You are on page 1of 40

Aircon heat load calculation sheet

Project Name: GO TAN HIEP


Address: BIEN HOA DONG NAI

14/April/2023
Heat load sum up table

Cooling Heating Heat load per area


Floor
Qty.
Sys area
Room name Fl of Indoor SH Total Selected Time Total Selected Humid. Time Cooling Heating
-tem
rooms
[W] [Hr] [W] [kg/h] [Hr] [m2] [W/m2]

AHU 01- HANH LANG 1 1 1 5595 10479 11003 18 150.0 73.4


AHU 01- SHOP 07 1 1 1 5994 13396 14736 15 106.0 139.0
AHU 01- SHOP 08 1 1 1 8110 18435 20279 15 149.0 136.1
AHU 01- SHOP 09 1 1 1 24404 38016 41818 13 196.0 213.4
AHU 01- KIOSK 38 1 1 1 1411 3142 3299 14 25.0 132.0
AHU 01- KIOSK 39 1 1 1 1411 3142 3299 14 25.0 132.0
AHU 01- KIOSK 40 1 1 1 1411 3142 3299 14 25.0 132.0
AHU 01- KIOSK 41 1 1 1 1411 3142 3299 14 25.0 132.0
AHU 01- KIOSK 42 1 1 1 1411 3142 3299 14 25.0 132.0
AHU 01- KIOSK 43 1 1 1 1411 3142 3299 14 25.0 132.0
AHU 02- HANH LANG 1 2 1 7359 15160 15918 15 228.0 69.8
AHU 02- SHOP 14 1 2 1 4572 9449 9921 15 74.0 134.1

Peak load of building 12 63828 123238 132881 15 1053.0 126.2

SH : Sensible heat

-1-
Table of system heat load

Cooling Heating
Sys
Time F/A vol Indoor SH Indoor Outside Total Selected Time F/A vol Indoor Outside Total Selected Humid.
-tem
[Hr] [m3/h] [W] AHU 01 [Hr] [m3/h] [W] [kg/h]

1 15 2729 51897 64775 33854 98629 107042


2 15 771 11931 15558 9051 24609 25839

AHU 02

F/A : Fresh air


SH : Sensible heat

-2-
System table

System Room name Floor Rooms System Room name Floor Rooms

1 AHU 01- HANH LANG 1 1


1 AHU 01- SHOP 07 1 1
1 AHU 01- SHOP 08 1 1
1 AHU 01- SHOP 09 1 1
1 AHU 01- KIOSK 38 1 1
1 AHU 01- KIOSK 39 1 1
1 AHU 01- KIOSK 40 1 1
1 AHU 01- KIOSK 41 1 1
1 AHU 01- KIOSK 42 1 1
1 AHU 01- KIOSK 43 1 1
2 AHU 02- HANH LANG 1 1
2 AHU 02- SHOP 14 1 1

-3-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 25.0


Design room humidity in summer(%RH) 60.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 25.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- HANH LANG Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 13
Floor area(m2) 150.0
Depth of underground wall(m) 0.0
Ceiling height(m) 6.0 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 150.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 5.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-4-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- HANH LANG 1 1 1 Shop 150.0 6.0 13 Summer 325.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 25.0(CDB) 60.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 347 0 0 554 0 92 359 767 1118 1931 0 0 3691 1477 3259 8427
9 32.5 69.2 405 0 0 671 0 111 360 767 1118 1931 0 0 3885 1478 3406 8769
10 33.9 63.4 497 0 0 796 0 132 352 767 1118 1931 0 0 4123 1470 3500 9093
11 35.0 58.8 636 0 0 894 0 149 341 767 1118 1931 0 0 4377 1459 3534 9370
12 35.8 55.5 798 0 0 966 0 160 330 767 1118 1931 0 0 4622 1448 3540 9610
13 36.1 54.3 959 0 0 992 0 165 325 767 1118 1931 0 0 4814 1443 3540 9797
14 35.9 55.2 1168 0 0 974 0 162 330 767 1118 1931 0 0 5002 1448 3551 10001
15 35.4 57.2 1422 0 0 930 0 154 336 767 1118 1931 0 0 5204 1454 3543 10201
16 34.6 60.4 1699 0 0 858 0 143 345 767 1118 1931 0 0 5398 1463 3521 10382
17 33.6 64.4 1942 0 0 769 0 128 352 767 1118 1931 0 0 5537 1470 3461 10468
*18 32.5 69.2 2115 0 0 671 0 111 360 767 1118 1931 0 0 5595 1478 3406 10479
19 31.6 72.8 2092 0 0 590 0 98 360 767 1118 1931 0 0 5478 1478 3307 10263
20 30.8 75.8 1873 0 0 519 0 86 356 767 1118 1931 0 0 5176 1474 3191 9841
21 30.3 78.0 1561 0 0 474 0 79 356 767 1118 1931 0 0 4812 1474 3137 9423
22 29.9 79.5 1225 0 0 438 0 73 352 767 1118 1931 0 0 4434 1470 3071 8975

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-5-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- HANH LANG 1 1 1 Shop 150.0 6.0 13

Indoor Outdoor
Summer 25.0C 60.0% Summer 32.5C 69.2%

Fresh air Vol. Summer:325.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
11000 40 11000 30

10000 10000

9000 9000
30 20
8000 8000

7000 7000

6000 6000
20 10
5000 5000

4000 4000

3000 3000
10 0
2000 2000

1000 1000

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 18 2115 0 0 671 0 111 360 767 1118 1931 0 0 3406 10479 11003

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-6-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 424.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- SHOP 07 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 22
Floor area(m2) 106.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 106.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 1000 0
Safety factor Cooling 1.10
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-7-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- SHOP 07 1 1 1 Shop 106.0 3.5 22 Summer 424.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 548 0 0 455 0 44 174 1298 1892 1365 1000 0 4710 2066 4973 11749
9 32.5 69.2 653 0 0 537 0 52 174 1298 1892 1365 1000 0 4905 2066 5166 12137
10 33.9 63.4 783 0 0 625 0 61 171 1298 1892 1365 1000 0 5132 2063 5288 12483
11 35.0 58.8 940 0 0 695 0 67 166 1298 1892 1365 1000 0 5365 2058 5332 12755
12 35.8 55.5 1110 0 0 745 0 72 161 1298 1892 1365 1000 0 5590 2053 5342 12985
13 36.1 54.3 1279 0 0 764 0 74 160 1298 1892 1365 1000 0 5780 2052 5341 13173
14 35.9 55.2 1423 0 0 752 0 73 161 1298 1892 1365 1000 0 5911 2053 5356 13320
*15 35.4 57.2 1541 0 0 720 0 70 164 1298 1892 1365 1000 0 5994 2056 5346 13396
16 34.6 60.4 1593 0 0 670 0 65 168 1298 1892 1365 1000 0 5991 2060 5315 13366
17 33.6 64.4 1606 0 0 606 0 59 170 1298 1892 1365 1000 0 5934 2062 5239 13235
18 32.5 69.2 1580 0 0 537 0 52 174 1298 1892 1365 1000 0 5832 2066 5166 13064
19 31.6 72.8 1475 0 0 480 0 47 174 1298 1892 1365 1000 0 5665 2066 5036 12767
20 30.8 75.8 1319 0 0 430 0 42 172 1298 1892 1365 1000 0 5454 2064 4886 12404
21 30.3 78.0 1149 0 0 398 0 39 172 1298 1892 1365 1000 0 5249 2064 4816 12129
22 29.9 79.5 992 0 0 373 0 36 171 1298 1892 1365 1000 0 5064 2063 4729 11856

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-8-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- SHOP 07 1 1 1 Shop 106.0 3.5 22

Indoor Outdoor
Summer 24.0C 55.0% Summer 35.4C 57.2%

Fresh air Vol. Summer:424.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
14000 40 14000 30
13000 13000
12000 12000
11000 11000
30 20
10000 10000
9000 9000
8000 8000
7000 20 7000 10
6000 6000
5000 5000
4000 4000
10 0
3000 3000
2000 2000
1000 1000
0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 15 1541 0 0 720 0 70 164 1298 1892 1365 1000 0 5346 13396 14736

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-9-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 596.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- SHOP 08 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 30
Floor area(m2) 149.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 149.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 12.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 1000 0
Safety factor Cooling 1.10
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-10-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- SHOP 08 1 1 1 Shop 149.0 3.5 30 Summer 596.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 823 0 0 639 0 62 244 1770 2580 1919 1000 0 6213 2824 6991 16028
9 32.5 69.2 979 0 0 755 0 73 245 1770 2580 1919 1000 0 6496 2825 7262 16583
10 33.9 63.4 1175 0 0 879 0 85 240 1770 2580 1919 1000 0 6828 2820 7433 17081
11 35.0 58.8 1410 0 0 977 0 95 233 1770 2580 1919 1000 0 7171 2813 7495 17479
12 35.8 55.5 1665 0 0 1048 0 102 227 1770 2580 1919 1000 0 7504 2807 7509 17820
13 36.1 54.3 1919 0 0 1075 0 104 224 1770 2580 1919 1000 0 7787 2804 7509 18100
14 35.9 55.2 2135 0 0 1057 0 102 227 1770 2580 1919 1000 0 7983 2807 7528 18318
*15 35.4 57.2 2311 0 0 1012 0 98 231 1770 2580 1919 1000 0 8110 2811 7514 18435
16 34.6 60.4 2389 0 0 941 0 91 236 1770 2580 1919 1000 0 8110 2816 7472 18398
17 33.6 64.4 2409 0 0 853 0 83 240 1770 2580 1919 1000 0 8034 2820 7364 18218
18 32.5 69.2 2370 0 0 755 0 73 245 1770 2580 1919 1000 0 7887 2825 7262 17974
19 31.6 72.8 2213 0 0 675 0 65 244 1770 2580 1919 1000 0 7642 2824 7080 17546
20 30.8 75.8 1978 0 0 604 0 59 242 1770 2580 1919 1000 0 7330 2822 6868 17020
21 30.3 78.0 1723 0 0 559 0 54 242 1770 2580 1919 1000 0 7025 2822 6770 16617
22 29.9 79.5 1488 0 0 524 0 51 240 1770 2580 1919 1000 0 6752 2820 6646 16218

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-11-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- SHOP 08 1 1 1 Shop 149.0 3.5 30

Indoor Outdoor
Summer 24.0C 55.0% Summer 35.4C 57.2%

Fresh air Vol. Summer:596.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
20000 40 20000 30

18000 18000

16000 16000
30 20
14000 14000

12000 12000

10000 20 10000 10

8000 8000

6000 6000
10 0
4000 4000

2000 2000

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 15 2311 0 0 1012 0 98 231 1770 2580 1919 1000 0 7514 18435 20279

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-12-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 784.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- SHOP 09 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 40
Floor area(m2) 196.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 196.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 15698 0
Safety factor Cooling 1.10
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-13-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- SHOP 09 1 1 1 Shop 196.0 3.5 40 Summer 784.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 757 0 0 841 0 81 321 2360 3440 2524 15698 0 22261 3761 9197 35219
9 32.5 69.2 1110 0 0 993 0 96 322 2360 3440 2524 15698 0 22781 3762 9553 36096
10 33.9 63.4 1501 0 0 1156 0 112 316 2360 3440 2524 15698 0 23351 3756 9777 36884
11 35.0 58.8 1867 0 0 1285 0 125 307 2360 3440 2524 15698 0 23859 3747 9860 37466
12 35.8 55.5 2128 0 0 1378 0 134 299 2360 3440 2524 15698 0 24222 3739 9878 37839
*13 36.1 54.3 2272 0 0 1413 0 137 295 2360 3440 2524 15698 0 24404 3735 9877 38016
14 35.9 55.2 2246 0 0 1390 0 135 299 2360 3440 2524 15698 0 24353 3739 9904 37996
15 35.4 57.2 2128 0 0 1332 0 129 303 2360 3440 2524 15698 0 24171 3743 9885 37799
16 34.6 60.4 1971 0 0 1238 0 120 310 2360 3440 2524 15698 0 23911 3750 9828 37489
17 33.6 64.4 1789 0 0 1121 0 109 315 2360 3440 2524 15698 0 23601 3755 9687 37043
18 32.5 69.2 1606 0 0 993 0 96 322 2360 3440 2524 15698 0 23277 3762 9553 36592
19 31.6 72.8 1410 0 0 888 0 86 321 2360 3440 2524 15698 0 22966 3761 9313 36040
20 30.8 75.8 1253 0 0 794 0 77 318 2360 3440 2524 15698 0 22706 3758 9034 35498
21 30.3 78.0 1084 0 0 736 0 71 318 2360 3440 2524 15698 0 22473 3758 8905 35136
22 29.9 79.5 940 0 0 689 0 67 316 2360 3440 2524 15698 0 22278 3756 8742 34776

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-14-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- SHOP 09 1 1 1 Shop 196.0 3.5 40

Indoor Outdoor
Summer 24.0C 55.0% Summer 36.1C 54.3%

Fresh air Vol. Summer:784.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
40000 40 40000 30

36000 36000

32000 32000
30 20
28000 28000

24000 24000

20000 20 20000 10

16000 16000

12000 12000
10 0
8000 8000

4000 4000

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 13 2272 0 0 1413 0 137 295 2360 3440 2524 15698 0 9877 38016 41818

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-15-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 100.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- KIOSK 38 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 25.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 25.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 600 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-16-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- KIOSK 38 1 1 1 Shop 25.0 3.5 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 0 0 0 107 0 10 41 295 430 322 600 0 1334 471 1173 2978
9 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
10 33.9 63.4 0 0 0 148 0 14 40 295 430 322 600 0 1379 470 1247 3096
11 35.0 58.8 0 0 0 164 0 16 39 295 430 322 600 0 1397 469 1258 3124
12 35.8 55.5 0 0 0 176 0 17 38 295 430 322 600 0 1410 468 1259 3137
13 36.1 54.3 0 0 0 180 0 17 38 295 430 322 600 0 1414 468 1259 3141
*14 35.9 55.2 0 0 0 177 0 17 38 295 430 322 600 0 1411 468 1263 3142
15 35.4 57.2 0 0 0 170 0 16 39 295 430 322 600 0 1403 469 1261 3133
16 34.6 60.4 0 0 0 158 0 15 40 295 430 322 600 0 1390 470 1254 3114
17 33.6 64.4 0 0 0 143 0 14 40 295 430 322 600 0 1374 470 1236 3080
18 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
19 31.6 72.8 0 0 0 113 0 11 41 295 430 322 600 0 1341 471 1188 3000
20 30.8 75.8 0 0 0 101 0 10 41 295 430 322 600 0 1328 471 1152 2951
21 30.3 78.0 0 0 0 94 0 9 41 295 430 322 600 0 1320 471 1136 2927
22 29.9 79.5 0 0 0 88 0 9 40 295 430 322 600 0 1314 470 1115 2899

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-17-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- KIOSK 38 1 1 1 Shop 25.0 3.5 5

Indoor Outdoor
Summer 24.0C 55.0% Summer 35.9C 55.2%

Fresh air Vol. Summer:100.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
4000 40 4000 30

3600 3600

3200 3200
30 20
2800 2800

2400 2400

2000 20 2000 10

1600 1600

1200 1200
10 0
800 800

400 400

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 14 0 0 0 177 0 17 38 295 430 322 600 0 1263 3142 3299

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-18-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 100.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- KIOSK 39 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 25.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 25.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 600 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-19-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- KIOSK 39 1 1 1 Shop 25.0 3.5 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 0 0 0 107 0 10 41 295 430 322 600 0 1334 471 1173 2978
9 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
10 33.9 63.4 0 0 0 148 0 14 40 295 430 322 600 0 1379 470 1247 3096
11 35.0 58.8 0 0 0 164 0 16 39 295 430 322 600 0 1397 469 1258 3124
12 35.8 55.5 0 0 0 176 0 17 38 295 430 322 600 0 1410 468 1259 3137
13 36.1 54.3 0 0 0 180 0 17 38 295 430 322 600 0 1414 468 1259 3141
*14 35.9 55.2 0 0 0 177 0 17 38 295 430 322 600 0 1411 468 1263 3142
15 35.4 57.2 0 0 0 170 0 16 39 295 430 322 600 0 1403 469 1261 3133
16 34.6 60.4 0 0 0 158 0 15 40 295 430 322 600 0 1390 470 1254 3114
17 33.6 64.4 0 0 0 143 0 14 40 295 430 322 600 0 1374 470 1236 3080
18 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
19 31.6 72.8 0 0 0 113 0 11 41 295 430 322 600 0 1341 471 1188 3000
20 30.8 75.8 0 0 0 101 0 10 41 295 430 322 600 0 1328 471 1152 2951
21 30.3 78.0 0 0 0 94 0 9 41 295 430 322 600 0 1320 471 1136 2927
22 29.9 79.5 0 0 0 88 0 9 40 295 430 322 600 0 1314 470 1115 2899

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-20-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- KIOSK 39 1 1 1 Shop 25.0 3.5 5

Indoor Outdoor
Summer 24.0C 55.0% Summer 35.9C 55.2%

Fresh air Vol. Summer:100.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
4000 40 4000 30

3600 3600

3200 3200
30 20
2800 2800

2400 2400

2000 20 2000 10

1600 1600

1200 1200
10 0
800 800

400 400

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 14 0 0 0 177 0 17 38 295 430 322 600 0 1263 3142 3299

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-21-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 100.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- KIOSK 40 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 25.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 25.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 600 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-22-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- KIOSK 40 1 1 1 Shop 25.0 3.5 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 0 0 0 107 0 10 41 295 430 322 600 0 1334 471 1173 2978
9 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
10 33.9 63.4 0 0 0 148 0 14 40 295 430 322 600 0 1379 470 1247 3096
11 35.0 58.8 0 0 0 164 0 16 39 295 430 322 600 0 1397 469 1258 3124
12 35.8 55.5 0 0 0 176 0 17 38 295 430 322 600 0 1410 468 1259 3137
13 36.1 54.3 0 0 0 180 0 17 38 295 430 322 600 0 1414 468 1259 3141
*14 35.9 55.2 0 0 0 177 0 17 38 295 430 322 600 0 1411 468 1263 3142
15 35.4 57.2 0 0 0 170 0 16 39 295 430 322 600 0 1403 469 1261 3133
16 34.6 60.4 0 0 0 158 0 15 40 295 430 322 600 0 1390 470 1254 3114
17 33.6 64.4 0 0 0 143 0 14 40 295 430 322 600 0 1374 470 1236 3080
18 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
19 31.6 72.8 0 0 0 113 0 11 41 295 430 322 600 0 1341 471 1188 3000
20 30.8 75.8 0 0 0 101 0 10 41 295 430 322 600 0 1328 471 1152 2951
21 30.3 78.0 0 0 0 94 0 9 41 295 430 322 600 0 1320 471 1136 2927
22 29.9 79.5 0 0 0 88 0 9 40 295 430 322 600 0 1314 470 1115 2899

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-23-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- KIOSK 40 1 1 1 Shop 25.0 3.5 5

Indoor Outdoor
Summer 24.0C 55.0% Summer 35.9C 55.2%

Fresh air Vol. Summer:100.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
4000 40 4000 30

3600 3600

3200 3200
30 20
2800 2800

2400 2400

2000 20 2000 10

1600 1600

1200 1200
10 0
800 800

400 400

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 14 0 0 0 177 0 17 38 295 430 322 600 0 1263 3142 3299

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-24-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 100.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- KIOSK 41 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 25.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 25.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 600 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-25-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- KIOSK 41 1 1 1 Shop 25.0 3.5 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 0 0 0 107 0 10 41 295 430 322 600 0 1334 471 1173 2978
9 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
10 33.9 63.4 0 0 0 148 0 14 40 295 430 322 600 0 1379 470 1247 3096
11 35.0 58.8 0 0 0 164 0 16 39 295 430 322 600 0 1397 469 1258 3124
12 35.8 55.5 0 0 0 176 0 17 38 295 430 322 600 0 1410 468 1259 3137
13 36.1 54.3 0 0 0 180 0 17 38 295 430 322 600 0 1414 468 1259 3141
*14 35.9 55.2 0 0 0 177 0 17 38 295 430 322 600 0 1411 468 1263 3142
15 35.4 57.2 0 0 0 170 0 16 39 295 430 322 600 0 1403 469 1261 3133
16 34.6 60.4 0 0 0 158 0 15 40 295 430 322 600 0 1390 470 1254 3114
17 33.6 64.4 0 0 0 143 0 14 40 295 430 322 600 0 1374 470 1236 3080
18 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
19 31.6 72.8 0 0 0 113 0 11 41 295 430 322 600 0 1341 471 1188 3000
20 30.8 75.8 0 0 0 101 0 10 41 295 430 322 600 0 1328 471 1152 2951
21 30.3 78.0 0 0 0 94 0 9 41 295 430 322 600 0 1320 471 1136 2927
22 29.9 79.5 0 0 0 88 0 9 40 295 430 322 600 0 1314 470 1115 2899

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-26-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- KIOSK 41 1 1 1 Shop 25.0 3.5 5

Indoor Outdoor
Summer 24.0C 55.0% Summer 35.9C 55.2%

Fresh air Vol. Summer:100.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
4000 40 4000 30

3600 3600

3200 3200
30 20
2800 2800

2400 2400

2000 20 2000 10

1600 1600

1200 1200
10 0
800 800

400 400

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 14 0 0 0 177 0 17 38 295 430 322 600 0 1263 3142 3299

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-27-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 100.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- KIOSK 42 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 25.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 25.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 600 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-28-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- KIOSK 42 1 1 1 Shop 25.0 3.5 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 0 0 0 107 0 10 41 295 430 322 600 0 1334 471 1173 2978
9 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
10 33.9 63.4 0 0 0 148 0 14 40 295 430 322 600 0 1379 470 1247 3096
11 35.0 58.8 0 0 0 164 0 16 39 295 430 322 600 0 1397 469 1258 3124
12 35.8 55.5 0 0 0 176 0 17 38 295 430 322 600 0 1410 468 1259 3137
13 36.1 54.3 0 0 0 180 0 17 38 295 430 322 600 0 1414 468 1259 3141
*14 35.9 55.2 0 0 0 177 0 17 38 295 430 322 600 0 1411 468 1263 3142
15 35.4 57.2 0 0 0 170 0 16 39 295 430 322 600 0 1403 469 1261 3133
16 34.6 60.4 0 0 0 158 0 15 40 295 430 322 600 0 1390 470 1254 3114
17 33.6 64.4 0 0 0 143 0 14 40 295 430 322 600 0 1374 470 1236 3080
18 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
19 31.6 72.8 0 0 0 113 0 11 41 295 430 322 600 0 1341 471 1188 3000
20 30.8 75.8 0 0 0 101 0 10 41 295 430 322 600 0 1328 471 1152 2951
21 30.3 78.0 0 0 0 94 0 9 41 295 430 322 600 0 1320 471 1136 2927
22 29.9 79.5 0 0 0 88 0 9 40 295 430 322 600 0 1314 470 1115 2899

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-29-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- KIOSK 42 1 1 1 Shop 25.0 3.5 5

Indoor Outdoor
Summer 24.0C 55.0% Summer 35.9C 55.2%

Fresh air Vol. Summer:100.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
4000 40 4000 30

3600 3600

3200 3200
30 20
2800 2800

2400 2400

2000 20 2000 10

1600 1600

1200 1200
10 0
800 800

400 400

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 14 0 0 0 177 0 17 38 295 430 322 600 0 1263 3142 3299

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-30-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 24.0


Design room humidity in summer(%RH) 55.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 100.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 01- KIOSK 43 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 1 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 25.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 25.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 600 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-31-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 01- KIOSK 43 1 1 1 Shop 25.0 3.5 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 0 0 0 107 0 10 41 295 430 322 600 0 1334 471 1173 2978
9 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
10 33.9 63.4 0 0 0 148 0 14 40 295 430 322 600 0 1379 470 1247 3096
11 35.0 58.8 0 0 0 164 0 16 39 295 430 322 600 0 1397 469 1258 3124
12 35.8 55.5 0 0 0 176 0 17 38 295 430 322 600 0 1410 468 1259 3137
13 36.1 54.3 0 0 0 180 0 17 38 295 430 322 600 0 1414 468 1259 3141
*14 35.9 55.2 0 0 0 177 0 17 38 295 430 322 600 0 1411 468 1263 3142
15 35.4 57.2 0 0 0 170 0 16 39 295 430 322 600 0 1403 469 1261 3133
16 34.6 60.4 0 0 0 158 0 15 40 295 430 322 600 0 1390 470 1254 3114
17 33.6 64.4 0 0 0 143 0 14 40 295 430 322 600 0 1374 470 1236 3080
18 32.5 69.2 0 0 0 127 0 12 41 295 430 322 600 0 1356 471 1219 3046
19 31.6 72.8 0 0 0 113 0 11 41 295 430 322 600 0 1341 471 1188 3000
20 30.8 75.8 0 0 0 101 0 10 41 295 430 322 600 0 1328 471 1152 2951
21 30.3 78.0 0 0 0 94 0 9 41 295 430 322 600 0 1320 471 1136 2927
22 29.9 79.5 0 0 0 88 0 9 40 295 430 322 600 0 1314 470 1115 2899

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-32-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 01- KIOSK 43 1 1 1 Shop 25.0 3.5 5

Indoor Outdoor
Summer 24.0C 55.0% Summer 35.9C 55.2%

Fresh air Vol. Summer:100.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
4000 40 4000 30

3600 3600

3200 3200
30 20
2800 2800

2400 2400

2000 20 2000 10

1600 1600

1200 1200
10 0
800 800

400 400

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 14 0 0 0 177 0 17 38 295 430 322 600 0 1263 3142 3299

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-33-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 50.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 25.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 02- HANH LANG Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 2 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 19
Floor area(m2) 228.0
Depth of underground wall(m) 0.0
Ceiling height(m) 6.0 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 228.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-34-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 02- HANH LANG 1 2 1 Shop 228.0 6.0 19 Summer 475.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 407 0 0 707 0 117 626 1121 1634 2936 0 0 5288 2260 5160 12708
9 32.5 69.2 555 0 0 883 0 147 627 1121 1634 2936 0 0 5642 2261 5375 13278
10 33.9 63.4 740 0 0 1074 0 178 615 1121 1634 2936 0 0 6049 2249 5511 13809
11 35.0 58.8 962 0 0 1223 0 203 598 1121 1634 2936 0 0 6445 2232 5562 14239
12 35.8 55.5 1202 0 0 1332 0 221 581 1121 1634 2936 0 0 6812 2215 5572 14599
13 36.1 54.3 1443 0 0 1372 0 228 574 1121 1634 2936 0 0 7100 2208 5571 14879
14 35.9 55.2 1646 0 0 1345 0 223 581 1121 1634 2936 0 0 7271 2215 5588 15074
*15 35.4 57.2 1813 0 0 1277 0 212 591 1121 1634 2936 0 0 7359 2225 5576 15160
16 34.6 60.4 1887 0 0 1169 0 194 604 1121 1634 2936 0 0 7307 2238 5542 15087
17 33.6 64.4 1905 0 0 1033 0 172 614 1121 1634 2936 0 0 7167 2248 5456 14871
18 32.5 69.2 1868 0 0 883 0 147 627 1121 1634 2936 0 0 6955 2261 5375 14591
19 31.6 72.8 1720 0 0 761 0 126 627 1121 1634 2936 0 0 6664 2261 5230 14155
20 30.8 75.8 1498 0 0 652 0 108 620 1121 1634 2936 0 0 6315 2254 5061 13630
21 30.3 78.0 1258 0 0 584 0 97 620 1121 1634 2936 0 0 5996 2254 4983 13233
22 29.9 79.5 1036 0 0 530 0 88 615 1121 1634 2936 0 0 5711 2249 4884 12844

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-35-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 02- HANH LANG 1 2 1 Shop 228.0 6.0 19

Indoor Outdoor
Summer 26.0C 50.0% Summer 35.4C 57.2%

Fresh air Vol. Summer:475.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
20000 40 20000 30

18000 18000

16000 16000
30 20
14000 14000

12000 12000

10000 20 10000 10

8000 8000

6000 6000
10 0
4000 4000

2000 2000

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 15 1813 0 0 1277 0 212 591 1121 1634 2936 0 0 5576 15160 15918

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-36-
Room data(Input data)

Project name GO TAN HIEP Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 50.0
Address BIEN HOA DONG NAI Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Ho Chi Minh/Viet Nam
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 296.0
Winter ----
Max. fresh air temp.
36.1
in summer(C)
infiltration ventilation(Times/h) Summer 0.05
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name AHU 02- SHOP 14 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Heat absorbing 10mm
System No 2 Blind type No
Shading factor/OHTC 0.72/6.06
No of rooms 1

Usage of Room Shop

Ceiling board Available Lighting Fluorescent lamp(W/m2) 11.1


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 15
Floor area(m2) 74.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 2.5
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 74.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 1000 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 22:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Lighting 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-37-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

AHU 02- SHOP 14 1 2 1 Shop 74.0 3.5 15 Summer 296.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 287 0 0 229 0 22 118 885 1290 953 1000 0 3376 1408 3215 7999
9 32.5 69.2 392 0 0 287 0 28 119 885 1290 953 1000 0 3545 1409 3350 8304
10 33.9 63.4 522 0 0 348 0 34 117 885 1290 953 1000 0 3742 1407 3435 8584
11 35.0 58.8 679 0 0 397 0 38 113 885 1290 953 1000 0 3952 1403 3465 8820
12 35.8 55.5 849 0 0 432 0 42 110 885 1290 953 1000 0 4161 1400 3472 9033
13 36.1 54.3 1018 0 0 445 0 43 109 885 1290 953 1000 0 4344 1399 3472 9215
14 35.9 55.2 1162 0 0 437 0 42 110 885 1290 953 1000 0 4479 1400 3482 9361
*15 35.4 57.2 1279 0 0 415 0 40 112 885 1290 953 1000 0 4572 1402 3475 9449
16 34.6 60.4 1332 0 0 379 0 37 114 885 1290 953 1000 0 4586 1404 3454 9444
17 33.6 64.4 1345 0 0 335 0 32 116 885 1290 953 1000 0 4550 1406 3400 9356
18 32.5 69.2 1319 0 0 287 0 28 119 885 1290 953 1000 0 4472 1409 3350 9231
19 31.6 72.8 1214 0 0 247 0 24 119 885 1290 953 1000 0 4323 1409 3259 8991
20 30.8 75.8 1058 0 0 212 0 21 117 885 1290 953 1000 0 4129 1407 3154 8690
21 30.3 78.0 888 0 0 190 0 18 117 885 1290 953 1000 0 3934 1407 3105 8446
22 29.9 79.5 731 0 0 172 0 17 117 885 1290 953 1000 0 3758 1407 3044 8209

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-38-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

AHU 02- SHOP 14 1 2 1 Shop 74.0 3.5 15

Indoor Outdoor
Summer 26.0C 50.0% Summer 35.4C 57.2%

Fresh air Vol. Summer:296.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
10000 40 10000 30

9000 9000

8000 8000
30 20
7000 7000

6000 6000

5000 20 5000 10

4000 4000

3000 3000
10 0
2000 2000

1000 1000

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 15 1279 0 0 415 0 40 112 885 1290 953 1000 0 3475 9449 9921

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat

-39-