You are on page 1of 1

PROJECT: HCL COMMERCIAL COMPLEX, LUCKNOW

Cooling load analysis

Original with DGU


Heat load estimate (Summer & Monsoon) MAY AUG
Client HCL Space used for Convenience store City name Lucknow
Engineer Floor Level GF Date of print
Enquiry number Remarks Date of Heatload

Room Length (Ft.) Width(Ft.) Heigth(Ft.) Area(SFt.) Volume(Cft.) Room Num. Total Rooms Latitude Sun Time
0 0 12 3497 41964 26.52 16.00
DB WB RH DP GR/Lbs Enthalpy
F F % F Btu/Lb
Temp rise = (1 - BF) * (Rm DB - ADP) Summer > 109 79 26 68 102 43
Dehumidified Cfm = ERSH / (1.08 * Temp rise) Monsoon> 94 83 64 79 152 47.5
Outlet td. = RSH / (1.08 * De.Hum CFM) Room > 75 64.4 60 59 75 29.53
Supply air Cfm = RSH / (1.08 * Desired td.) Diff > 34 27 13.47

Item Area / Qty Sun gain monsoon Factor Summer Monsoon Outdoor air Details
SFt. / Ft. TD TD Btu/Hour Btu/Hour
(Solar heat gain through Glasses) Fresh air Cfm 'Fresh air Changes
East 12 11 0.5 0.00 0.00 944.64
West 82 164 165 0.5 6724.00 6765.00 7.5
South 840 12 13 0.5 5040.00 5460.00 0.12
North 994 14 11 0.5 6958.00 5467.00
S.East 12 11 0.5 0.00 0.00
SW 100 127 0.5 0.00 0.00
NE 12 11 0.5 0.00 0.00
NW 123 100 0.5 0.00 0.00
SKY LIGHT 123 107 1 0.00 0.00
Solar heat & Transmission gain Through walls & roof) (ESHF) (ADP) (Dehum ris(Dehum CFM)(Supply CFM) (Bypass)
East 0 36 21 0.12 0.00 0.00 0.93 52 19.55 9024.38 9024.38 0
West 38 374 30 15 0.12 1346.40 673.20 0.89 52 19.55 7571.41 9024.38 1452.98
South 93 276 34 19 0.12 1126.08 629.28
North 93 122 22 7 0.12 322.08 102.48
S.East 0 36 21 0.12 0.00 0.00
SW 0 32 17 0.12 0.00 0.00
NE 0 28 13 0.12 0.00 0.00
NW 0 24 9 0.12 0.00 0.00
Roof sun 3497 50 35 0.12 20982.00 14687.40
Roof sun ( Metal ) 60 45 0.5 0.00 0.00
(Transmission gain - Except walls & Roof)
Ceiling 20 15 0.4 0.00 0.00
Floor 20 15 0.4 0.00 0.00
Gl Exposed ( 1916 35 20 0.55 36883.00 21076.00
Gl Exposed (sky light) 0 35 20 1.1 0.00 0.00
Partition (Gl) 30 15 1.1 0.00 0.00
Partition–wall 26 312 20 15 0.4 2496.00 1872.00
Partition–toilet 0 8 8 0.4 0.00 0.00
(Internal Heat gain)
People 70 240 16800.00 16800.00
Equipment 3 10491 3.412 1 35795.29 35795.29
Lights 2 6994 3.4 1.25 29724.50 29724.50
Sub Total 164197.35 139052.15
S.Factor % 5 8209.87 6952.61
Room Sensible Heat 172407.22 146004.76
SA Duct % 2.5 4310.18 3650.12
SA Fan gain 5 8620.36 7300.24
Fresh air 944.64 0.15 34 1.08 5203.08 2907.60
Reheat
Effective Room Sensible Heat 190540.84 159862.72
Latent Heat
People 70 160 11200.00 11200.00
Sub Total 11200.00 11200.00
S.Factor % 5 560.00 560.00
Room latent Heat 11760.00 11760.00
Fresh air 944.64 0.15 77 27 0.68 2601.54 7419.20
Effective Room latent Heat 14361.54 19179.20
Effective Room total Heat 204902.38 179041.92
Outdoor Air Heat
F.air Sen 944.64 0.85 19 34 1.08 29484.10 16476.41
F.air Lat 944.64 0.85 77 27 0.68 14742.05 42042.15
RA Gain 0.00 0.00
RA Fan Gain
Grand Total 249128.53 237560.48
Tons 20.76 19.80

MVAC CONSULTING ENGINEERS: DEW POINT SERVICES CONSULTANTS LLP


AN ISO 9001-2008 CERTIFIED COMPANY