20/April/2019
Heat load sum up table (Upper:W, Lower:kcal/h)
Phong hop 1 1 1 10994 15275 16039 15 6195 6815 0.76 8 60.0 267.3 113.6
( 9455) ( 13137) ( 13793) ( 5328) ( 5860) (229.9) ( 97.7)
Phong hop 1 1 1 10994 15275 16039 15 6195 6815 0.76 8 60.0 267.3 113.6
( 9455) ( 13137) ( 13793) ( 5328) ( 5860) (229.9) ( 97.7)
Peak load of building 2 21988 30550 32078 15 12390 13629 1.51 8 120.0 267.3 113.6
( 18910) ( 26273) ( 27587) ( 10655) ( 11721) ( 229.9) ( 97.7)
SH : Sensible heat
-1-
Table of system heat load (Upper:W, Lower:kcal/h)
Cooling Heating
Sys
Time F/A vol Indoor SH Indoor Outside Total Selected Time F/A vol Indoor Outside Total Selected Humid.
-tem
[Hr] [m3/h] [W] (kcal/h) [Hr] [m3/h] [W] (kcal/h) [kg/h]
1 15 300 21988 24712 5838 30550 32078 8 300 11252 1138 12390 13629 1.51
( 18910) ( 21252) ( 5021) ( 26273) ( 27587) ( 9677) ( 979) ( 10655) ( 11721)
-2-
System table
System Room name Floor Rooms System Room name Floor Rooms
1 Phong hop 1 1
1 Phong hop 1 1
-3-
Room data(Input data)
Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 3.76 II
-4-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)
[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 50.0(%RH) [W] (kcal/h)
8 30.9 76.4 3241 0 0 0 686 148 669 420 360 1044 1000 0 6539 1029 1890 9458( 8134)
9 32.5 75.4 4191 0 0 0 712 182 766 420 360 1044 1000 0 7549 1126 2195 10870( 9348)
10 34.1 74.3 5101 0 0 0 692 216 870 420 360 1044 1000 0 8473 1230 2513 12216( 10506)
11 35.5 73.1 5902 0 0 0 637 246 960 420 360 1044 1000 0 9249 1320 2791 13360( 11490)
12 36.4 72.5 6481 0 0 0 614 265 1024 420 360 1044 1000 0 9824 1384 2984 14192( 12205)
13 36.8 72.2 6910 0 0 0 616 274 1053 420 360 1044 1000 0 10264 1413 3071 14748( 12683)
14 36.6 72.2 7346 0 0 0 594 269 1035 420 360 1044 1000 0 10673 1395 3019 15087( 12975)
*15 36.1 72.7 7701 0 0 0 570 259 1002 420 360 1044 1000 0 10994 1362 2919 15275( 13137)
16 35.3 73.1 7825 0 0 0 548 242 943 420 360 1044 1000 0 11079 1303 2742 15124( 13007)
17 34.3 74.0 7688 0 0 0 501 220 879 420 360 1044 1000 0 10873 1239 2545 14657( 12605)
18 33.1 74.9 7241 0 0 0 431 195 803 420 360 1044 1000 0 10331 1163 2308 13802( 11870)
[Heating load] Condition of indoor design temprature & humidity: 22.0(CDB) 50.0(%RH) [W] (kcal/h)
* 8 10.5 76.2 4942 0 0 0 278 406 199 0 0 0 0 0 5626 199 569 6195( 5328)
9 11.1 74.5 4685 0 0 0 264 385 189 0 0 0 0 0 5334 189 540 5874( 5052)
10 11.8 73.4 4383 0 0 0 247 360 171 0 0 0 0 0 4990 171 505 5495( 4726)
11 12.5 71.2 4082 0 0 0 231 335 162 0 0 0 0 0 4648 162 470 5118( 4401)
12 13.1 69.5 3825 0 0 0 216 314 153 0 0 0 0 0 4355 153 441 4796( 4125)
13 13.5 68.7 3653 0 0 0 206 300 145 0 0 0 0 0 4159 145 421 4580( 3939)
14 13.6 68.3 3610 0 0 0 203 296 144 0 0 0 0 0 4109 144 416 4525( 3892)
15 13.6 68.3 3610 0 0 0 203 296 144 0 0 0 0 0 4109 144 416 4525( 3892)
16 13.4 69.2 3696 0 0 0 208 303 144 0 0 0 0 0 4207 144 426 4633( 3984)
17 13.1 69.5 3825 0 0 0 216 314 153 0 0 0 0 0 4355 153 441 4796( 4125)
18 12.8 70.9 3954 0 0 0 223 325 153 0 0 0 0 0 4502 153 455 4957( 4263)
-5-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person
Indoor Outdoor
Summer 24.0C 50.0% Summer 36.1C 72.7%
Winter 22.0C 50.0% Winter 10.5C 76.2%
Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
20000 40 20000 20
18000 18000
16000 16000
30 10
14000 14000
12000 12000
10000 20 10000 0
8000 8000
6000 6000
10 -10
4000 4000
2000 2000
0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)
[Detail]
Summer 15 7701 0 0 0 570 259 1002 420 360 1044 1000 0 2919 15275 16039
Note) Total indoor heat load & selected heat load are not contained latent heat.
SH : Sensible heat
LH : Latent heat
-6-
Room data(Input data)
Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 3.76 II
-7-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)
[Cooling load] Condition of indoor design temprature & humidity: 24.0(CDB) 50.0(%RH) [W] (kcal/h)
8 30.9 76.4 3241 0 0 0 686 148 669 420 360 1044 1000 0 6539 1029 1890 9458( 8134)
9 32.5 75.4 4191 0 0 0 712 182 766 420 360 1044 1000 0 7549 1126 2195 10870( 9348)
10 34.1 74.3 5101 0 0 0 692 216 870 420 360 1044 1000 0 8473 1230 2513 12216( 10506)
11 35.5 73.1 5902 0 0 0 637 246 960 420 360 1044 1000 0 9249 1320 2791 13360( 11490)
12 36.4 72.5 6481 0 0 0 614 265 1024 420 360 1044 1000 0 9824 1384 2984 14192( 12205)
13 36.8 72.2 6910 0 0 0 616 274 1053 420 360 1044 1000 0 10264 1413 3071 14748( 12683)
14 36.6 72.2 7346 0 0 0 594 269 1035 420 360 1044 1000 0 10673 1395 3019 15087( 12975)
*15 36.1 72.7 7701 0 0 0 570 259 1002 420 360 1044 1000 0 10994 1362 2919 15275( 13137)
16 35.3 73.1 7825 0 0 0 548 242 943 420 360 1044 1000 0 11079 1303 2742 15124( 13007)
17 34.3 74.0 7688 0 0 0 501 220 879 420 360 1044 1000 0 10873 1239 2545 14657( 12605)
18 33.1 74.9 7241 0 0 0 431 195 803 420 360 1044 1000 0 10331 1163 2308 13802( 11870)
[Heating load] Condition of indoor design temprature & humidity: 22.0(CDB) 50.0(%RH) [W] (kcal/h)
* 8 10.5 76.2 4942 0 0 0 278 406 199 0 0 0 0 0 5626 199 569 6195( 5328)
9 11.1 74.5 4685 0 0 0 264 385 189 0 0 0 0 0 5334 189 540 5874( 5052)
10 11.8 73.4 4383 0 0 0 247 360 171 0 0 0 0 0 4990 171 505 5495( 4726)
11 12.5 71.2 4082 0 0 0 231 335 162 0 0 0 0 0 4648 162 470 5118( 4401)
12 13.1 69.5 3825 0 0 0 216 314 153 0 0 0 0 0 4355 153 441 4796( 4125)
13 13.5 68.7 3653 0 0 0 206 300 145 0 0 0 0 0 4159 145 421 4580( 3939)
14 13.6 68.3 3610 0 0 0 203 296 144 0 0 0 0 0 4109 144 416 4525( 3892)
15 13.6 68.3 3610 0 0 0 203 296 144 0 0 0 0 0 4109 144 416 4525( 3892)
16 13.4 69.2 3696 0 0 0 208 303 144 0 0 0 0 0 4207 144 426 4633( 3984)
17 13.1 69.5 3825 0 0 0 216 314 153 0 0 0 0 0 4355 153 441 4796( 4125)
18 12.8 70.9 3954 0 0 0 223 325 153 0 0 0 0 0 4502 153 455 4957( 4263)
-8-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person
Indoor Outdoor
Summer 24.0C 50.0% Summer 36.1C 72.7%
Winter 22.0C 50.0% Winter 10.5C 76.2%
Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
20000 40 20000 20
18000 18000
16000 16000
30 10
14000 14000
12000 12000
10000 20 10000 0
8000 8000
6000 6000
10 -10
4000 4000
2000 2000
0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)
[Detail]
Summer 15 7701 0 0 0 570 259 1002 420 360 1044 1000 0 2919 15275 16039
Note) Total indoor heat load & selected heat load are not contained latent heat.
SH : Sensible heat
LH : Latent heat
-9-