You are on page 1of 7

Aircon heat load calculation sheet

Project Name: P204 HVCTHCM


Address: 419 Hoang Quoc Viet

11/March/2021
Heat load sum up table (Upper:W, Lower:kcal/h)

Cooling Heating Heat load per area


Floor
Qty.
Sys area
Room name Fl of Indoor SH Total Selected Time Total Selected Humid. Time Cooling Heating
-tem
rooms
[W](kcal/h) [Hr] [W](kcal/h) [kg/h] [Hr] [m2] [W/m2](kcal/hm2)

P204 1 1 1 30738 62001 65101 15 190.0 342.6


( 26435) ( 53321) ( 55987) (294.7)

Peak load of building 1 30738 62001 65101 15 190.0 342.6


( 26435) ( 53321) ( 55987) ( 294.7)

SH : Sensible heat

-1-
Table of system heat load (Upper:W, Lower:kcal/h)

Cooling Heating
Sys
Time F/A vol Indoor SH Indoor Outside Total Selected Time F/A vol Indoor Outside Total Selected Humid.
-tem
[Hr] [m3/h] [W] (kcal/h) [Hr] [m3/h] [W] (kcal/h) [kg/h]

1 15 2375 30738 40999 21002 62001 65101


( 26435) ( 35259) ( 18062) ( 53321) ( 55987)

F/A : Fresh air


SH : Sensible heat

-2-
System table

System Room name Floor Rooms System Room name Floor Rooms

1 P204 1 1

-3-
Room data(Input data)

Project name P204 HVCTHCM Design room temperature in summer(CDB) 25.0


Design room humidity in summer(%RH) 50.0
Address 419 Hoang Quoc Viet Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam Total heat
Fresh air intake Air volume(m3/h person) Exchange Efficient(%)
Outer wall assembly Normal Concrete Summer 25.0 60.0
Winter ---- ----
Max. fresh air temp.
38.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name P204 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 13.0


Incandescent lamp(W/m2) 0.0
Method of
Total heat exchange
fresh air intake
No of persons 95
Floor area(m2) 190.0
Depth of underground wall(m) 0.0
Ceiling height(m) 4.5 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.6
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 190.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 1.80 III

N E S W NE SE SW NW Shade Inner Wall <1> 1.80


Outer wall length(m) <1> 12.0 0.0 12.0 12.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 22.4 0.0 24.0 9.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 12.0 3.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 2000 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-4-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

P204 1 1 1 Office 190.0 4.5 95 Summer2375.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 25.0(CDB) 50.0(%RH) [W] (kcal/h)

F/A cond. Roof Infiltration Human body Equipments Indoor heat


Outer Inner Light Fresh
Time & Floor Window Total heat load
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH

8 32.9 76.4 1148 1388 384 0 5385 446 2065 5320 7220 2865 2000 0 18936 9285 13952 42173( 36269)
9 34.5 75.4 1312 1672 461 0 6274 536 2352 5320 7220 2865 2000 0 20440 9572 16043 46055( 39607)
10 36.1 74.3 1571 2176 540 0 7058 626 2652 5320 7220 2865 2000 0 22156 9872 18215 50243( 43209)
11 37.5 73.1 1868 2933 608 0 7714 705 2916 5320 7220 2865 2000 0 24013 10136 20118 54267( 46670)
12 38.4 72.5 2207 3911 651 0 8074 756 3104 5320 7220 2865 2000 0 25784 10324 21445 57553( 49496)
13 38.8 72.2 2563 4983 671 0 8590 779 3186 5320 7220 2865 2000 0 27771 10406 22028 60205( 51776)
14 38.6 72.2 2903 6024 661 0 9132 767 3135 5320 7220 2865 2000 0 29672 10355 21682 61709( 53070)
*15 38.1 72.7 3238 6813 636 0 9127 739 3041 5320 7220 2865 2000 0 30738 10261 21002 62001( 53321)
16 37.3 73.1 3547 7286 598 0 8693 694 2867 5320 7220 2865 2000 0 31003 10087 19786 60876( 52353)
17 36.3 74.0 3788 7349 549 0 7709 638 2682 5320 7220 2865 2000 0 30218 9902 18444 58564( 50365)
18 35.1 74.9 3902 7002 491 0 6250 570 2457 5320 7220 2865 2000 0 28400 9677 16817 54894( 47209)

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-5-
Heat load graph
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person

P204 1 1 1 Office 190.0 4.5 95

Indoor Outdoor
Summer 25.0C 50.0% Summer 38.1C 72.7%

Fresh air Vol. Summer:2375.0m3/h

Outdoor Outdoor
Summer temperature Winter temperature
(W) (C) (W) (C)
70000 40 70000 20

63000 63000

56000 56000
30 10
49000 49000

42000 42000

35000 20 35000 0

28000 28000

21000 21000
10 -10
14000 14000

7000 7000

0 0
1 6 12 18 24 Time(Hr) 1 6 12 18 24 Time(Hr)

[Detail]

Roof Infiltration Human body Equipments Total Selected


Outer Inner Light Fresh
Time & Floor Window heat heat
wall wall -ing air
(W) Ceiling SH LH SH LH SH LH load load

Summer 15 3238 6813 636 0 9127 739 3041 5320 7220 2865 2000 0 21002 62001 65101

Winter -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

SH : Sensible heat
LH : Latent heat