Aircon heat load calculation sheet

Project Name: P204 HVCTHCM


Address: 419 Hoang Quoc Viet

11/March/2021
Heat load sum up table (Upper:W, Lower:kcal/h)

Cooling Heating Heat load per area


Floor
Qty.
Sys area
Room name Fl of Indoor SH Total Selected Time Total Selected Humid. Time Cooling Heating
-tem
rooms
[W](kcal/h) [Hr] [W](kcal/h) [kg/h] [Hr] [m2] [W/m2](kcal/hm2)

P204 1 1 1 30738 62001 65101 15 190.0 342.6


( 26435) ( 53321) ( 55987) (294.7)

Peak load of building 1 30738 62001 65101 15 190.0 342.6


( 26435) ( 53321) ( 55987) ( 294.7)

SH : Sensible heat

-1-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

P204 1 1 1 Office 190.0 4.5 95 Summer2375.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 25.0(CDB) 50.0(%RH) [W] (kcal/h)

F/A cond. Roof Infiltration Human body Equipments Indoor heat


Outer Inner Light Fresh
Time & Floor Window Total heat load
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH

8 32.9 76.4 1148 1388 384 0 5385 446 2065 5320 7220 2865 2000 0 18936 9285 13952 42173( 36269)
9 34.5 75.4 1312 1672 461 0 6274 536 2352 5320 7220 2865 2000 0 20440 9572 16043 46055( 39607)
10 36.1 74.3 1571 2176 540 0 7058 626 2652 5320 7220 2865 2000 0 22156 9872 18215 50243( 43209)
11 37.5 73.1 1868 2933 608 0 7714 705 2916 5320 7220 2865 2000 0 24013 10136 20118 54267( 46670)
12 38.4 72.5 2207 3911 651 0 8074 756 3104 5320 7220 2865 2000 0 25784 10324 21445 57553( 49496)
13 38.8 72.2 2563 4983 671 0 8590 779 3186 5320 7220 2865 2000 0 27771 10406 22028 60205( 51776)
14 38.6 72.2 2903 6024 661 0 9132 767 3135 5320 7220 2865 2000 0 29672 10355 21682 61709( 53070)
*15 38.1 72.7 3238 6813 636 0 9127 739 3041 5320 7220 2865 2000 0 30738 10261 21002 62001( 53321)
16 37.3 73.1 3547 7286 598 0 8693 694 2867 5320 7220 2865 2000 0 31003 10087 19786 60876( 52353)
17 36.3 74.0 3788 7349 549 0 7709 638 2682 5320 7220 2865 2000 0 30218 9902 18444 58564( 50365)
18 35.1 74.9 3902 7002 491 0 6250 570 2457 5320 7220 2865 2000 0 28400 9677 16817 54894( 47209)

F/A : Fresh air


SH : Sensible heat
LH : Latent heat