MECHANICAL CALCULATION
REPORT
1. INTRODUCTION ............................................................................................................. 3
2. CODES AND STANDARDS ............................................................................................ 4
3. ABBREVIATIONS ........................................................................................................... 4
4. DESIGN CONDITIONS ................................................................................................... 5
5. COOLING LOAD CALCULATION ................................................................................... 9
6. VENTILATION CALCULATION ......................................................................................11
7. SYSTEM PROPOSED ...................................................................................................12
8. TIE-IN POINT .................................................................................................................12
9. ANNEXURE 1 COOLING LOAD CALCULATION ...........................................................13
The aim of this report is to provide the references, methodology and calculation results related
to the mechanical systems of MIRAL NERVE project in Miral HQ building located on Yas island,
Abu Dhabi.
The following codes and standards shall be adopted for the design calculations of this project:
3. ABBREVIATIONS
• Latitude: 24.29° N
• Longitude: 54.35 ° E
• Altitude: 10 m
Design Relative
Temperatures NC Humidity Humidity
S.No Space
Level Control
Cooling °C %RH
1 Audio record 23⁰C ± 1⁰C 20 50 ± 10 Not controlled
Lighting and heat dissipation has been considered as per inputs provided by specialist.
Technical Power (in addition to regular office power supply) for other rooms:
• Studio: Utility + Technical Power: 25 KW
o 20 m2 of video walls, at 700 W/m2 = 14 KW
o 3x media systems wall boxes, at 2 KW per wallbox= 6 KW
o Allowance for other on-floor equipment= 5 KW
• Studio Lighting= 30 KW
o Based on 300 W/ m2 for a 100 m2 space
• CAR: 12 KW
o 3x fully equipped racks at 4KW per rack
• Gallery: 5 KW
• Audio Control: 1 KW
• Audio Record: 1 KW
• Post-Production (Mezzanine): 6 KW
o 4x High-end workstations with multiple computer and video monitors, + 4x wall-
mounted large screens.
AHU Load
VENTILATION CALCULATION
Occupancy outdoor Air Rate Area outdoor Air Rate
(Rp) (Ra)
ASHRAE
Occupancy Results
62,1 Supply Supply
Area for the Results Results Ventilation flow (
Sr. no Room Name Equivalent Rate Rate
[ m²] Space
area as per Rp+ Ra ), L/s
ARCH
Type (3)
/ASHRAE l/s per Flows l/s per Flows
62.1 person l/s m2 l/s
8. TIE-IN POINT
Existing tie-in points are available for chilled water, fresh air and general extract air in this
office area, which are not sufficient as per design requirement. Please find summary as
follows:
Tie-in Point
Sr No. System Existing Required Capacity
Capacity As Per New Design
1. General Details:
Floor Area 16.3 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 4.60 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
AUDIO CONTROL
1. General Details:
Floor Area 5.5 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 4.60 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
AUDIO RECORD
1. General Details:
Floor Area 12.5 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 4.60 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
GALLERY
1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
POST PRODUCTION
1. General Details:
Floor Area 30.6 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 4.60 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 30.0 0 1
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
RECEPTION
1. General Details:
Floor Area 30.5 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 9.70 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area 14.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 4.60 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
STAIR
1. General Details:
Floor Area 12.6 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 4.60 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.5 0 1
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
STUDIO
1. General Details:
Floor Area 93.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Std 62.1-2016
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 30.0 People
Wattage 19500.0 Watts Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING Latent 60.1 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Air System Name AHU -01
Equipment Type Chilled Water AHU
Air System Type Single Zone CAV
Number of zones 1
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
AHU ROOM /STORAGE x1
AUDIO CONTROL x1
AUDIO RECORD x1
GALLERY x1
POST PRODUCTION x1
RECEPTION x1
STAIR x1
STUDIO x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.7 21.0 18.3 1.00 100 0.0 0.0
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 5 %
Heating 5 %
5. Equipment Data
No equipment data required for this system.
1. General Details:
Air System Name FAN COIL UNIT
Equipment Type Chilled Water AHU
Air System Type Single Zone CAV
Number of zones 1
Humidification Data:
Minimum RH Setpoint 50 %
Humidifier Type Self-Contained Steam - Electric
Input Power 0.000 kWh/kg
Dehumidification Data:
Maximum RH Setpoint 55 %
Heating Source Electric Resistance
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
SERVER ROOM (CAR) x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.7 21.0 18.3 1.00 100 0.0 0.0
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 5 %
Heating 5 %
5. Equipment Data
No equipment data required for this system.
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
AHU ROOM /STORAGE 1 0.6 Jan 2300 46 0.0 16.3 2.83
AUDIO CONTROL 1 1.0 Jan 2300 72 0.0 5.5 13.13
AUDIO RECORD 1 1.0 Jan 2300 75 0.0 12.5 5.99
GALLERY 1 4.4 Jan 2300 331 0.0 18.0 18.40
POST PRODUCTION 1 11.5 Jun 1400 872 0.6 30.6 28.49
RECEPTION 1 1.1 Jan 2300 86 0.0 30.5 2.84
STAIR 1 2.6 Jun 1400 197 0.2 12.6 15.65
STUDIO 1 43.1 Jan 2300 3254 0.0 93.0 34.98
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.203 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2938.2 W/(L/s)
Site Altitude = 26.8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.203 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2938.2 W/(L/s)
Site Altitude = 26.8 m
0.016
0.012
12 0.010
3
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
SERVER ROOM (CAR) 1 14.0 Jan 2300 1056 0.0 14.0 75.43
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.203 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2938.2 W/(L/s)
Site Altitude = 26.8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.203 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2938.2 W/(L/s)
Site Altitude = 26.8 m
0.016
0.012
3 4 0.010
2
1
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
0.016
0.012
0.010
12
3 0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )