◈ TABLE OF CONTENTS
[1]. Building - Load Ouput Summary.
- 1. Project Name.
- 2. Date.
- 3. Location.
- 4. Design Conditions.
- 5. Cooling and Heating Loads.
Summer Winter
N1. suite sur 15.9 1711.2 1363.1 6.4 24.8 18.0 13.4 12.8 17:00 -165.5
N1. dormitorio 1 sur 9 1144.5 877.8 4.1 25.2 18.4 13.4 12.8 18:00 -144.8
N1. dormitorio 2 sur11.6 1418.6 1121.1 5.2 24.9 18.1 13.4 12.8 18:00 -166.2
N1. sala-comedor sur38.8 2770.4 2151.7 10.0 24.5 17.8 13.4 12.7 18:00 -344.1
N1. cocina sur 20.5 2283.7 1808.2 8.4 24.6 17.8 13.4 12.8 17:00 -266.0
N1.dormitorioserv.sur 4 728.2 520.4 2.4 26.0 19.1 13.4 12.8 19:00 -88.7
N1. suite norte 15.9 1669.8 1321.6 6.2 24.8 18.0 13.4 12.8 18:00 -165.5
N1.dormitorio 1 norte 9 1144.5 877.8 4.1 25.2 18.4 13.4 12.8 18:00 -144.8
N1.dormitorio 2 norte11.6 1418.6 1121.1 5.2 24.9 18.1 13.4 12.8 18:00 -166.2
N1.sala-comedor nor38.8 2838.9 2220.2 10.4 24.5 17.8 13.4 12.7 17:00 -344.1
N1. cocina norte 20.5 2232.4 1756.9 8.2 24.6 17.9 13.4 12.8 18:00 -266.0
Area
[m2]
[W] [W] [CMM] [W]
N1.dormitorio serv. 4n 728.2 520.4 2.4 26.0 19.1 13.4 12.8 19:00 -88.7
N2. suite sur 15.9 1373.9 1025.8 4.8 25.0 18.2 13.4 12.8 17:00 -165.5
N2. dormitorio 1 sur9 953.7 687.0 3.2 25.5 18.6 13.4 12.8 18:00 -144.8
N2. dormitorio 2 sur
11.6 1172.3 874.7 4.1 25.2 18.4 13.4 12.8 18:00 -166.2
N2. sala-comedor sur
38.8 2528.5 1909.8 8.9 24.5 17.8 13.4 12.8 18:00 -344.1
N2. cocina sur 20.5 1848.0 1372.5 6.4 24.8 18.0 13.4 12.8 17:00 -266.0
N2.dormitorioserv.sur
4 643.2 435.4 2.0 26.4 19.4 13.5 12.8 19:00 -88.7
N2. suite norte 15.9 1332.5 984.3 4.6 25.1 18.3 13.4 12.8 18:00 -165.5
N2.dormitorio 1 norte
9 953.7 687.0 3.2 25.5 18.6 13.4 12.8 18:00 -144.8
N2.dormitorio 2 norte
11.6 1172.3 874.7 4.1 25.2 18.4 13.4 12.8 18:00 -166.2
N2.sala-comedor nor
38.8 2597.1 1978.4 9.2 24.5 17.8 13.4 12.8 17:00 -344.1
N2. cocina norte20.5 1796.7 1321.2 6.2 24.8 18.0 13.4 12.8 18:00 -266.0
N2.dormitorio serv. 4n 643.2 435.4 2.0 26.4 19.4 13.5 12.8 19:00 -88.7
N3. suite sur 15.9 3295.5 2947.4 13.7 24.4 17.7 13.4 12.7 15:00 -587.3
N3. dormitorio 1 sur9 2027.1 1760.5 8.2 24.6 17.9 13.4 12.8 15:00 -383.5
N3. dormitorio 2 sur
11.6 2562.8 2265.3 10.6 24.5 17.7 13.4 12.7 15:00 -474.3
N3. sala-comedor sur
38.8 7304.4 6685.7 31.2 24.2 17.5 13.3 12.7 15:00 -1374.4
N3. cocina sur 20.5 4333.0 3857.5 18.0 24.3 17.6 13.4 12.7 15:00 -810.9
N3.dormitorioserv.sur
4 1094.3 886.5 4.1 25.2 18.4 13.4 12.8 16:00 -195.0
N3. suite norte 15.9 3247.1 2899.0 13.5 24.4 17.7 13.4 12.7 15:00 -587.3
N3.dormitorio 1 norte
9 2027.1 1760.5 8.2 24.6 17.9 13.4 12.8 15:00 -383.5
N3.dormitorio 2 norte
11.6 2562.8 2265.3 10.6 24.5 17.7 13.4 12.7 15:00 -474.3
N3.sala-comedor nor
38.8 7384.4 6765.7 31.5 24.2 17.5 13.3 12.7 15:00 -1374.4
N3. cocina norte20.5 4280.4 3804.9 17.7 24.3 17.6 13.4 12.7 15:00 -810.9
N3.dormitorio serv. 4n 1094.3 886.5 4.1 25.2 18.4 13.4 12.8 16:00 -195.0
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space Input Data
Adj.Region Temp
LG Electronics Space - Load Output
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 139 139 8.12
Partition 421.1 421.1 24.61
Sub Total 560.1 560.1 32.73
Internal Load
Light 295.2 295.2 17.25
People 50.3 37.6 87.9 5.14
Misc 255.5 0 255.5 14.93
Sub Total 601 37.6 638.6 37.32
Infiltration / Ventilation
Infiltration 97.6 150 247.6 14.47
Ventilation 104.5 160.5 265 15.49
Sub Total 202.1 310.5 512.6 29.95
Grand Total 1363.2 348.1 1711.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -76 45.92
Partition 0 0.00
Sub Total -76 45.92
Infiltration
Infiltration -89.5 54.08
Ventilation 0 0.00
Sub Total -89.5 54.08
Grand Total -165.5 100.00
1200
Sensibl
1000 e
800 Latent
Total
600
400
200
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Time[hr]
Wall Cond
Ventilation 8%
15%
Space
Net
Partition Heat
Infiltration 25%
14% Gain
1711.2
W
Misc
15% Light
17%
People
5%
Space
Glass Cond Heat
Infiltration 46% Loss
54%
-165.5
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 146.5 146.5 12.80
Partition 231.7 231.7 20.25
Sub Total 378.2 378.2 33.05
Internal Load
Light 167 167 14.59
People 28.4 21.3 49.7 4.34
Misc 144.5 0 144.5 12.63
Sub Total 339.9 21.3 361.2 31.56
Infiltration / Ventilation
Infiltration 55.2 84.8 140 12.23
Ventilation 104.5 160.5 265 23.16
Sub Total 159.7 245.3 405 35.39
Grand Total 877.8 266.6 1144.4 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -94.2 65.06
Partition 0 0.00
Sub Total -94.2 65.06
Infiltration
Infiltration -50.6 34.94
Ventilation 0 0.00
Sub Total -50.6 34.94
Grand Total -144.8 100.00
1200
Load
1000
Sensibl
800 e
Latent
600
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
13%
Space
Ventilation Net
23%
Heat
Partition
20% Gain
1144.5
Infiltration W
12%
Misc Light
13% 15%
People
4%
Infiltration
Space
35% Heat
Glass Cond Loss
65% -144.8
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 156.8 156.8 11.05
Partition 349.6 349.6 24.64
Sub Total 506.4 506.4 35.70
Internal Load
Light 215.6 215.6 15.20
People 36.7 27.5 64.2 4.53
Misc 186.6 0 186.6 13.15
Sub Total 438.9 27.5 466.4 32.88
Infiltration / Ventilation
Infiltration 71.3 109.5 180.8 12.74
Ventilation 104.5 160.5 265 18.68
Sub Total 175.8 270 445.8 31.43
Grand Total 1121.1 297.5 1418.6 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -100.8 60.69
Partition 0 0.00
Sub Total -100.8 60.69
Infiltration
Infiltration -65.3 39.31
Ventilation 0 0.00
Sub Total -65.3 39.31
Grand Total -166.1 100.00
1400
1200
Load
1000 Sensibl
e
800
Latent
600 Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
11%
Space
Ventilation
19% Net
Heat
Partition
Infiltration
25% Gain
13%
1418.6
W
Misc
13% Light
15%
People
5%
Space
Infiltration Heat
39%
Glass Cond Loss
61% -166.2
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 161 161 5.81
Partition 292.4 292.4 10.55
Sub Total 453.4 453.4 16.37
Internal Load
Light 608.5 608.5 21.97
People 122.8 91.9 214.7 7.75
Misc 624 0 624 22.52
Sub Total 1355.3 91.9 1447.2 52.24
Infiltration / Ventilation
Infiltration 238.4 366.3 604.7 21.83
Ventilation 104.5 160.5 265 9.57
Sub Total 342.9 526.8 869.7 31.39
Grand Total 2151.6 618.7 2770.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -125.6 36.50
Partition 0 0.00
Sub Total -125.6 36.50
Infiltration
Infiltration -218.5 63.50
Ventilation 0 0.00
Sub Total -218.5 63.50
Grand Total -344.1 100.00
2500
Load
2000
Sensibl
e
1500
Latent
Total
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Glass Cond Heat
37%
Infiltration
Loss
63% -344.1
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 281 281 12.31
Partition 396.6 396.6 17.37
Sub Total 677.6 677.6 29.67
Internal Load
Light 407.9 407.9 17.86
People 162 121.2 283.2 12.40
Misc 330.1 0 330.1 14.46
Sub Total 900 121.2 1021.2 44.72
Infiltration / Ventilation
Infiltration 126.1 193.7 319.8 14.00
Ventilation 104.5 160.5 265 11.60
Sub Total 230.6 354.2 584.8 25.61
Grand Total 1808.2 475.4 2283.6 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -150.4 56.54
Partition 0 0.00
Sub Total -150.4 56.54
Infiltration
Infiltration -115.6 43.46
Ventilation 0 0.00
Sub Total -115.6 43.46
Grand Total -266 100.00
2000
Load
1500 Sensibl
e
Latent
1000 Total
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Infiltration Heat
43% Glass Cond Loss
57%
-266.0
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 141.9 141.9 19.48
Partition 119.2 119.2 16.37
Sub Total 261.1 261.1 35.85
Internal Load
Light 74.4 74.4 10.22
People 12.7 9.5 22.2 3.05
Misc 43.2 0 43.2 5.93
Sub Total 130.3 9.5 139.8 19.20
Infiltration / Ventilation
Infiltration 24.6 37.8 62.4 8.57
Ventilation 104.5 160.5 265 36.39
Sub Total 129.1 198.3 327.4 44.95
Grand Total 520.5 207.8 728.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -66.1 74.60
Partition 0 0.00
Sub Total -66.1 74.60
Infiltration
Infiltration -22.5 25.40
Ventilation 0 0.00
Sub Total -22.5 25.40
Grand Total -88.6 100.00
700
600
Load
500 Sensibl
e
400
Latent
300 Total
200
100
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Wall Cond
19%
Net
Ventilation Heat
36%
Partition
Gain
16% 728.2
W
Light
10%
Infiltration
9%
Misc People
6% 3%
Infiltration Space
25%
Heat
Loss
Glass Cond
75%
-88.7
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 97.5 97.5 5.84
Partition 421.1 421.1 25.22
Sub Total 518.6 518.6 31.06
Internal Load
Light 295.2 295.2 17.68
People 50.3 37.6 87.9 5.26
Misc 255.5 0 255.5 15.30
Sub Total 601 37.6 638.6 38.24
Infiltration / Ventilation
Infiltration 97.6 150 247.6 14.83
Ventilation 104.5 160.5 265 15.87
Sub Total 202.1 310.5 512.6 30.70
Grand Total 1321.7 348.1 1669.8 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -76 45.92
Partition 0 0.00
Sub Total -76 45.92
Infiltration
Infiltration -89.5 54.08
Ventilation 0 0.00
Sub Total -89.5 54.08
Grand Total -165.5 100.00
1200
Sensibl
1000 e
800 Latent
Total
600
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
Ventilation 6%
16% Space
Net
Partition
25%
Heat
Infiltration
15% Gain
1669.8
W
Misc Light
15% 18%
People
5%
Space
Glass Cond Heat
Infiltration 46% Loss
54%
-165.5
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 146.5 146.5 12.80
Partition 231.7 231.7 20.25
Sub Total 378.2 378.2 33.05
Internal Load
Light 167 167 14.59
People 28.4 21.3 49.7 4.34
Misc 144.5 0 144.5 12.63
Sub Total 339.9 21.3 361.2 31.56
Infiltration / Ventilation
Infiltration 55.2 84.8 140 12.23
Ventilation 104.5 160.5 265 23.16
Sub Total 159.7 245.3 405 35.39
Grand Total 877.8 266.6 1144.4 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -94.2 65.06
Partition 0 0.00
Sub Total -94.2 65.06
Infiltration
Infiltration -50.6 34.94
Ventilation 0 0.00
Sub Total -50.6 34.94
Grand Total -144.8 100.00
1200
Load
1000
Sensibl
800 e
Latent
600
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
13%
Space
Ventilation Net
23%
Heat
Partition
20% Gain
1144.5
Infiltration W
12%
Misc Light
13% 15%
People
4%
Infiltration
Space
35% Heat
Glass Cond Loss
65% -144.8
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 156.8 156.8 11.05
Partition 349.6 349.6 24.64
Sub Total 506.4 506.4 35.70
Internal Load
Light 215.6 215.6 15.20
People 36.7 27.5 64.2 4.53
Misc 186.6 0 186.6 13.15
Sub Total 438.9 27.5 466.4 32.88
Infiltration / Ventilation
Infiltration 71.3 109.5 180.8 12.74
Ventilation 104.5 160.5 265 18.68
Sub Total 175.8 270 445.8 31.43
Grand Total 1121.1 297.5 1418.6 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -100.8 60.69
Partition 0 0.00
Sub Total -100.8 60.69
Infiltration
Infiltration -65.3 39.31
Ventilation 0 0.00
Sub Total -65.3 39.31
Grand Total -166.1 100.00
1400
1200
Load
1000 Sensibl
e
800
Latent
600 Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
11%
Space
Ventilation
19% Net
Heat
Partition
Infiltration
25% Gain
13%
1418.6
W
Misc
13% Light
15%
People
5%
Space
Infiltration Heat
39%
Glass Cond Loss
61% -166.2
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 229.6 229.6 8.09
Partition 292.4 292.4 10.30
Sub Total 522 522 18.39
Internal Load
Light 608.5 608.5 21.43
People 122.8 91.9 214.7 7.56
Misc 624 0 624 21.98
Sub Total 1355.3 91.9 1447.2 50.98
Infiltration / Ventilation
Infiltration 238.4 366.3 604.7 21.30
Ventilation 104.5 160.5 265 9.33
Sub Total 342.9 526.8 869.7 30.64
Grand Total 2220.2 618.7 2838.9 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -125.6 36.50
Partition 0 0.00
Sub Total -125.6 36.50
Infiltration
Infiltration -218.5 63.50
Ventilation 0 0.00
Sub Total -218.5 63.50
Grand Total -344.1 100.00
2500
Load
2000
Sensibl
e
1500
Latent
Total
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
People
8%
Space
Glass Cond Heat
37%
Infiltration
Loss
63% -344.1
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 229.8 229.8 10.29
Partition 396.6 396.6 17.77
Sub Total 626.4 626.4 28.06
Internal Load
Light 407.9 407.9 18.27
People 162 121.2 283.2 12.69
Misc 330.1 0 330.1 14.79
Sub Total 900 121.2 1021.2 45.74
Infiltration / Ventilation
Infiltration 126.1 193.7 319.8 14.33
Ventilation 104.5 160.5 265 11.87
Sub Total 230.6 354.2 584.8 26.20
Grand Total 1757 475.4 2232.4 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -150.4 56.54
Partition 0 0.00
Sub Total -150.4 56.54
Infiltration
Infiltration -115.6 43.46
Ventilation 0 0.00
Sub Total -115.6 43.46
Grand Total -266 100.00
2000
Load
1500 Sensibl
e
Latent
1000 Total
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Infiltration Heat
43% Glass Cond Loss
57%
-266.0
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 141.9 141.9 19.48
Partition 119.2 119.2 16.37
Sub Total 261.1 261.1 35.85
Internal Load
Light 74.4 74.4 10.22
People 12.7 9.5 22.2 3.05
Misc 43.2 0 43.2 5.93
Sub Total 130.3 9.5 139.8 19.20
Infiltration / Ventilation
Infiltration 24.6 37.8 62.4 8.57
Ventilation 104.5 160.5 265 36.39
Sub Total 129.1 198.3 327.4 44.95
Grand Total 520.5 207.8 728.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -66.1 74.60
Partition 0 0.00
Sub Total -66.1 74.60
Infiltration
Infiltration -22.5 25.40
Ventilation 0 0.00
Sub Total -22.5 25.40
Grand Total -88.6 100.00
700
600
Load
500 Sensibl
e
400
Latent
300 Total
200
100
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Wall Cond
19%
Net
Ventilation Heat
36%
Partition
Gain
16% 728.2
W
Light
10%
Infiltration
9%
Misc People
6% 3%
Infiltration Space
25%
Heat
Loss
Glass Cond
75%
-88.7
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 139 139 10.12
Partition 83.8 83.8 6.10
Sub Total 222.8 222.8 16.22
Internal Load
Light 295.2 295.2 21.48
People 50.3 37.6 87.9 6.40
Misc 255.5 0 255.5 18.60
Sub Total 601 37.6 638.6 46.48
Infiltration / Ventilation
Infiltration 97.6 150 247.6 18.02
Ventilation 104.5 160.5 265 19.29
Sub Total 202.1 310.5 512.6 37.31
Grand Total 1025.9 348.1 1374 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -76 45.92
Partition 0 0.00
Sub Total -76 45.92
Infiltration
Infiltration -89.5 54.08
Ventilation 0 0.00
Sub Total -89.5 54.08
Grand Total -165.5 100.00
1400
1200
Load
1000 Sensibl
e
800
Latent
600 Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
10%
Partition Space
Ventilation
19%
6% Net
Heat
Light
Gain
Infiltration
18% 21% 1373.9
W
Misc
19%
People
6%
Space
Glass Cond Heat
Infiltration 46% Loss
54%
-165.5
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 146.5 146.5 15.36
Partition 40.9 40.9 4.29
Sub Total 187.4 187.4 19.65
Internal Load
Light 167 167 17.51
People 28.4 21.3 49.7 5.21
Misc 144.5 0 144.5 15.15
Sub Total 339.9 21.3 361.2 37.88
Infiltration / Ventilation
Infiltration 55.2 84.8 140 14.68
Ventilation 104.5 160.5 265 27.79
Sub Total 159.7 245.3 405 42.47
Grand Total 687 266.6 953.6 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -94.2 65.06
Partition 0 0.00
Sub Total -94.2 65.06
Infiltration
Infiltration -50.6 34.94
Ventilation 0 0.00
Sub Total -50.6 34.94
Grand Total -144.8 100.00
1000
Load
800
Sensibl
e
600
Latent
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
15%
Space
Ventilation Partition Net
28% 4% Heat
Gain
Light 953.7
Infiltration 18%
15% W
Misc
15% People
5%
Infiltration
Space
35% Heat
Glass Cond Loss
65% -144.8
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 156.8 156.8 13.38
Partition 103.3 103.3 8.81
Sub Total 260.1 260.1 22.19
Internal Load
Light 215.6 215.6 18.39
People 36.7 27.5 64.2 5.48
Misc 186.6 0 186.6 15.92
Sub Total 438.9 27.5 466.4 39.79
Infiltration / Ventilation
Infiltration 71.3 109.5 180.8 15.42
Ventilation 104.5 160.5 265 22.61
Sub Total 175.8 270 445.8 38.03
Grand Total 874.8 297.5 1172.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -100.8 60.69
Partition 0 0.00
Sub Total -100.8 60.69
Infiltration
Infiltration -65.3 39.31
Ventilation 0 0.00
Sub Total -65.3 39.31
Grand Total -166.1 100.00
1200
Load
1000
Sensibl
800 e
Latent
600
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
13%
Space
Ventilation
Partition Net
23%
9% Heat
Gain
Infiltration 1172.3
15% Light
18% W
Misc
16%
People
5%
Space
Infiltration Heat
39%
Glass Cond Loss
61% -166.2
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 161 161 6.37
Partition 50.6 50.6 2.00
Sub Total 211.6 211.6 8.37
Internal Load
Light 608.5 608.5 24.07
People 122.8 91.9 214.7 8.49
Misc 624 0 624 24.68
Sub Total 1355.3 91.9 1447.2 57.24
Infiltration / Ventilation
Infiltration 238.4 366.3 604.7 23.92
Ventilation 104.5 160.5 265 10.48
Sub Total 342.9 526.8 869.7 34.40
Grand Total 1909.8 618.7 2528.5 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -125.6 36.50
Partition 0 0.00
Sub Total -125.6 36.50
Infiltration
Infiltration -218.5 63.50
Ventilation 0 0.00
Sub Total -218.5 63.50
Grand Total -344.1 100.00
2500
Load
2000
Sensibl
e
1500
Latent
Total
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Glass Cond Heat
37%
Infiltration
Loss
63% -344.1
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 281 281 15.21
Partition -39.2 -39.2 -2.12
Sub Total 241.8 241.8 13.09
Internal Load
Light 407.9 407.9 22.07
People 162 121.2 283.2 15.33
Misc 330.1 0 330.1 17.86
Sub Total 900 121.2 1021.2 55.27
Infiltration / Ventilation
Infiltration 126.1 193.7 319.8 17.31
Ventilation 104.5 160.5 265 14.34
Sub Total 230.6 354.2 584.8 31.65
Grand Total 1372.4 475.4 1847.8 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -150.4 56.54
Partition 0 0.00
Sub Total -150.4 56.54
Infiltration
Infiltration -115.6 43.46
Ventilation 0 0.00
Sub Total -115.6 43.46
Grand Total -266 100.00
1400
1200 Sensibl
e
1000
Latent
800 Total
600
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Infiltration Heat
43% Glass Cond Loss
57%
-266.0
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 141.9 141.9 22.06
Partition 34.1 34.1 5.30
Sub Total 176 176 27.36
Internal Load
Light 74.4 74.4 11.57
People 12.7 9.5 22.2 3.45
Misc 43.2 0 43.2 6.72
Sub Total 130.3 9.5 139.8 21.74
Infiltration / Ventilation
Infiltration 24.6 37.8 62.4 9.70
Ventilation 104.5 160.5 265 41.20
Sub Total 129.1 198.3 327.4 50.90
Grand Total 435.4 207.8 643.2 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -66.1 74.60
Partition 0 0.00
Sub Total -66.1 74.60
Infiltration
Infiltration -22.5 25.40
Ventilation 0 0.00
Sub Total -22.5 25.40
Grand Total -88.6 100.00
600
Load
500
Sensibl
400 e
Latent
300
Total
200
100
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Wall Cond Net
22%
Ventilation Heat
41% Gain
Partition
5% 643.2
Light W
12%
People
Infiltration Misc 3%
10% 7%
Infiltration Space
25%
Heat
Loss
Glass Cond
75%
-88.7
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 97.5 97.5 7.32
Partition 83.8 83.8 6.29
Sub Total 181.3 181.3 13.61
Internal Load
Light 295.2 295.2 22.15
People 50.3 37.6 87.9 6.60
Misc 255.5 0 255.5 19.17
Sub Total 601 37.6 638.6 47.92
Infiltration / Ventilation
Infiltration 97.6 150 247.6 18.58
Ventilation 104.5 160.5 265 19.89
Sub Total 202.1 310.5 512.6 38.47
Grand Total 984.4 348.1 1332.5 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -76 45.92
Partition 0 0.00
Sub Total -76 45.92
Infiltration
Infiltration -89.5 54.08
Ventilation 0 0.00
Sub Total -89.5 54.08
Grand Total -165.5 100.00
1200
Load
1000
Sensibl
800 e
Latent
600
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
7%
Partition Space
Ventilation 6%
20%
Net
Heat
Light Gain
Infiltration 22%
19%
1332.5
W
Misc
19% People
7%
Space
Glass Cond Heat
Infiltration 46% Loss
54%
-165.5
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 146.5 146.5 15.36
Partition 40.9 40.9 4.29
Sub Total 187.4 187.4 19.65
Internal Load
Light 167 167 17.51
People 28.4 21.3 49.7 5.21
Misc 144.5 0 144.5 15.15
Sub Total 339.9 21.3 361.2 37.88
Infiltration / Ventilation
Infiltration 55.2 84.8 140 14.68
Ventilation 104.5 160.5 265 27.79
Sub Total 159.7 245.3 405 42.47
Grand Total 687 266.6 953.6 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -94.2 65.06
Partition 0 0.00
Sub Total -94.2 65.06
Infiltration
Infiltration -50.6 34.94
Ventilation 0 0.00
Sub Total -50.6 34.94
Grand Total -144.8 100.00
1000
Load
800
Sensibl
e
600
Latent
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
15%
Space
Ventilation Partition Net
28% 4% Heat
Gain
Light 953.7
Infiltration 18%
15% W
Misc
15% People
5%
Infiltration
Space
35% Heat
Glass Cond Loss
65% -144.8
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 156.8 156.8 13.38
Partition 103.3 103.3 8.81
Sub Total 260.1 260.1 22.19
Internal Load
Light 215.6 215.6 18.39
People 36.7 27.5 64.2 5.48
Misc 186.6 0 186.6 15.92
Sub Total 438.9 27.5 466.4 39.79
Infiltration / Ventilation
Infiltration 71.3 109.5 180.8 15.42
Ventilation 104.5 160.5 265 22.61
Sub Total 175.8 270 445.8 38.03
Grand Total 874.8 297.5 1172.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -100.8 60.69
Partition 0 0.00
Sub Total -100.8 60.69
Infiltration
Infiltration -65.3 39.31
Ventilation 0 0.00
Sub Total -65.3 39.31
Grand Total -166.1 100.00
1200
Load
1000
Sensibl
800 e
Latent
600
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Wall Cond
13%
Space
Ventilation
Partition Net
23%
9% Heat
Gain
Infiltration 1172.3
15% Light
18% W
Misc
16%
People
5%
Space
Infiltration Heat
39%
Glass Cond Loss
61% -166.2
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 229.6 229.6 8.84
Partition 50.6 50.6 1.95
Sub Total 280.2 280.2 10.79
Internal Load
Light 608.5 608.5 23.43
People 122.8 91.9 214.7 8.27
Misc 624 0 624 24.03
Sub Total 1355.3 91.9 1447.2 55.72
Infiltration / Ventilation
Infiltration 238.4 366.3 604.7 23.28
Ventilation 104.5 160.5 265 10.20
Sub Total 342.9 526.8 869.7 33.49
Grand Total 1978.4 618.7 2597.1 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -125.6 36.50
Partition 0 0.00
Sub Total -125.6 36.50
Infiltration
Infiltration -218.5 63.50
Ventilation 0 0.00
Sub Total -218.5 63.50
Grand Total -344.1 100.00
2500
Load
2000
Sensibl
e
1500
Latent
Total
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Glass Cond Heat
37%
Infiltration
Loss
63% -344.1
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 229.8 229.8 12.79
Partition -39.2 -39.2 -2.18
Sub Total 190.6 190.6 10.61
Internal Load
Light 407.9 407.9 22.70
People 162 121.2 283.2 15.76
Misc 330.1 0 330.1 18.37
Sub Total 900 121.2 1021.2 56.84
Infiltration / Ventilation
Infiltration 126.1 193.7 319.8 17.80
Ventilation 104.5 160.5 265 14.75
Sub Total 230.6 354.2 584.8 32.55
Grand Total 1321.2 475.4 1796.6 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -150.4 56.54
Partition 0 0.00
Sub Total -150.4 56.54
Infiltration
Infiltration -115.6 43.46
Ventilation 0 0.00
Sub Total -115.6 43.46
Grand Total -266 100.00
1400
1200 Sensibl
e
1000
Latent
800 Total
600
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Infiltration Heat
43% Glass Cond Loss
57%
-266.0
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 0 0 0.00
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 141.9 141.9 22.06
Partition 34.1 34.1 5.30
Sub Total 176 176 27.36
Internal Load
Light 74.4 74.4 11.57
People 12.7 9.5 22.2 3.45
Misc 43.2 0 43.2 6.72
Sub Total 130.3 9.5 139.8 21.74
Infiltration / Ventilation
Infiltration 24.6 37.8 62.4 9.70
Ventilation 104.5 160.5 265 41.20
Sub Total 129.1 198.3 327.4 50.90
Grand Total 435.4 207.8 643.2 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond 0 0.00
Glass Cond 0 0.00
Wall Cond -66.1 74.60
Partition 0 0.00
Sub Total -66.1 74.60
Infiltration
Infiltration -22.5 25.40
Ventilation 0 0.00
Sub Total -22.5 25.40
Grand Total -88.6 100.00
600
Load
500
Sensibl
400 e
Latent
300
Total
200
100
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Wall Cond Net
22%
Ventilation Heat
41% Gain
Partition
5% 643.2
Light W
12%
People
Infiltration Misc 3%
10% 7%
Infiltration Space
25%
Heat
Loss
Glass Cond
75%
-88.7
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 1921.3 1921.3 58.30
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 125.1 125.1 3.80
Partition 97.9 97.9 2.97
Sub Total 2144.3 2144.3 65.07
Internal Load
Light 295.2 295.2 8.96
People 50.3 37.6 87.9 2.67
Misc 255.5 0 255.5 7.75
Sub Total 601 37.6 638.6 19.38
Infiltration / Ventilation
Infiltration 97.6 150 247.6 7.51
Ventilation 104.5 160.5 265 8.04
Sub Total 202.1 310.5 512.6 15.55
Grand Total 2947.4 348.1 3295.5 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -421.8 71.82
Glass Cond 0 0.00
Wall Cond -76 12.94
Partition 0 0.00
Sub Total -497.8 84.76
Infiltration
Infiltration -89.5 15.24
Ventilation 0 0.00
Sub Total -89.5 15.24
Grand Total -587.3 100.00
3000
Load
2500
Sensibl
2000 e
Latent
1500
Total
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
8%
Infiltration Space
8% Net
Misc
8% Heat
People Gain
3% Roof Cond
58% 3295.5
Light W
9%
Partition
3%
Wall Cond
4%
Infiltration
15%
Space
Glass Cond Heat
13% Loss
Roof Cond -587.3
72%
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 1086.9 1086.9 53.62
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 125.1 125.1 6.17
Partition 48.9 48.9 2.41
Sub Total 1260.9 1260.9 62.20
Internal Load
Light 167 167 8.24
People 28.4 21.3 49.7 2.45
Misc 144.5 0 144.5 7.13
Sub Total 339.9 21.3 361.2 17.82
Infiltration / Ventilation
Infiltration 55.2 84.8 140 6.91
Ventilation 104.5 160.5 265 13.07
Sub Total 159.7 245.3 405 19.98
Grand Total 1760.5 266.6 2027.1 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -238.6 62.23
Glass Cond 0 0.00
Wall Cond -94.2 24.57
Partition 0 0.00
Sub Total -332.8 86.80
Infiltration
Infiltration -50.6 13.20
Ventilation 0 0.00
Sub Total -50.6 13.20
Grand Total -383.4 100.00
2000
Load
1500 Sensibl
e
Latent
1000 Total
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
13%
Space
Infiltration Net
7%
Heat
Misc Roof Cond Gain
7%
People
54% 2027.1
2% W
Light
8%
Partition
2% Wall Cond
6%
Infiltration
13%
Space
Heat
Glass Cond
25% Roof Cond Loss
62% -383.5
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 1403.1 1403.1 54.75
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 133.8 133.8 5.22
Partition 113.6 113.6 4.43
Sub Total 1650.5 1650.5 64.40
Internal Load
Light 215.6 215.6 8.41
People 36.7 27.5 64.2 2.51
Misc 186.6 0 186.6 7.28
Sub Total 438.9 27.5 466.4 18.20
Infiltration / Ventilation
Infiltration 71.3 109.5 180.8 7.06
Ventilation 104.5 160.5 265 10.34
Sub Total 175.8 270 445.8 17.40
Grand Total 2265.2 297.5 2562.7 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -308.1 64.97
Glass Cond 0 0.00
Wall Cond -100.8 21.26
Partition 0 0.00
Sub Total -408.9 86.23
Infiltration
Infiltration -65.3 13.77
Ventilation 0 0.00
Sub Total -65.3 13.77
Grand Total -474.2 100.00
2500
Load
2000
Sensibl
e
1500
Latent
Total
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
10%
Infiltration Space
7% Net
Misc Heat
7% Roof Cond Gain
People 55% 2562.8
3% W
Light
8%
Partition
4%
Wall Cond
5%
Infiltration
14%
Space
Glass Cond
Heat
21% Roof Cond
Loss
65% -474.3
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 4692.4 4692.4 64.24
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 126.8 126.8 1.74
Partition 168.3 168.3 2.30
Sub Total 4987.5 4987.5 68.28
Internal Load
Light 608.5 608.5 8.33
People 122.8 91.9 214.7 2.94
Misc 624 0 624 8.54
Sub Total 1355.3 91.9 1447.2 19.81
Infiltration / Ventilation
Infiltration 238.4 366.3 604.7 8.28
Ventilation 104.5 160.5 265 3.63
Sub Total 342.9 526.8 869.7 11.91
Grand Total 6685.7 618.7 7304.4 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -1030.3 74.96
Glass Cond 0 0.00
Wall Cond -125.6 9.14
Partition 0 0.00
Sub Total -1155.9 84.10
Infiltration
Infiltration -218.5 15.90
Ventilation 0 0.00
Sub Total -218.5 15.90
Grand Total -1374.4 100.00
7000
6000
Load
5000 Sensibl
e
4000
Latent
3000 Total
2000
1000
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
Infiltration 4%
8%
Space
Misc
9%
Net
People Heat
3% Gain
Light Roof Cond 7304.4
8% 64% W
Partition
2%
Wall Cond
2%
Infiltration
16%
Space
Glass Cond
9%
Heat
Loss
Roof Cond -1374.4
75%
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 2481.8 2481.8 57.28
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 266 266 6.14
Partition -20.9 -20.9 -0.48
Sub Total 2726.9 2726.9 62.93
Internal Load
Light 407.9 407.9 9.41
People 162 121.2 283.2 6.54
Misc 330.1 0 330.1 7.62
Sub Total 900 121.2 1021.2 23.57
Infiltration / Ventilation
Infiltration 126.1 193.7 319.8 7.38
Ventilation 104.5 160.5 265 6.12
Sub Total 230.6 354.2 584.8 13.50
Grand Total 3857.5 475.4 4332.9 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -544.9 67.20
Glass Cond 0 0.00
Wall Cond -150.4 18.55
Partition 0 0.00
Sub Total -695.3 85.74
Infiltration
Infiltration -115.6 14.26
Ventilation 0 0.00
Sub Total -115.6 14.26
Grand Total -810.9 100.00
3500
3000 Sensibl
e
2500
Latent
2000 Total
1500
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
6%
Infiltration Space
7%
Net
Misc
8% Heat
People Roof Cond
Gain
6% 57% 4333.0
Light
9%
W
Partition
0%
Wall Cond
6%
Infiltration
14%
Space
Heat
Glass Cond
19% Loss
Roof Cond
67% -810.9
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 474.6 474.6 43.37
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 114.8 114.8 10.49
Partition 37.7 37.7 3.45
Sub Total 627.1 627.1 57.31
Internal Load
Light 74.4 74.4 6.80
People 12.7 9.5 22.2 2.03
Misc 43.2 0 43.2 3.95
Sub Total 130.3 9.5 139.8 12.78
Infiltration / Ventilation
Infiltration 24.6 37.8 62.4 5.70
Ventilation 104.5 160.5 265 24.22
Sub Total 129.1 198.3 327.4 29.92
Grand Total 886.5 207.8 1094.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -106.3 54.54
Glass Cond 0 0.00
Wall Cond -66.1 33.91
Partition 0 0.00
Sub Total -172.4 88.46
Infiltration
Infiltration -22.5 11.54
Ventilation 0 0.00
Sub Total -22.5 11.54
Grand Total -194.9 100.00
1000
Load
800
Sensibl
e
600
Latent
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Ventilation Net
24% Heat
Roof Cond
Infiltration Gain
43%
6%
1094.3
Misc
4% W
People
2%
Light
7% Partition
Wall Cond
3% 10%
Infiltration
12%
Space
Heat
Glass Cond Roof Cond Loss
34% 55%
-195.0
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 1921.3 1921.3 59.17
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 76.7 76.7 2.36
Partition 97.9 97.9 3.01
Sub Total 2095.9 2095.9 64.55
Internal Load
Light 295.2 295.2 9.09
People 50.3 37.6 87.9 2.71
Misc 255.5 0 255.5 7.87
Sub Total 601 37.6 638.6 19.67
Infiltration / Ventilation
Infiltration 97.6 150 247.6 7.63
Ventilation 104.5 160.5 265 8.16
Sub Total 202.1 310.5 512.6 15.79
Grand Total 2899 348.1 3247.1 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -421.8 71.82
Glass Cond 0 0.00
Wall Cond -76 12.94
Partition 0 0.00
Sub Total -497.8 84.76
Infiltration
Infiltration -89.5 15.24
Ventilation 0 0.00
Sub Total -89.5 15.24
Grand Total -587.3 100.00
3000
Load
2500
Sensibl
2000 e
Latent
1500
Total
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
8%
Infiltration Space
8% Net
Misc
8%
Heat
People Gain
Roof Cond
3%
59%
3247.1
Light W
9%
Partition
3%
Wall Cond
2%
Infiltration
15%
Space
Glass Cond Heat
13% Loss
Roof Cond -587.3
72%
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 1086.9 1086.9 53.62
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 125.1 125.1 6.17
Partition 48.9 48.9 2.41
Sub Total 1260.9 1260.9 62.20
Internal Load
Light 167 167 8.24
People 28.4 21.3 49.7 2.45
Misc 144.5 0 144.5 7.13
Sub Total 339.9 21.3 361.2 17.82
Infiltration / Ventilation
Infiltration 55.2 84.8 140 6.91
Ventilation 104.5 160.5 265 13.07
Sub Total 159.7 245.3 405 19.98
Grand Total 1760.5 266.6 2027.1 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -238.6 62.23
Glass Cond 0 0.00
Wall Cond -94.2 24.57
Partition 0 0.00
Sub Total -332.8 86.80
Infiltration
Infiltration -50.6 13.20
Ventilation 0 0.00
Sub Total -50.6 13.20
Grand Total -383.4 100.00
2000
Load
1500 Sensibl
e
Latent
1000 Total
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
13%
Space
Infiltration Net
7%
Heat
Misc Roof Cond Gain
7%
People
54% 2027.1
2% W
Light
8%
Partition
2% Wall Cond
6%
Infiltration
13%
Space
Heat
Glass Cond
25% Roof Cond Loss
62% -383.5
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 1403.1 1403.1 54.75
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 133.8 133.8 5.22
Partition 113.6 113.6 4.43
Sub Total 1650.5 1650.5 64.40
Internal Load
Light 215.6 215.6 8.41
People 36.7 27.5 64.2 2.51
Misc 186.6 0 186.6 7.28
Sub Total 438.9 27.5 466.4 18.20
Infiltration / Ventilation
Infiltration 71.3 109.5 180.8 7.06
Ventilation 104.5 160.5 265 10.34
Sub Total 175.8 270 445.8 17.40
Grand Total 2265.2 297.5 2562.7 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -308.1 64.97
Glass Cond 0 0.00
Wall Cond -100.8 21.26
Partition 0 0.00
Sub Total -408.9 86.23
Infiltration
Infiltration -65.3 13.77
Ventilation 0 0.00
Sub Total -65.3 13.77
Grand Total -474.2 100.00
2500
Load
2000
Sensibl
e
1500
Latent
Total
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
10%
Infiltration Space
7% Net
Misc Heat
7% Roof Cond Gain
People 55% 2562.8
3% W
Light
8%
Partition
4%
Wall Cond
5%
Infiltration
14%
Space
Glass Cond
Heat
21% Roof Cond
Loss
65% -474.3
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 4692.4 4692.4 63.55
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 206.7 206.7 2.80
Partition 168.3 168.3 2.28
Sub Total 5067.4 5067.4 68.62
Internal Load
Light 608.5 608.5 8.24
People 122.8 91.9 214.7 2.91
Misc 624 0 624 8.45
Sub Total 1355.3 91.9 1447.2 19.60
Infiltration / Ventilation
Infiltration 238.4 366.3 604.7 8.19
Ventilation 104.5 160.5 265 3.59
Sub Total 342.9 526.8 869.7 11.78
Grand Total 6765.6 618.7 7384.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -1030.3 74.96
Glass Cond 0 0.00
Wall Cond -125.6 9.14
Partition 0 0.00
Sub Total -1155.9 84.10
Infiltration
Infiltration -218.5 15.90
Ventilation 0 0.00
Sub Total -218.5 15.90
Grand Total -1374.4 100.00
7000
6000
Load
5000 Sensibl
e
4000
Latent
3000 Total
2000
1000
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
Infiltration 4%
8%
Space
Misc
8% Net
People Heat
3% Gain
Light Roof Cond 7384.4
8% 64%
W
Partition
2%
Wall Cond
3%
Infiltration
16%
Space
Glass Cond
9%
Heat
Loss
Roof Cond -1374.4
75%
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 2481.8 2481.8 57.98
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 213.4 213.4 4.99
Partition -20.9 -20.9 -0.49
Sub Total 2674.3 2674.3 62.48
Internal Load
Light 407.9 407.9 9.53
People 162 121.2 283.2 6.62
Misc 330.1 0 330.1 7.71
Sub Total 900 121.2 1021.2 23.86
Infiltration / Ventilation
Infiltration 126.1 193.7 319.8 7.47
Ventilation 104.5 160.5 265 6.19
Sub Total 230.6 354.2 584.8 13.66
Grand Total 3804.9 475.4 4280.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -544.9 67.20
Glass Cond 0 0.00
Wall Cond -150.4 18.55
Partition 0 0.00
Sub Total -695.3 85.74
Infiltration
Infiltration -115.6 14.26
Ventilation 0 0.00
Sub Total -115.6 14.26
Grand Total -810.9 100.00
3000
Sensibl
2500 e
2000 Latent
Total
1500
1000
500
0
1 2 3 4 5 6 7 8 9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24
Ventilation
6%
Infiltration Space
7%
Net
Misc
8% Heat
People Gain
Roof Cond
7% 57% 4280.4
Light W
9%
Partition
0%
Wall Cond
5%
Infiltration
14%
Space
Heat
Glass Cond
19% Loss
Roof Cond
67% -810.9
W
1. COOLING LOAD
Space Space Net Percent Of Total
Item
Sens(W) Lat(W) Total(W) (%)
External Load
Roof Cond 474.6 474.6 43.37
Glass Solar 0 0 0.00
Glass Cond 0 0 0.00
Wall Cond 114.8 114.8 10.49
Partition 37.7 37.7 3.45
Sub Total 627.1 627.1 57.31
Internal Load
Light 74.4 74.4 6.80
People 12.7 9.5 22.2 2.03
Misc 43.2 0 43.2 3.95
Sub Total 130.3 9.5 139.8 12.78
Infiltration / Ventilation
Infiltration 24.6 37.8 62.4 5.70
Ventilation 104.5 160.5 265 24.22
Sub Total 129.1 198.3 327.4 29.92
Grand Total 886.5 207.8 1094.3 100.00
2. HEATING LOAD
Space Percent Of Total
Item
Sens(W) (%)
External Load
Roof Cond -106.3 54.54
Glass Cond 0 0.00
Wall Cond -66.1 33.91
Partition 0 0.00
Sub Total -172.4 88.46
Infiltration
Infiltration -22.5 11.54
Ventilation 0 0.00
Sub Total -22.5 11.54
Grand Total -194.9 100.00
1000
Load
800
Sensibl
e
600
Latent
Total
400
200
0
1 2 3 4 Time[hr]
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Space
Ventilation Net
24% Heat
Roof Cond
Infiltration Gain
43%
6%
1094.3
Misc
4% W
People
2%
Light
7% Partition
Wall Cond
3% 10%
Infiltration
12%
Space
Heat
Glass Cond Roof Cond Loss
34% 55%
-195.0
W