cat. 4

5 09.12.15 en / 619
Application Examples

L1
L2
L3

fuse

main switch

N
F
F

off

N on
U1 V1 W1
17 M
27 A1 23 33 L1 L2 L3 3~
N BC7936N d
W2 U2 V2
18 28 X1 K4
LH5946 X2
K5
A1 A2 24 34
K4 K5
N d
A2
N
M9967_a

d = star delta timer


N = mains contactor
= star-contactor
= triangle contactor

Typical connection combination with star delta timer, 2-channel connection of the measuring inputs; suitable up to SIL3, Performance Level e, Cat. 4

L1
L2
L3

fuse

main switch

N
F
F

off

N on
U1 V1 W1
17 M
27
BC7936N

A1 23 33 L1 L2 L3 3~
N d
W2 U2 V2
18 28 X1 K4
LH5946 X2
K5
A1 A2 24 34
K4 K5
N d
A2
N
M9969_a

d = star delta timer With “3-phase” connection of LH5946 the star contactor ( )
N = mains contactor has to be closed after the motor is switched off to detect standstill.
= star-contactor If this is not the case the failure signal “broken wire” blocks
= triangle contactor the output contacts in off posisition.

Typical connection combination with star delta timer, 3-channel connection of the measuring inputs; suitable up to SIL3, Performance Level e, Cat. 4

E. DOLD & SÖHNE KG • D-78114 Furtwangen • PO Box 1251 • Telephone (+49) 77 23 / 654-0 • Telefax (+49) 77 23 / 654-356
e-mail: dold-relays@dold.com • internet: http://www.dold.com 6 09.12.15 en / 619