Professional Documents
Culture Documents
Thb ~ w pmpmd for pmaonlntion M the 1S93 SPE/lAOC Dfllllw Coalefance held in Amsterdam 23-25 Februaw 1993. I
Ilmabl, n Pmanm, - fW n.cw$mlti twikcl MV rxmitkm of tha WE or WOC, ltmk oltkml. w nwmbefs, Paows c.f-&cnted w SPE/lADC rneelimasam sibiect to nublkatkm i
359
2 HARQ OR SOFf’ SHUT-IN : WHICH IS THE BEST APPROACH ? ~PE 25712
accurate anmdus pressure readings. In addition there 255 kPa (37 psi). A further pressure pulse would,
are complexities in physically performing the initial however, be produced on closure of the choke.
shut-in procedure which differ from one method to
the other. Simplifying the task minimises the risk of
human error. This, coupled with the primary concern In reality BOPS do not close instantly. If the effective
for the sal’etyof personnel and rig, have encouraged closure time is larger than the pressure wave round
many opexators and contractors to elect for the hard trip in the well, then theoretical considerations [2]
shut-in procedure as their well control policy for show that the expected maximum pulse amplitude is
shutting in a well. given approximately by the relation:
To try and resolve the hard or soft shut-in issue, a AP~= = APln, & . .. ...... ... ... .. ... ... .. .... .. .. ..(2)
series of tests have been conducted using a 1430m
test well and full-scale drilling rig equipped with
complete surface instrumentation as well as .
downhole temperature and pressure measurements. where APlm is the maximum pressure for
The shut-in tests formed part of a suite of instantaneous BOP closure as calculated using
experiments to obtain accurate and detailed data for equation (1), tr is the pressure wave round-trip time
kick simulators which are currently under (i.e. the time taken for the pressure wave to travel
development. Consequently it was important that down the well, reflect at the bottom and travel back
experimental conditions were as close to true to surface) and Tc is the effective BOP closure time.
operational conditions as possible. Test nxults along
with supporting theory are presented to give
improved understanding of the issues involved. Effect of BOP closure time
WATER HAMMER In practice equation (2) signifies that for BOP closure
times greater than the pressure wave round trip time,
the water hammer pulse amplitude is reduced due to
“Water hammer” is a general term describing pressure reduction caused by the upward traveling
pressure wave generation and propagation through wave, The effective BOP closure time is defined as
liquids in pipes and pipe networks. It can be the time taken from the start of pressu~ build at the
observed in domestic water systems, where if a valve BOP until a seal is formed at the drillpipe. For the
or tap is closed rapidly a bang can be heard from the experiments described in this paper, there was
pipes throughout the entire system. estimated to be a measurable pressure drop at the
BOP for 5 seconds while the pressure rise in the
If the BOP on a flowing well is closed rapidly then a hydraulic system lasted for approximately 10
pressure wave is produced and this propagates down seconds. The effective estimated closure time for
the well. In this section we calculate the likely these tests was therefore taken to be 5 seconds. In
pressure changes during a hard and soft shut-in. If the case above, for a 1400 m well, this would reduce
the BOP closes instantly and the flow stops the 120 psi pressure pulse to 50 psi.
completely the pressure rise, AP, is:
Provided that the effective BOP closure time exceeds
the traveling wave round trip time, there is expected
AP = f)CU, .. . . . . . . . . . . . .. . . . . . . . . .. . . . . . .. . . . . . . .. . . . . . (1) m be significant reduction in the pressure wave
amplitude due to the upwards reflected pressure
- where p is the mud density, c the wave speed wave for most field situations. Typical field annular
preventers take 30-60 seconds for pressure build in
through the mud and u, the initial mud velocity. the hydraulic system so 10 seconds is taken to be a
The derivation of this equation is discussed in the conservative estimate for “Tc”. Using a pressure
appendix and illustrated in Figure 1, For a typical wave velocity of 1350 m/s, as derived in the
kick with an influx rate of 0.014 m 3/s (5.5 Bbl/min) appendix, indicates that equation (2) is valid for hole
in 9~in casing his produces a pressure wave of depths up to 6700 m.
amplitude 827 kPa (120 psi). If the choke remains
open and fluid continues to tlow after the BOP is Although normally there is a significant reduction in
shut, the pressure jump is reduced. The size of the water hammer pressure due to the presence of an
reduction is a function of the choke line length, upward retlected pressure wave as in the tests
diameter and geometry. For the case of a 50 m long, described in this paper, it is possible to conceive of a
0.077m diameter line the pmsure wave is reduced to BOP closure where the effective inc~ase in pressure
. .
SPE 25712 S.1. JARDINE, A.B. JOHNSON, D.B. WHITE AND W. STIBBS 3
drop occurs on a short time scale compared to the later the kick is detected the more rapidly the well is
wave round-trip time. In such a case, a water- flowing and the time delay between the two methods
hammer pulse will be produced of amplitude given would lead to larger pit gain and pressure
by equation (1); there behg no significant attenuation differences. A soft shut-in therefore leads to higher
as described by equation (2). For this situation, pressures during shut-in and during the subsequent
however, there is still no benefit in using a soft shut- well control operation.
in as the water-hammer pulse will then merely be
delayed until the choke valve is closed as eflective EXPERIMENTAL DESCRIPTION
closure of the choke is normally at least as rapid as
closure of the BOP,
The 1430m experimental test well which was used
for the experimental test of shut-in procedure is
IMPLICATIONS OF SHUT-IN METHOD
described in Table 3 and illustrated in Figure 3. The
ON PIT GAIN AND CHOKE PRESSURE outer annulus contained lin (0.0254m) coiled tubing
to allow nitrogen injection and to give access to
Use of a soft rather than a hard shut-in can have cabling for pressure and temperature sensors at the
significant impact on the final volume of influx and bottom and mid-point of the well. The usual rig
subsequent casing “shoe” pressures. A gas kick measurements of surface pressures and pit gain were
simulator [3] was used to investigate the effect on the recorded. A unique feature of the experiments was
influx and subsequent annulus pressure for a change the inclusion of the following downhole
in the shut-in procedure from soft to hard. A 3048 m measurements:
(10,000 ft) well was modeled with the scenario of
drilling ahead to the 9 5/8 in (0.244 m) casing point (1) Shoe presswe and temperature at 708m.
when an overpressured formation was entered. The
full well details used by the simulator are given in (2) Bit presstue and temperature at 1430m.
Table 1.
Test Procedure
The kick detection threshold was set at 10 bbls (1.6
m 3) for both the soft and hard shut-ins, At kick The real influx flow-rate during a kick would be
detection both shut-ins followed the same pump described by the behaviour of the producing
ramp down routine and then a short flow check. formation. To simulate the expected behaviour of a
After the flow check the two processes start m differ formation during the kick tests, the nitrogen injection
as the HCR valves (failsafes) have to be opened prior rate at surface was controlled in a manner to produce
to actuating the annular preventer in the soft shut-in, the expected influx behaviour downhole. For the
but both actions am carried out concurrently in the tests described here, the formation was modeled to
hard shut-in. The time break downs are in Table 2. have permeability “K” of 100mD (9.87E-14 mz) and
The total time figures show that the extra time taken overpressure of 200psi (1.38 MPa). The downhole
by the soft shut-in route is estimated to he 50 flow-rates in the coiled tubing were related to the
seconds, although this may be greater in some cases. imposed surface flow-rates using a numerical
simulator which modeled the injection gas dynamic
Two separate model runs were carried out with the behaviour and frictional loss m the coiled tubing.
same well and rig details but with the time break This enabled predefine tlow schedules for the
downs being changed from one run to the next. The nitrogen injection to be calculated.
model estimates both the pit gain and the well-bore
pressures during the kick, after the well hits been For both the hard and soft shut-in experiments, the
closed in and during the well control phase. The surface nitrogen pressure was increased using the
results for the pit gain and for the choke line pressure predefine injection schedule so as to introduce 10
were investigated and plotted in Figure 2. The soft bbl (1.6 m~) of nitrogen at the bottom of the well,
shut-in run can be seen to have produced a higher pit The annular preventer was then closed and the
gain and a higher choke line pressure than the hard nitrogen flow-rate was brought to zero at an
shut-in. The pit gain was 1.8 bbl (0.3 m~) or 12.5% exponential decay rate to simulate continued flow
more for the soft shut-in than for the hard shut-in. from the formation until this is overcome by the
The maximum choke line pressure, whilst the well incwase in bottom hole pressure after shut-in.
was shut in for a 15 minute period, was 60 psi or
10% higher for the soft shut-in, Both of these
differences would be further increased if there were For each test, the following procedure was carried
either a greater time difference between the two out :
methods or a longer delay in detecting the kick. The
361
.
SPE 25712 S.1. JARDINE, A.B. JOHNSON, D.B. WHITE AND W. STIBBS 5
on the 150 psi (1.03 MPa) pressure rise associated ● They am much smaller than the stabilised shut-in
with stabilisation of bottom hole pressure. pressures when the influx ceases.
Detailed calculations for the expected water hammer . In both cases the pressure pulse amplitude
pulse behaviour are presented in the appendix. produced by the water hammer effect is lower than
the pressure increase of 60 psi (414 kPa) associated
Analysis of results with the additional influx when using the soft shut-in
procedure in the simulated kick example. The
pressure increase due to the additional influx is more
For the test well, the pressure wave round-trip time serious as it can increase an already high value
“Tr “ is calculated to be 2.1 seconds in the appendix whereas the pressure pulse due to the water-hammer
using a ctiiefully derived result for the expected effect occurs before there is significant pressure build
pressure wave velocity of 1350 m/s. A small BOP in the annulus.
unit was used foy the tests, for which effective BOP
closure was estimated to be 5 seconds. Applying
. Downhole measurements show a significantly
equation (2), the maximum pressure rise for the hard reduced pressure pulse amplitude at the shoe and at
shut-in case in the 1430m well is then reduced from
the bit most probably due to dispersion effects in the
827 kPa (120 psi) to 345 kPa (50 psi), and for the
well-bore.
soft case from 372 kPa (54 psi) to 110 kPa (16 psi).
A comparison between the theoretical and
experimental results is made in Table 4 and it can be . Agreement between theory and experiment is good
seen that there is good agreement. The measured confirming that pressure pulse amplitudes are
difference in the water hammer pulse amplitude generally insignificant compared to other factors.
between hard and soft shut-ins at surface was 37 psi
(255 kPa) , for an estimated effective annular Given the results of the experiment the arguments
preventer closure time of 5 seconds. The hard shut-in formeriy given against using the hard shut-in
theoretical pulse amplitude was also in good
procedure appear no longer to be valid. However,
agreement with that measured experimentally and the
the arguments against using the soft shut-in are
pulse width confirmed that the pressure pulse is significant. The additional influx into the well-bore
dominated by the pressure wave round-trip time in
can easily lead to increases in casing pressure which
the borehole.
exceed the amplitude of the water hammer pulse. In
addition there is the additional risk of human error
When the effective preventer closure tiie exceeds the associated with the closing and opening of the
pressure wave round trip for the well, as is the case valves. Therefore in the interests of safety for
in most field situations, the difference between hard personnel, rig equipment and the V’~11-borethe hard
and soft shut-in procedures produces a negligible shut-in is the preferred procedure. This implies that
effect downhole and only a small effect at surface. the well will be initially closed in with the annular
Neither the actual measured pressure increases nor preventer’and while in the drilling mode the manual
the theoretical pressures increases due to the water ~alves either upstream or downstream of the choke
hammer effect can be expected to produce any will be maintained in the closed position.
damage to the well. For very rapid closure times, the
use of a soft shut-in is expected to merely delay the NOMENCLATURE
water hammer pulse until the rapid effective closure
of the choke valve.
a Inner radius
CONCLUSIONS A Flowing area
U Change of flowing area
An experimental and theoretical study has been made b Outer radius
of the effect of shut-in procedure on the water Sound speed
c
hammer pressure pulse. During shut-in tests this was
measured both in the surface casing and downhole at d Pipe diameter
the casing shoe and at the bit. The following points Friction factor
regarding the water-hammer pulse amplitudes are f
noted: K Bulk modulus
1 Pipe length
nh Dynamic head loss in choke line
363
.
Pi Inner pressure
[4] Massey, B. S., “Mechanics of Fluids”, Van
P. Outer pressute Nostrand Reinhold, 1989.
AP Pressure rise across shock
r Radius [5] Timoshenko, S.P., and Goodier, J,N,, “Theory
u, Initial velocity of Elasticity”, McGraw-Hill Book Company,
1970.
%? Velocity after wave
U3 Velocity after wave in choke line APPENDIX A : WATER-HAMMER
1983, pp 130-131.
AA cc A we can calculate the pressure rise across
[21
. . Dau~hertv. R.L.. Franzini. J.B. and Finnemore. the wave as:
E.~., “~luid Mechanics with Engineering
# ~ations”, McGraw-Hill Book Company,
! . AP = PC(UI - U2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . , [A3]
[3] White, D.B. and Walton, I.C.: “A Computer Wave Speed Calculation
Model for Kicks in Water- and Oil-Based
Muds,” SPE/IADC 19975, presented at the
W~ADC Drilling Conference, Houston, To calculate AP we must know the wavt?
. propagation speed along the pipe, c. This is a
3s4
●
pia2 - pob2 1
/(
c= . ... ..... ... .. .... .. ...... ..... ..[A9]
b2 -02 lAA
+ pia2 - pob2
b2 -02
. . . . . . . . ...[A6]
p Z+AAP -)
For a water based mud of density,
The radial displacement of the casing is calculated p = 1018.5 Kg/m3, in this geometry we calculate a
from se = Ar/r and for plain strain: wave speed in the range 1320< c e 1370m/s, If the
pipe and casing are assumed rigid the wave speed is
c = 1470 m/s. The well-bore and drillpipe rigidity
CO=;[OO(l-V2)-C,V( l+V)] .. ................[A7] make a significant cmection to the wave speed in the
system. For the purpose of the further analysis we
consider that the wave speed is c = 1350m/s.
We assume that the casing string is concentric in the
hole and that the cement has no gas channeling.
Then we can apply equations [A6] and [A7] for the Rapidly Closing Vaive - No Bypass
interfaces between the mud and the casing, the casing
and the cement, and the cement and formation and Considering a rapidly closing valve in a rigid pipe
thereby caiculate an effective stiffness for the casing with no bypass flow the pressure calculation is
string. A similar approach can be Men for a 9X in simple. Since there is no bypass U2= O, we know
casing tilde a 13%in string, The result is that for a the mud density and the sound speed. A typical
typical 9)( in casing string the well-bore stiffness formation influx rate is 0.014 m 3/s (5.5 Bbl/min)
ties in the range: which gives an initial velocity
.
-pcu, = o
w
.
WE25712
I Well G eometry 1
367
Table 3: Well and influx details for water-hammer experiment
Well Depth
Casing Shoe depth 708 m 2322 ft
Casing ID 0.216 m 8.5 in
Casing OD 0.244 m 9.625 in
Drill Pipe ID 0.108 m 4.25 in
Drill Pipe OD 0.127 m 5 in
Choke Length 50 m 165 ft
Choke Line ID 0.077 m 3 in
Choke Line Geometry 5 x 90 deg bends
Mud 1018 8.5 lb/gal
Density Kg/ins
Mud Solids Volume Fraction 10% -
Influx Rate ).01 4 m3/s 5.5 bbl/min
Mud velocity at shut-in 0.6 m/s
J__ 1.97 ft/sec
? ? T P 7 - $)
!
.. . . . .. . ..-...-,,,
,.,.
.,,’-, ,’ ...-.,.., .,,’, . x
,,,
. ,.,,
”,,,,,,,. ,,
,,,.
,,. ,,,,
,,,,
,.. .,. .~
+
ii-
—
In
. .
-+
~
u)
.. ...
...,... .........-
—- ...”
....-------- ..
u
I
i
o
I
~ 90 * e
gg~~l
1 ~
R
(l(w)w!) WI
309
Time (seconds)
~’:
150
(b)
\Vater-hamrne=r
puls
~ 100 Hard
u BOP
s closed I
; 50’ ..-
Sort .--------- —----
-..—-
#----~-
1 . ,’ . . .
0
110 120 1.X) 140 1.S)
{a)
‘W’nler
hammer”’
$
1150 - Pumps
2 so
2
t
A 1050
L a
o 2on Joo
Tbnc (seconds}
i I
Figure 3: Schematic diagmm oitti well showing prc.wre measurements.
Ttme (seconds)
Figure 5 (a) Casing “’shoe” and (b) bit pressu~ correwmdbw tO t~ SUfi~e
meawrmcnts thow n in FIgurc 4a).